9099ceb1af |
SAFETY-31: the grid is 42, not 90, and the wrong number was in the failure text
checks / unit (pull_request) Successful in 6m27s
Review reproduced every figure in both PRs except one, and rejected on it. ⚠️ "0 of 90 GAINS x SPLITS combinations produce opposing shares" - the SUBSTANCE is right and review re-measured it, but the DENOMINATOR is invented. sitesim.py declares GAINS with 7 entries and SPLITS with 6: the grid is 42. 90 is not even divisible by 7, so no reading of "GAINS x SPLITS" reaches it. It is almost certainly TEST-20`s RUN count (84 + 6), which is a different quantity that happened to be nearby. ⚠️ AND THE WORST COPY OF IT WAS INSIDE THE `PRECONDITION FAILED` TEXT, so the next engineer to see this scenario go red would have been handed an unreproducible measurement as their diagnosis - the exact defect class this campaign exists to correct, in the failure path where it does the most harm. Corrected in all seven places. At the failure-text site the denominator is now `len(GAINS) * len(SPLITS)`, computed rather than typed, so it cannot drift from the grid again - the same fix test_translations.py already took. Also N3: a missing blank line was going to render the S3 and M19 paragraphs as one in DECISIONS. Re-run after the change: `inject.py two_master_circulation` PASS in 35 s, norig, no rig lock taken. Add-on suite 26 files, all pass. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
295a2aedb6 |
SAFETY-31 AC 4: the alarm's attribution was graded by nothing, and a mutation proved it
checks / unit (pull_request) Successful in 6m27s
`pos, neg = opposing(...)` -> `([], [])` in main.py's `check_circulating()`
(-102 B) deletes the "Right now X is discharging while Y charges" clause from
the operator notification, and SURVIVED ALL 26 FILES. The commit that shipped
this card claimed "18 mutations, all RED"; the ledger has no entry for the
attribution, and this is that entry.
It is not dead code. Ledger M18 - the whole `await check_circulating()` call
removed - is red on four checks, so the function runs. The three checks on the
notification asserted METER CANNOT SEE, CONTROL HAS BEEN STOPPED and `isolator`,
and never an inverter name. `circulation.py`'s own docstring calls that sentence
the first thing somebody woken by this alarm needs and "impossible to
reconstruct from the number alone".
test_watchdog.py section 6a closes it on a fixture that can tell three failures
apart:
* the roster is ["garage", "shed", "cellar"] - operator names, none of them
`UNIT_A`, for test_maintenance.py section 11's reason: on a fixture whose
names are the module's own constants a check cannot tell the roster from
the constant;
* the site is run TWICE, MIRRORED, so the sentence is not symmetric and a
pos/neg swap is a different red from a deletion;
* a third pack rests at 5 W, so the floor that stops a pack in standby being
named as a participant in a 6 kW loop is graded too.
Mutations, on a tree with no __pycache__ mounted :ro into the checks image:
M20 pos, neg = opposing(...) -> ([], []) -102 B RED (2 checks)
M21 pos and neg exchanged +0 B RED (3 checks)
M22 opposing(..., min_w=cfg.min_w/2.0) -> 0.0 -25 B RED (3 checks)
26/26 files green with the block in place.
AND A DISCLOSURE, WHICH IS THE UNCOMFORTABLE HALF. DECISIONS section 3 records
that the 924-run campaign behind `circulation_w: 700` and `circulation_hold_s:
75` used a harness that is not committed in either repository. Two further
sweeps have now been run and no two of the three agree: peaks of 1700 W, 2750 W
and 1048 W, and worst-continuous figures above 700 W of 5.0 s, 15.0 s and 5.0 s.
That is NOT evidence of fabrication and is not reported as any. The committed
sweep measures why the spread is that wide: on one grid, changing only the
plant model and the write-stagger set, the worst legitimate peak is 1048 W, or
2250 W, or 0 W. The plant and the stagger are TERMS of the number. What the
spread does establish is that the claim cannot be adjudicated while the
instrument is missing.
The window argument survives and is now committed - all three sweeps trip zero
times, on 924 + 48 + 840 non-faulty runs. The threshold CURVE does not survive
as stated: `505.0 s at 100 W`, which is what the "knee at 400 W" argument rests
on, is 10.0 s on the committed grid. The curve still falls with the threshold,
so the knee is real in direction; its depth is established by nothing anybody
can run, and this commit says so rather than repeating it. The overclaiming
comment at test_watchdog.py's 1700 W fixture ("the worst single transient the
rig can produce") is replaced with what the fixture can support.
The committed, re-runnable half is admin/goodwe's `two_master_circulation`,
opened as a separate PR against that repository.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
bb469163a6 | Merge pull request 'UX-04: nothing was hidden, the defaults pin was never built, and CFG-04 was closed by UX-02' (#66) from UX-04 into release/1.0 | ||
|
|
477911afa1 |
UX-04: the 59 was computed and then graded against "> 15"
checks / unit (pull_request) Successful in 6m22s
Review approved and found four things worth fixing. Three are cosmetic; the fourth is the same defect this card is about, one level up. ⚠️ THE FLOOR WAS PRINTED AS 59 AND ASSERTED AS `> 15`. So a manifest change dropping the required count to 20 would have passed while the sentence beside it still said 59 - a number displayed but not graded, which is exactly what let UX-01's AC 3 survive review in the first place, and exactly the shape `test_translations.py` was already fixed for. Now DERIVED and graded in two separate assertions, because they are two different claims: 1. `_EXPECT_REQ = len(schema) - len(_OPTIONAL)`, where optional is Supervisor's own rule - a `?` suffix, plus `inverters` because `UiOptions` marks a list optional - asserted EQUAL to Supervisor's required count. The printed number is computed, so it cannot go stale. 2. ⚠️ AND THE WITHDRAWAL'S PREMISE, SEPARATELY. The equality alone is not enough and I checked why: both sides read the same `?` convention, so marking a key optional moves BOTH and it stays green - measured, by making `slew_w` optional and watching it pass. That grades Supervisor agreeing with us, NOT the thing AC 3 was withdrawn for. The second assertion grades the premise: the floor is still far above the ~15 AC 3 asked for, and if it ever is not, the withdrawal needs re-arguing rather than re-asserting. Driven, both directions, against the real 2026.08.0 image: clean PASS "floor is DERIVED: 71 schema keys minus 12 optional ones is 59, and Supervisor's own required flag agrees" premise threshold 15 -> 40 FAIL "the floor of 59 is still far above the ~40 AC 3 asked for" Also: a dangling reference to `DECISIONS/UX-04-hiding-and-the-deepmerge.md`, which was never the filename shipped, and `DOCS.md` still saying section F "prints" what it now grades. Not changed, and review agreed both are disclosed rather than defects: the pair-keyed ledger cannot see a SECOND site for a pair it already holds (the site count can grow while the pair set cannot), and the probe's assertions run by hand rather than in CI because they need the Supervisor image - the same status as before this card, not a regression. Suite: 27 files, all pass. Probe: all cases passed on ghcr.io/home-assistant/amd64-hassio-supervisor:2026.08.0, --network none. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
21f22b393a |
UX-04: nothing was hidden, the defaults pin was never built, and CFG-04 was closed by UX-02
checks / unit (pull_request) Successful in 6m20s
UX-01's three unmet acceptance criteria, closed out. It shipped in 0.7.0 and is LIVE, so all three describe the running install. No behaviour, no schema and no default moves here: config.yaml, translations/ and every module under app/ are byte-identical to |
||
|
|
6e7b23388c | Merge pull request 'PKG-13: the no-op half of the pre-deploy check has never run as documented' (#65) from PKG-13 into release/1.0 | ||
|
|
1ba35f9c99 |
PKG-13: one safe.directory flag, not two, and the tighter of the pair
checks / unit (pull_request) Successful in 6m19s
Review found `-c safe.directory={where}` and `-c safe.directory=*` set on the
same invocation, the specific value redundant once the wildcard is present.
Dropped the WILDCARD rather than the specific path, which is the opposite of
the suggestion and the tighter end of it: `_git()` always runs `-C where`, so
the only repository it ever reads is the one it was pointed at, and naming that
one path grants exactly the trust the tool needs. `*` granted trust to every
repository on the machine for the lifetime of each subprocess - harmless for
read-only `log`/`show` with no tty, as review measured, but broader than the
job.
Verified after the change: the documented container invocation still runs BOTH
halves and reports `no runtime change since the last bump` / `CLEARED for
deploy`, so the fix this branch exists for is intact.
Suite: 26 files, all pass.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
0b653c35a6 |
PKG-13: the no-op half of the pre-deploy check has never run as documented
checks / unit (pull_request) Successful in 6m19s
⚠️ THE INVOCATION ON PKG-09's CARD AND IN THE TOOL'S OWN DOCSTRING RUNS ONLY HALF THE CHECK. The container runs as uid 0 against a checkout owned by the operator, and git refuses that: fatal: detected dubious ownership in repository at '/w/goodwe-addon' `_git` returned non-zero, `last_version_change()` returned None, and the silent-no-op check - THE REASON PKG-09 EXISTS - reported SKIPPED. Measured, on the documented command against release/1.0: ⚠️ SKIPPED: could not ask git what changed since the last bump; the no-op check is INCONCLUSIVE, not clean NOT CLEARED and with `--user $(id -u):$(id -g)`, unchanged otherwise: no runtime change since the last bump - nothing to deploy CLEARED for deploy. ⚠️ THE TWO HALVES WERE MUTUALLY EXCLUSIVE ACROSS THE TWO DOCUMENTED ENVIRONMENTS. In the container the validator ran and git skipped; on a bare host git ran and the validator skipped on aiohttp. NEITHER DOCUMENTED COMMAND RAN BOTH. The pre-0.9.0 clearance was sound only because it happened to be driven as two separate invocations. ⚠️ AND IT WAS INVISIBLE IN THE ONLY CASE ANYONE HAD RUN. `main()` consults the git result only when `shipped == deployed`; every real run so far compared 0.7.0 against 0.9.0 and printed its verdict without ever needing git. FIXED IN `_git()` WITH `safe.directory`, NOT BY DOCUMENTING `--user`. The tool should be correct however it is invoked rather than requiring every future caller to remember a flag; the read is read-only, on a repository the operator is about to deploy from. ⚠️ WHY THE TESTS COULD NOT SEE IT, WHICH IS THE FINDING BEHIND THE FINDING. `test_version_gate.py` invokes the gate with `sys.executable` against fixtures it creates as its own uid, so no fixture could ever meet an ownership mismatch. MUTATION.md habit 4 in a fourth shape, inside the file written to prevent it - after the pickaxe bug, after the one-bump history, after the filter-only survivor. Two fixtures added: - a directory that is NOT a git repository, so the lookup genuinely fails: the gate must exit 2 saying INCONCLUSIVE and must NOT say CLEARED. - ⚠️ THE EXIT CODES PINNED BY VALUE, NOT BY TRUTHINESS. `returncode != 0` is satisfied by collapsing NOT-CLEARED into REFUSED, which review found the earlier draft could not tell apart. 1 says "this deploy is wrong"; 2 says "nobody checked". Driven: collapsing 2 into 1 now goes red on exactly that check. Suite: 26 files, all pass. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
d0633665c9 |
Merge pull request 'PKG-12: bump 0.8.0 -> 0.9.0, so the five merges behind it can actually ship' (#64) from PKG-12 into release/1.0
PKG-12: bump 0.8.0 -> 0.9.0, so the five merges behind it can actually ship |
||
|
|
8e3734f5ea |
PKG-12: the live options WERE checked, and the changelog said they were not
checks / unit (pull_request) Successful in 6m17s
Review approved the bump and, in doing so, dated one of its own paragraphs.
When this section was written the pre-deploy check had not been run and the
changelog said so, correctly. The owner then exported the reference install's
options and the check cleared, which makes the shipped sentence false in the
release notes an operator reads at the hardware.
Replaced with what was measured, twice:
stored blob as-is exit 0, CLEARED
effective post-upgrade config exit 0, CLEARED
(the 70 stored keys merged OVER 0.9.0's
71 config.yaml defaults)
max_w 5000, slew_w 400, rule-10 ceiling 555.6 W.
⚠️ AND THE SECOND CHECK IS NOT CEREMONY. The stored blob has 70 keys, not 71:
`delivery_hold_s` arrived with SAFETY-42 in 0.8.0, so a box running 0.7.0 has
never stored it, and it is REQUIRED in the schema with no trailing `?` - the
exact shape that becomes exit 78. It resolves to its `options:` default of 185
because the Supervisor sets `App.options = deepmerge(defaults, stored)`, which
`tools/supervisor_selfapi_probe.py` §D pins against a real Supervisor image.
Review re-derived that independently rather than taking the reasoning on trust.
"Your saved settings are valid" and "what the box will actually run is valid"
are different questions, and only the second one is the one being asked before
a deploy.
Suite: 26 files, all pass.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
86bdf49332 |
PKG-12: bump 0.8.0 -> 0.9.0, so the five merges behind it can actually ship
checks / unit (pull_request) Successful in 6m14s
⚠️ MINOR FOR NEW FUNCTIONALITY, NOT FOR A BREAK, AND THAT DISTINCTION IS
CHECKED RATHER THAN ASSERTED. PKG-07 was minor because a config that started on
0.7.0 could be REFUSED on 0.8.0. Nothing of that kind is true here:
- `options:` and `schema:` hold 71 top-level keys on both
|
||
|
|
fcaa72418d |
Merge pull request 'PKG-09: refuse a deploy that would be a no-op, or that the add-on would reject' (#63) from PKG-09 into release/1.0
PKG-09: refuse a deploy that would be a no-op, or that the add-on would reject |
||
|
|
04b3330def |
PKG-09: refuse a deploy that would be a no-op, or that the add-on would reject
checks / unit (pull_request) Successful in 6m16s
Two ways a deploy of this add-on has gone wrong, and the Supervisor reports both as success. THE SILENT NO-OP. The Supervisor keys the built image by `version:`, so `ha apps update` against an unchanged version installs nothing and says it worked. PKG-06 recorded this on 2026-09-05 with six merges behind an unbumped version; PKG-07 recorded it again on 2026-09-06 with six. Both times a human noticed. Nothing else was going to. THE REFUSED CONFIG. A config the shipped validator rejects is SystemExit(78) - the add-on does not start. ⚠️ AND THE INGRESS PANEL GOES WITH IT, because the add-on serving it is not running, so recovery means the Supervisor UI. ⚠️ IT CAUGHT A LIVE ONE ON ITS OWN PULL REQUEST. Run against release/1.0 while this branch was in review: version 0.8.0 on both sides with UX-02's and OPT-09's runtime commits already merged behind it. The class this exists to catch had recurred, the same day, unnoticed - which is the argument for PKG-10, a non-required post-merge check, since this script only helps someone who remembers to run it. ⚠️ THE FIRST VERSION WAS BROKEN ON EVERY REAL REPOSITORY AND ITS TESTS COULD NOT SEE IT. The "when did the version last change" lookup was `git log -S`, the pickaxe, which finds commits that change the COUNT of a literal string. A bump edits the line IN PLACE, so the count never moves and it returned only the commit that first INTRODUCED the line. Measured here: -S -> |
||
|
|
fdb3b69397 |
Merge pull request 'OPT-09: the weights parameter nothing ever passed, and what it cannot do' (#62) from OPT-09 into release/1.0
OPT-09: the weights parameter nothing ever passed, and what it costs SAFETY-42 |
||
|
|
cab267c4f3 |
OPT-09: the 6500 W window is a bound the ratings never let the site reach
checks / unit (pull_request) Successful in 6m10s
Round-2 non-blocking findings, both fixed. ⚠️ THE WINDOW FIGURE WAS ARITHMETIC NOBODY HAD RUN. `min_w * (w_A + w_B) / w_B` = 6500 W is correct about `_fill()`'s PROPORTIONAL regime and is not a reachable steady state: the healthy pack's own 5000 W rating binds first. SWEPT on part 8b's own fixture, reproduced rather than transcribed: load equal OPT-09 site target A B 1000 199/200 0/200 1080 997 83 2000 199/200 0/200 2170 2003 167 3000 199/200 0/200 3250 3000 250 4000 199/200 4/200 4340 4006 334 4500 199/200 8/200 4890 4514 376 4900 199/200 41/200 5320 4911 409 <- largest suppressed 5000 199/200 195/200 8000 5000 3000 <- A at its rating 6000 199/200 195/200 8000 5000 3000 So the alarm returns BELOW the formula bound, not above it, and the largest site target reached with the wedged unit still under the 500 W threshold is 5320 W - not 6500. The equal-weights "suppressed below 1000 W" bound is unreachable for the same reason: the equal arm names the wedged unit 199/200 at EVERY load swept, 1000 W included. The formula and its check are kept, because the mechanism they state is right and it is the mechanism that generalises to other ratings. What was wrong was the sentence around them, in four places, implying the site passes through the bound. Each now carries the sweep and says the rating binds first. ⚠️ THIS NUMBER CAME FROM THE REVIEW, NOT FROM THE BRANCH, and was adopted in good faith by the implementer. The reviewer found it in round 2 and said so. That is worth recording: a figure arriving from a trusted reviewer got less scrutiny than one written by the author, and PROC-01's eight fabricated numbers in two days is now nine. The rule that catches it is the same either way - run it before you ship it. Also: the DECISIONS header's base sha, stale for the third time ( |
||
|
|
8d83ef0dfb |
OPT-09: the weights DO move on a wedged unit, and that narrows SAFETY-42
checks / unit (pull_request) Successful in 6m11s
B1, the blocking review finding. §5 of the decision said:
"A wedged unit reads a healthy SoC, so no envelope closes and no weight
moves - OPT-09 cannot see it at all."
The first clause is true and is about the ENVELOPE. The second clause is
FALSE, and it was load-bearing for the claim that OPT-09 and SAFETY-42 meet
without overlapping. A weight is a function of a pack's ENERGY HEADROOM, not
of what the pack delivers, so a wedged unit's weight moves whenever its
headroom differs from its sibling's - the ordinary case this card exists to
exploit. And delivery.delinquent() (app/delivery.py:484, threshold at :531)
names a unit only while its short_by() gap exceeds min_w = Tuning.saturation_w
= 500 W in ABSOLUTE WATTS. Shrinking the share shrinks the gap below the
threshold, and the alarm stops firing on a unit still delivering nothing.
So the seam, stated accurately: OPT-09 stops the ask AND narrows SAFETY-42's
detection window for a low-headroom unit. That is a DETECTION REGRESSION at
N=2. It is disclosed here, not fixed: making delinquent() relative to the ask
rather than absolute is SAFETY-42's code and a design change, filed as its own
card.
1. THE CORRECTION, in the three places that carried the claim
* DECISIONS/OPT-09-soc-aware-weights.md §5 - rewritten. States the seam
accurately, quotes the sentence it is replacing, carries the measured
rows and the window arithmetic, and names the residual in the same voice
as SAFETY-13's "2 of 272" and SAFETY-42's "the discriminator does not
exist". Also drops "they meet and do not overlap" from the opening.
* app/packshare.py - a new section in the module docstring, immediately
after "weights are a comfort choice for stability and not for delivery",
which is where the over-read starts.
* CHANGELOG.md - a new paragraph in the SAFETY-42 entry, ending on the
operator-facing sentence: a wedged inverter with less energy headroom
than its sibling can now go unreported at ordinary house loads.
test_packshare.py part 8's closing check and its "what this file cannot
see" list repeated the same false clause; both now say the ENVELOPE cannot
reach a wedged unit and point at part 8b for what the WEIGHTS do to it.
2. THE GRADED CHECK - test_packshare.py part 8b, 6 named checks
The reviewer's probe, reproduced: real compute(), real plan(), real
packshare.weights(), real delivery.account(), real delivery.delinquent();
the only model is the plant (A obeys within one cycle inside its rating,
B accepts its share and delivers 0 W). Unit B is WEDGED at 15 % against
its own 10 % floor, so envelope() does not close and account() explains
nothing - a SAFETY-42 true positive by that card's own definition, which
a PRECONDITION check asserts before anything is concluded from it.
load 1500 W, B wedged at 15 %, equal weights named on 199/200 cycles,
site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
load 1500 W, B wedged at 15 %, OPT-09 weights named on 0/200 cycles,
site target +1630 W, shares a+1505, b+125, grid -5 W, named=(nobody)
load 6000 W, B wedged at 15 %, equal weights named on 199/200 cycles
load 6000 W, B wedged at 15 %, OPT-09 weights named on 195/200 cycles
suppression window: equal weights, site target < 1000 W; OPT-09
weights, site target < 6500 W of a 9600 W site
THE CHECKS ASSERT THE CURRENT, UNFLATTERING BEHAVIOUR ON PURPOSE - that
the weighted arm names NOBODY where the equal arm names the wedged unit.
A check asserting the alarm still fires would fail, and papering over it
would be worse than the original defect. The 6000 W row is there so the
part is not pinning "the weighted arm never names anybody": past the
healthy pack's own rating, _fill()'s last-resort pass hands the wedged
unit 3000 W and both arms name it. The window is real and it has an edge.
MUTATION - packshare.weights() keeps its shape and forces every weight to
1.0 (M11 in part 11's table, which now has 11 rows). RUN on a purged tree
with python3 -B, not reasoned about:
load 1500 W, B wedged at 15 %, equal weights named on 199/200 cycles,
site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
load 1500 W, B wedged at 15 %, OPT-09 weights named on 199/200 cycles,
site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
load 6000 W, B wedged at 15 %, OPT-09 weights named on 199/200 cycles,
site target +4000 W, shares a+2000, b+2000, grid +4000 W, named=[b]
suppression window: equal weights < 1000 W; OPT-09 weights < 1000 W
FAIL AND WITH OPT-09's WEIGHTS IT IS NAMED ON NONE OF THE 200 [...]
FAIL ...and the arithmetic behind it, stated as a window [...]
FAIL AND IT IS NOT THAT THE WEIGHTED ARM NEVER NAMES ANYBODY [...]
test_packshare.py exits 1. Restored: exits 0.
3. THREE PROC-01 PROSE DEFECTS
* DECISIONS/OPT-09-soc-aware-weights.md:3 said "Base: release/1.0 @
464d398". The branch was rebased; git merge-base HEAD
|
||
|
|
f8e501393f |
OPT-09: the weights parameter nothing ever passed, and what it cannot do
`allocator.plan()` has taken a `weights` argument since ALLOC-01 and NOTHING
had ever passed one - main.py called `resolve()` without it and the arbiter
defaulted it to 1.0 per unit - so the site target was split 50/50 regardless
of what either pack could do. Two things now feed it, and they are different
kinds of thing:
* a `pack` UNIT claim at P_SAFETY that CLOSES a unit's envelope at its own
`bms_soc_floor` or at 100 % - a PERMISSION, obeyed absolutely, so an empty
pack is not asked to discharge and its share goes to the sibling;
* SoC-aware weights by ENERGY headroom in kWh - a PREFERENCE, which
`_fill()`'s last-resort pass will override the moment the sibling saturates.
Measured (test_packshare.py part 8): at a load one pack cannot cover, the
weighted arm and the shipped arm command the IDENTICAL watts into an empty pack
and deliver the IDENTICAL watts. Only the envelope stops the ask, and what it
buys is not delivery - it is a reported `unmet_w` where the record used to read
impeccable. Weights are a comfort choice for STABILITY and NOT for DELIVERY.
Also: an optional per-entry `capacity_kwh` (schema change, all-or-nothing across
the roster, rule 9 refuses a partial one); per-pack arbitrage sizing, with the
sell side's no-op stated rather than hidden; and a 0 W trade refused by name,
because a 0 W arbitrage claim is a park order that outranks the loop.
SAFETY-42 and this card meet at one hazard from opposite sides - OPT-09 stops
the site ASKING a pack whose SoC says it cannot deliver, SAFETY-42 alarms when a
pack that said it could does not - and its end-to-end fixture moved as a result.
Its finding is unchanged and is now stated on the two quantities its rejected
discriminator actually reads.
Not filed at all at a roster of one: at N=1 every source routes to the site, so
the interval would bound the SITE TARGET, and SAFETY-25's decided Option A
stands untouched on the live install.
⚠️ INVERTER B DOES NOT EXIST. Its 4600 W / 20.48 kWh / 10 % are FROM DATASHEET
AND SERIAL, and `sim/plantsim.py`'s INVERTER_B is inverter A copied
(`measured=False`), so every two-inverter figure here is arithmetic or two
copies of A. No hardware was touched.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
3d2999337d |
Merge pull request 'UX-02: the validator's refusals, next to the field, before the save' (#61) from UX-02 into release/1.0
UX-02: the validator refusals, next to the field, before the save |
||
|
|
bcee2356e0 |
UX-02: pin both halves of the max_w fix, because neither was graded
checks / unit (pull_request) Successful in 6m16s
Review of the fix commit found that BOTH halves reverted with the whole 24-file suite still green - including the half that turns a crash into a SILENT ACCEPTANCE, which was my own wrong first attempt at this fix. A fix nothing grades is a fix that comes back. MUTATION.md habit 4. ⚠️ AND THE OBVIOUS PIN HAD THE SAME DEFECT IT WAS WRITTEN TO CATCH. "problems_ and_ranges does not raise" is ALSO satisfied by the backstop swallowing the exception and returning [] - the silent acceptance half two exists to prevent. MEASURED: with both halves reverted, every max_w check reported `ok` and only the forced-boom pins went red. So half one is now pinned on `build_roster` ITSELF, where the backstop cannot answer for it. That is the same defect as the one being fixed - a check whose data cannot reach the failure it names - written into the check for it, and it is the twelfth recorded instance. New section 2b of test_selfconfig.py: - `_flat_max_w` agrees with `_number()` across ten shapes, so composition tolerates exactly what rule 9 tolerates. - ⭐ `build_roster(max_w="")` does not raise - half one, standing alone. - a cleared box answers with the validator's own verdict; an unparseable one answers "max_w 'abc' is not a number". - ⭐ clearing max_w on the LIVE shape (5000 W rail, explicit slew_w 400) is REFUSED by rule 10 "against a site rail of 2000 W". `unit_caps_indexed` reads the flat rail through the same `_number`, so the rail collapses in lockstep and rule 10 catches the collapse. This is what makes the fix safe rather than merely non-crashing: the box cannot be emptied into a quietly halved rail. - ⭐ the backstop never returns an empty list, forced by monkeypatching build_roster to raise; and the patch is shown undone. DRIVEN, all four arms through the real harness: clean rc=0 fails=0 revert half one rc=1 fails=2 (_flat_max_w -> bare float()) revert half two rc=1 fails=2 (backstop returns [] again) revert BOTH rc=1 fails=3 Each half is caught on its own, which is the property the earlier draft lacked. Suite: 24 files, all pass. Not addressed here, filed instead: N3 (`/config/` 404s), N4 (undeclared keys on a hand-crafted POST, which the page cannot produce and Supervisor drops), N5 (saving pins every default as an explicit option), the page reporting "would start" for a blob Supervisor's own schema refuses, and 2000.0 hardcoded in three places that agree today with nothing pinning them together. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
2bb07ccdde |
UX-02: the panel was weaker than the startup gate for one field
checks / unit (pull_request) Successful in 6m9s
Applying review finding N1, which was non-blocking because it fails closed, and
N2, which is a fabricated number.
N1. Clearing the `max_w` box answered HTTP 500 on a non-JSON body, which the
page rendered as "cannot reach the add-on" - untrue, and for the most prominent
limit field's most likely transient state. The cause was a disagreement between
two files that `inverter.py`'s own docstring says to keep in step:
validate.py `_number()` reads "" as "use the default", so rule 9 saw 2000
and was content
inverter.py line 515 did a bare `float(opts.get("max_w", 2000))`, which
raises ValueError on ""
So a shape rule 9 TOLERATED could not be composed at all - the docstring's rule
inverted. The roster path never had this: `_entry_max_w` already guards. Only
the flat single-inverter path did. `_flat_max_w()` now reads empty as the
default exactly as `_number()` does, and unparseable as 0.0 exactly as
`_entry_max_w` does, where rule 9 refuses it by name at line 790.
⚠️ THE FIRST ATTEMPT AT THIS MADE IT WORSE, AND THE PROBE CAUGHT IT. Guarding
`build_roster` in `selfconfig` with `except: return validate(opts), []` turned
the 500 into ZERO PROBLEMS for `max_w: ""` - the validator has nothing to say
about it, so an empty list came back and the page would have ENABLED SAVE. A
crash became a silent acceptance. The guard is kept as a backstop for shapes
neither file anticipates, but it can no longer return an empty list: if the
roster cannot be composed and the validator names no reason, that disagreement
is itself reported.
MEASURED after the fix, `problems_and_ranges` with no HA:
max_w 5000, slew_w 400 0 problems (the live shape)
max_w "", slew_w 400 1 problem rule 10, "against a site rail of
2000 W" - clearing the box FAILS
CLOSED on the live install rather
than silently halving the rail
max_w "", slew_w 0 0 problems accepted at the 2000 default
max_w "abc" 1 problem "max_w 'abc' is not a number"
Before the fix, both "" and "abc" raised ValueError instead.
N2. `translations/en.yaml:7` said "all 71 keys ... so ALL SEVENTY are rendered".
The 70->71 correction had been made in one half of the sentence and not the
other. 59-of-71 required is correct and was re-measured.
Suite: 24 files, all pass.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
fdaf3fb54f |
UX-02: the validator's refusals, next to the field, before the save
checks / unit (pull_request) Successful in 6m17s
The Configuration tab can only render types and ranges. `validate.py`'s most
useful refusals are CROSS-FIELD - two inverters naming one `setpoint_entity`, a
`maintenance_charge_w` above `max_w`, a flat `setpoint_entity` left set beside a
declared roster - and the Supervisor's UI has no way to express a rule spanning
two keys. Today the operator meets those as exit 78 in a log, after saving and
restarting. This puts them on the screen beside the field they name, before
anything is written.
WHAT IT ADDS
app/configui.py the field model, built from `GET /addons/self/info`'s own
`schema` + `translations`. No option key, no label, no
rule of its own. UX-01's `Group · ` label prefix becomes a
real section heading, in whichever language resolved.
app/selfconfig.py the Supervisor conversation and the write gate.
app/config_page.py the page. Its longest function decides which HTML input a
type deserves; it contains no rule.
app/web.py five routes. Still the only file a reviewer has to read to
answer "does anything here reach the inverter".
THE FOUR THINGS THAT COULD HURT SOMEBODY, AND HOW EACH IS HELD
1. A blob the SHIPPED validator refuses is never written - not warned about,
not written. An invalid blob plus a restart is exit 78, and the panel is
gone with the add-on that serves it.
2. A blob that moved underneath is refused, not clobbered. Read hands out a
sha256 of the canonical blob, save hands it back, and the stored blob is
re-read IMMEDIATELY BEFORE the write. This is SAFETY-28's discipline
applied to configuration - "a blob reaches the Supervisor only if it was
derived from the blob stored right now" - with the honest weakening stated
in the decision record: a second writer is DETECTED, not made
inexpressible.
3. Every message is the validator's own, byte for byte. test_selfconfig.py
part 6 inserts ONE new rule into a COPY of validate.py, hashes every file
under app/ to show validate.py is the only one that differs, and serves the
real /config/validate route out of that copy in a subprocess. The new
sentence arrives, filed under the key it names.
4. Nothing on the surface commands an inverter or clears a latch. Saving does
not restart: applying costs a control interruption - the wind-down commands
0 W on every inverter - so that is a separate, confirmed button that says
so first.
MEASURED, NOT CITED (tools/supervisor_selfapi_probe.py, run against
Supervisor 2026.08.0's own code; it contacts nothing)
- the three self-paths are permitted, and `/addons/self/info` is admitted by
the `default` role too while `options` and `restart` rest on the bypass
ALONE. The probe's first draft claimed the role admitted none of the three
and went red.
- `/addons/self/options/validate` is NOT reachable from inside an add-on, so
the only validator this panel can call is ours - which is the one with the
cross-field rules.
- a POST that omits a key does not preserve it: the key reverts to
config.yaml's default. Hence whole-blob read-modify-write.
- the Configuration tab CAN be removed, and doing so drops 0-of-71 options
through and takes the add-on down. The card said it could not be; it stays
by decision, which is a better reason.
DOES NOT TOUCH config.yaml, main.py or any control path. UX-01 is a dependency,
not something this supersedes: its translations are where every label,
description and section heading on this page comes from, and the Configuration
tab is still the recovery surface. DECISIONS/UX-02-two-config-surfaces.md
records which surface is authoritative (neither: the stored blob is) and what
the second surface costs.
Also corrects a stale "70 options" in three prose spots to the 71 the probe
counts - config.yaml grew a key in SAFETY-42 and the sentences did not follow.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
---
⚠️ REBASED ONTO release/1.0 @
|
||
|
|
3368231048 |
Merge pull request 'PKG-07: bump 0.7.0 -> 0.8.0, and stop the changelog calling shipped work unreleased' (#60) from PKG-07 into release/1.0
PKG-07: bump 0.7.0 -> 0.8.0, because 0.7.0's own default is now a refused config |
||
|
|
06661c5e17 |
PKG-07: bump 0.7.0 -> 0.8.0, because 0.7.0's own default is now a refused config
checks / unit (pull_request) Successful in 6m6s
Six merges landed behind an unbumped 0.7.0 - CI-06, SAFETY-38, SAFETY-39,
SAFETY-37, SAFETY-13, SAFETY-42. PKG-06 recorded this exact failure YESTERDAY
(
|
||
|
|
464d398051 |
Merge pull request 'SAFETY-42: a unit that stops delivering, and the discriminator the card asked for does not exist' (#59) from SAFETY-42 into release/1.0
checks / unit (pull_request) Successful in 6m6s
SAFETY-42: alarm when the saturation freeze persists past the plant bound |
||
|
|
090a8ecc35 |
SAFETY-42 round 2: pin the two thresholds at a config that is not the shipped one
checks / unit (pull_request) Successful in 6m7s
THE BLOCKER. At the `delinquent()` call site, `self.tuning.saturation_w` -> `250.0` (-19 B) was a survivor of all 23 suites. It is not an equivalent mutant: two copies of inverter A, B wedged, `saturation_w: 1800` (inside its own schema int(100,2000)) and a load of 1600 W put B's shortfall strictly between the literal and the configured value - head names nobody, the mutant names B. At the shipped 500 both name it, which is exactly why every fixture in part 4 was blind: their gaps are all above both thresholds. It matters beyond a mutation score. `delivery.py`'s MIN_W_IS_SATURATION_W note and the `delivery_hold_s` block in config.yaml both promise an operator, in shipped prose, that there is no fourth copy of a threshold to keep in step and no way for the two to drift - raise `saturation_w` and this check moves with you. A literal at the call site removes exactly that promise, silently, and the promise is why the design was chosen over a `delivery_w` key. ASKING THE SAME QUESTION OF EVERY OTHER NUMBER THIS CHECK READS FOUND A SECOND SURVIVOR OF ALL 23 SUITES: `bms_floor=inv.bms_soc_floor` -> `10.0` (-13 B), invisible because config.yaml's own example states 10 % and every fixture in this file used it. Two arms bracket it: a pack at 15 % against its own 25 % cut-out is cold and must stay unnamed (the literal names an empty pack), and a pack at 8 % against its own 5 % cut-out is wedged and must be named (the literal explains the fault away). One arm on each side leaves no constant at all. `delivery_hold_s` and `is_live()`'s window were ALREADY pinned - the fixtures had to move them to run - and `LINK_STALE_S` has no option behind it, so "pinned across a changed config" is not available for it and is not claimed. DECISIONS section 9 enumerates all of it with the deltas and which check kills which. Verified in the CI image, tree mounted :ro, `python3 -B`, `__pycache__` purged and counted before every run (TEST-15): R5 saturation_w -> 250.0 -19 B killed by part 4b(a) R6 bms_soc_floor -> 10.0 -13 B killed by part 4b(b), both arms R7 arm(self.delivery_cfg) -> DeliveryConfig() -1 B killed (already) R8 is_live(now) -> is_live(now, 3600.0) +8 B killed (already) R9 pack cut-out -> conjoined site floor +105 B killed twice head: 23/23 test files PASS, no bytecode written during the run. No shipped behaviour changes: the only edits to app/ are comments. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
c7eb8c6b97 |
SAFETY-42: close two mutation gaps, and correct what makes N=1 inert
The battery is 12 mutations, one freshly copied tree each, purged, `:ro`,
`python3 -B`, byte deltas measured. First round: 9 red, 3 survivors. All three
are now accounted for and the ledger is in DECISIONS §8.
M5 - `share <= 0` relaxed to `share == 0`, +0 B - WAS A REAL GAP AND THE TWO
OBVIOUS CHECKS DID NOT CLOSE IT. `short_by(-2000, 0) is None` and
`short_by(-2000, -100) is None` both stayed GREEN under the mutant: for a charge
share that is UNDER-delivered `share - measured` is negative and the `gap > 0`
test answers None anyway, so neither input can separate the two spellings. The
one that can is a unit moving MORE than its charge share - -2000 W told,
-3000 W measured, `share - measured` = +1000 W - which the mutant reports as a
shortfall. It is not one; it is something else driving that pack, which is
SAFETY-30's and SAFETY-31's question. That input is now the check, and M5 is RED.
MUTATION.md's third failure mode in miniature: the assertion ran, the sentence
was true, and the data could not reach the failure it named.
M11 - `inv.is_live(now)[0]` replaced by a literal `True`, -15 B - was a WIRING
gap the pure checks structurally could not see. `account(live=False, ...)` was
graded as a FUNCTION; nothing graded that `cycle()` asks the question, because no
fixture had a unit whose writes were being rejected. Such a unit still has its
last ACCEPTED command standing on the wire (`write_setpoint` leaves `last_write`
alone on a rejected write) and still measures nothing, so it looks exactly like a
wedged one to every number this check reads - and reporting it would be the
second, louder alarm about a state the allocator has already handled and logged.
`test_delivery.py` part 6 now builds that unit, with `rejected_since` back-dated
past LINK_STALE_S because the fixture runs in two seconds and the timer is
test_inverter.py's to grade. M11 is RED.
M3 - `len(asked) < 2` relaxed to `< 1`, +0 B - IS STILL A SURVIVOR, and it is an
EQUIVALENT MUTANT. With one asked unit `unaccounted` is a subset of a one-element
set, so it is either empty (`not unaccounted` returns {}) or equal to `asked`
(`len(unaccounted) == len(asked)` returns {}); with zero asked units both
spellings return {} as well. No input separates them, so no check can.
⚠️ AND FINDING IT CORRECTED THE MODULE'S OWN PROSE, WHICH IS THE MORE USEFUL
HALF. `delinquent()`'s docstring claimed `len(asked) < 2` was what makes N=1
inert. It is not - the PROPER-SUBSET rule is, and that line is a fast path and a
signpost. A false attribution of the mechanism in the file's own prose is exactly
what this repository keeps finding, and a mutation that survives is how it
surfaced. The line stays, with the equivalence written down beside it the way
circulation.circulating_w() records its own max(0.0, ...).
Also recorded, rather than left implicit: `account()`'s `parked` branch is graded
as a function but its WIRING is not mutated on its own; part 6's reversed-unit
fixture exercises it end to end, which is weaker, and the ledger says so.
Baseline 23/23 green before and after. app/main.py is byte-identical to the
previous commit - both closures are a test and a comment.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
706e625d99 |
SAFETY-42: a unit that stops delivering, and the discriminator the card asked for does not exist
A unit standing at a non-zero share and producing nothing is seen by NOTHING. SAFETY-30's per-unit sign gate needs OPPOSITION on both sides of 250 W and a unit at 0 W is not opposing, it is ABSENT. The site sum still agrees with the meter in direction. Circulating power is exactly zero when one unit does nothing. The only trace left is `reason == "saturated-freeze"`, which clamp.py:93-96 documents as the alarm an operator learns to ignore. It is HW-01's shape, which ran 6 h 25 m with all three layers spectators. ⚠️ THE CARD'S OWN DISCRIMINATOR WAS BUILT FIRST AND FALSIFIED, AND THAT IS THE MAIN CONTENT. SAFETY-42 asks for "saturation persisting past N while |grid error| > X, both derived". Run on the two-master rig it fails in BOTH directions, and no (N, X) fixes either: FALSE POSITIVE `plantsim.Plant.limit()` returns 0 W for a discharge command into a pack at its own floor, and a wedged unit produces 0 W too. Load 2000 W, equal weights, 2000 W per-unit cap, 120 cycles: THE TWO ARMS ARE IDENTICAL ON ALL 120 in grid, site target, every share and every measured watt. Both saturated-freeze on 116 of them, both hold |grid error| over 300 W on all 120 and settle at 1200 W, both read circulating 0.0 W. The predicate's inputs do not differ, so no threshold on them can differ. And "a cold pack at its floor must not alarm" is the card's own AC 2. FALSE NEGATIVE the standing grid error is what a HEALTHY SIBLING ERASES. Load 800 W, same config, B wedged: over the last 30 of 200 cycles the loop is frozen on 30 of 30 while the worst |grid error| is 30 W, with B standing at +770 W and delivering 0 W. Any X above 30 W is silent for the whole run on the exact fault the card describes. WHAT REPLACES IT. Per unit, for a discharge share, `share - measured`; readable because of a reduction that only exists at N>=2: a unit is named while it is short by more than `saturation_w` with NO ACCOUNT for it, and the units in that state are a PROPER SUBSET of the units asked to discharge. THE ACCOUNT keeps the cold pack out and is the only thing that can: the two cases are identical in the power domain, so the discriminator has to be a non-power fact, and there is exactly one - the pack's own SoC against its own `bms_soc_floor`, asked through `peakguard.discharge_permitted()` rather than transcribed. ⚠️ `bms_soc_floor` ALONE, not `pack_floor_pct()`'s conjunction with `peak_soc_floor`: that floor bounds a money-saving discharge only and using it would explain away a wedged unit anywhere between the two. THE PROPER SUBSET keeps a whole-site cause out - a derate this add-on cannot see hits every unit; one box that stopped listening does not - and it is what makes this INERT AT N=1, by algebra rather than by a roster guard. IT REPORTS. IT DOES NOT ACT, and the strongest argument is for acting. Dropping the wedged unit from `live` genuinely recovers a site the shipped path does not: at load 1500 W, kept in the split the site settles at 800 W with a 700 W error and NEVER comes inside 100 W in 150 cycles (the freeze pins the target, so the sibling's SHARE never grows); dropped, it delivers 1500 W from cycle 14. What refuses it is that the only re-allocation this add-on can express is all-or-nothing: a unit derated to 50 % is short by more than saturation_w with nothing to explain it, so this detector names it too, and at load 3000 W dropping it leaves the site delivering 2000 W against 2400 W kept - 400 W WORSE. A partial re-allocation is what would make acting safe and the allocator cannot express it. That is a card. control.py is NOT MODIFIED. The freeze shapes the loop; this reports on it. NUMBERS, MEASURED. The watts side is `Tuning.saturation_w`, read at runtime, so there is no fourth CFG-03 copy and it cannot drift from the number the control law itself calls "not following". `delivery_hold_s: 185` comes off 2640 closed-loop two-inverter runs in which nothing is faulty (6 gains x 5 slews over the whole schema range, across load reversals, a flapping load and ASYMMETRIC SPLITS - a family SAFETY-30's campaign did not have and the one that dominates here) plus 1890 runs at a roster of ONE as the control: threshold reversals flapping weighted N=1 control * 500 W 20.0 s 0.0 s 30.0 s 0.0 s The N=1 column is 0.0 s at EVERY threshold in all 1890 runs, and the flapping column - the family that defeated SAFETY-30's site window - is zero too, because a common stimulus makes both units short at once and the subset stops being proper. ⚠️ The curve is NOT monotone (55.0 s at 250 W against 40.0 s at 100 W): lowering the threshold can turn a proper subset into the whole roster and BREAK the run. ⚠️ THE MARGIN IS MEASURED, NOT FELT, BECAUSE INVERTER B DOES NOT PHYSICALLY EXIST. `plantsim.INVERTER_B` is A COPIED, `measured=False`, so every two-inverter figure above is two copies of A. Sweeping a different second unit: the worst legitimate episode is insensitive to B's RAMP (30.0 s at half A's) and scales with its LAG - 45.0 s at twice A's measured 10 s, 90.0 s at four times it. 185 s is 6.2x the measured worst, 2.06x the four-times-slower case, 6.2x LINK_STALE_S and 4.9x inside the 900 s quarter. Deliberately not 180, which is SAFETY-02's site hold. SAFETY-34. `unit/<name>/delivery_tripped` in the store, one notification id per unit, re-raised on the first cycle of every process, cleared by the Start press. No flat mirror: a rollback lands on a version that drives one actuator, where this check is inert. ⚠️ SCHEMA CHANGE - `delivery_hold_s` joins options: and schema:, so this needs a version bump before it ships. Additive and defaulted, so an existing options blob stays valid. STATED GAPS: charge shares are not graded (no configured charge ceiling exists, so a constant-voltage taper cannot be explained and arming it would fire on every maintenance charge); every unit wedged at once is not caught (the subset is not proper and no instrument here separates that from a plant that cannot). Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
0581648c73 |
Merge pull request 'SAFETY-13: the output freeze gets an exit, and only where it needs one' (#58) from SAFETY-13 into release/1.0
checks / unit (pull_request) Successful in 5m30s
|
||
|
|
f156fadac0 |
SAFETY-13: the bound came from the wrong half of a two-sided measurement
checks / unit (pull_request) Successful in 5m34s
NOTES.md 5.10 measured the 1.78 kW step BOTH ways - "Up: ~18 s from step to deadband. Down: ~23 s" (NOTES.md:1550). SAFETY-39 takes 18 correctly: its bound is a REFUSAL and the looser number refuses less. This branch reused PLANT_SETTLE_S for the opposite job - how long the plant may still be the EXPLANATION for a divergence - where the conservative half is the longer one. ceil(23/2) = 12, not 9, and being short there does not refuse anything, it accuses. The false positive is real and is measured here. One inverter, one compute(), one plant, no second writer anywhere in the harness: the command falls through zero while the pack is still coasting the old way, unasked_power() calls our own power "unasked", the counter reaches 9 while it is still coasting, and the law emits "freeze-released". At the plant's own measured 18 s/23 s shape, over 272 load-step pairs, the 9-cycle bound fires in 62 and the 12-cycle bound in 2. PLANT_SETTLE_DOWN_S = 23.0 is added beside PLANT_SETTLE_S = 18.0, because the plant's settling time is a PAIR and each bound has to say which half it means and why. SETTLE_CYCLES = ceil(PLANT_SETTLE_DOWN_S / LOOP_TICK_S) = 12. It is no longer the reciprocal of SLEW_RAIL_FRAC; that was a coincidence of both reading the same half, and test_control.py now asserts the inequality. _SAT_COUNT_CAP moves with it, 10 -> 13. config.yaml accepts saturation_cycles as int(1,10), so the whole accepted range is now strictly BELOW the bound and the degenerate configuration this branch used to document no longer exists - pinned against config.yaml's own schema line. Three shipped statements were falsified by that measurement and are rewritten, not renumbered - at 12 the residual is smaller, not zero: unasked_power()'s docstring said anything outside the interval "was put there by something other than this loop". It was our own power: eight cycles after a +1990 W command the command is 0 and the pack still reads +522.3 W. control.py said "SO THE BOUND BELONGS TO (b) AND ONLY TO (b)". It fired in case (a). DOCS.md told an operator "if you see freeze-released, look for the second writer" - on a single-inverter install, hunting something that does not exist. Replaced by a section that gives the innocent causes first (a large load or PV swing; a plant slower than the one measured, 8/320 scenarios at 23 s rising to 268/320 at 50 s) and the second writer only when the state STANDS. Round 1's own results are kept and re-graded, not weakened. The release/1.0 sweep had to widen to reach the new bound (3780 cases): 3267 bit-identical, 432 releases, 27 command changes - all still charge starts from prev_w == 0 - and 81 differing in the saturation counter alone, which nothing downstream can read. The card's case releases on the twelfth saturated cycle instead of the ninth and settles at the same -1190 W against the same frozen integrator. Also corrected, because they were claims and did not reproduce: the coverage table's "output freeze" row was 11, and the mutation form its own note describes gives 6 on this tree, 6 on the first SAFETY-13 commit and 2 on release/1.0; the detector row was left at 11 and is 15; the frozen = False footnote was left at 10 and is 13. And section 6 reported 107 625 as "released states" when it is the number of states SWEPT - 67 500 of them release, and both are counted now. Nothing here reached the inverter. 22/22 test files pass in goodwe-addon-ci, tree rsynced to a plain path, mounted :ro, python3 -B, __pycache__ purged and printed first (0 dirs / 0 .pyc; the worktree carries none). Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
6c4565659b |
SAFETY-13: the output freeze gets an exit, and only where it needs one
checks / unit (pull_request) Successful in 5m30s
While the loop is frozen the command's magnitude may fall but never rise. At prev_w == 0 there is no magnitude left to fall, so a charge cannot START. That refusal is deliberate and it is kept: the inverter reporting power we did not command means another writer is on the actuator, which is the §1.5 non-goal. What it did not have was an END - nothing cleared it but the other writer leaving. Reproduced on release/1.0 @ |
||
|
|
c8dcb38a95 |
Merge pull request 'SAFETY-37: a stale reading is None, and arrival cannot be what says so' (#57) from SAFETY-37 into release/1.0
|
||
|
|
8e241a3243 |
SAFETY-37: correct a wall-clock tick and a false size claim
checks / unit (pull_request) Successful in 5m32s
Two blocking findings from review, both in prose, both corrected at every site. 1. "trips on tick 7" was not what the fixture prints. It prints 11, five runs out of five, and the developer's own report says 11. ⚠️ But the deeper problem is that the number should never have been quoted: the tick is counted on the WALL CLOCK inside cycle() (hold_s 2 s, ticks 0.20 s apart), so it is load-dependent - 7 is what a box slow enough to stretch each tick to ~0.29 s would print - and nothing pins it. The DECISIONS transcript now says 11 because it is a transcript of a run; the CHANGELOG stops quoting a tick at all and states the checkable thing instead: it trips without the gate and never with it, which part 3 grades. 2. ⚠️ SURVIVOR 2's SIZE CLAIM WAS FALSE FOR ONE OF THE TWO CONSUMERS THIS CARD EXISTS TO PROTECT. It read "one contributing at most 250 W to a loop whose reporting floor is 700 W" at three sites. That bounds the COMMAND. Once the register is frozen its REPORTED value is unrelated to the command - which is exactly HW-01's shape: commanded ~0 W, register stuck on the last large number. Measured in review: a unit frozen at -1200 W beside a healthy +900 W sibling yields circulating_w = 1800 W against the 700 W floor, 2.6x OVER, with no gate armed. So the scoping is TRUE for the per-unit sign check and FALSE for circulation. Corrected to say exactly that, and the circulation consumer's exposure below MOVE_W is now recorded as a KNOWN GAP rather than a covered one. It survived because part 9's S2 check asserts only `not stale` and part 4 pairs the frozen unit with a RESTING sibling (circulating_w([A_FROZEN_W, 0.0]) == 0.0) - neither grades the size sentence. No behaviour change. Full suite: 22 passed, 0 failed. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
6864109a01 |
SAFETY-37: a stale reading is None, and arrival cannot be what says so
checks / unit (pull_request) Successful in 5m34s
The architect pass made SAFETY-37, TEL-06 and TEL-08 one systemic problem - "a stale reading holds its last value and reads healthy" - and this builds the single policy. Both consumers the card names are gated by one change, and neither consumer needed a line: `SignWatchdog.evaluate` already CLEARS its window on a None measurement and `circulating_w` already returns None for a roster with a missing term. Neither could ever receive one. The gate is the piece that was missing BETWEEN the shipped read and the shipped checks. ⚠️ ONE CRITERION IN THE CARD COULD NOT BE IMPLEMENTED AS WRITTEN, AND SAYING SO IS THE MAIN CONTENT. The card says "only arrival separates them". At this layer arrival cannot: `read_inputs()` polls Home Assistant's state cache about once a second and HA answers 200 with a number whether or not the publisher behind the entity is alive, so both members of the pair arrive identically for ever. test_freshness.py part 1a BUILDS the arrival-age gate the card asks for and grades it failing - the age is 0.0 s at every instant of both runs, a threshold that can never fire, which is TEL-06's own defect one layer up. The half of the rule that survives is honoured absolutely: nothing here reads a Home Assistant timestamp, and the check asserts the module contains no `last_updated`. So the criterion became: a reading is stale when it has not moved through a change it was OBLIGED to follow. STALE <=> unchanged >= 35 s AND |standing| >= 250 W AND |standing - standing when the reading last changed| >= 250 W Latched until a different value arrives. `Inverter.batt` becomes None - never a held number - which is a missing input, which §11.1 rule 1 answers with 0 W. WHY A CONJUNCTION AND NOT A THRESHOLD, MEASURED 2026-09-06. Replaying the committed 30-day capture of this house's own 1 W power entity (485,841 samples out of HA's recorder, where a row exists only on a CHANGE, so the gap between rows IS the unchanged duration every consumer saw): the longest legitimate unchanged run is 263.2 s, held at -899.0 W. A false-positive-free threshold would have to exceed that, and 263 s is 3.5x too slow for a consumer that trips at 75 s. There is no admissible threshold. Every one of those long runs is under an UNMOVING load, which is what the travel term keys on. THE BOUND, derived at both ends and graded against the shipped config.yaml. Floor 17.0 s = 6.0 plant settle (NOTES §5.9, measured 2026-08-22) + 10.0 ESPHome publish (firmware/goodwe-master.yaml:181) + 1.0 read period (run_control's asyncio.sleep(1)). Ceiling 75.0 s = min(circulation_hold_s 75, unit_sign_disagree_s 85). Band [34.0, 37.5]; 35 is a CHOICE inside a DERIVED band and the check says so - the first draft claimed the band held one integer and went red on its own first run. MOVE_W is the LARGEST admissible value, unit_sign_disagree_w, because below it the consumer cannot speak at all. SoC is STATED, NOT WIRED, and BOUNDS carries it with wired=False and the reason. Its obligation term is energy through the pack, not command travel - a rested pack holds a percent for hours under a 0 W command - and K needs a usable capacity nobody has measured. That is TEL-08's; the record says so. ⚠️ BEHAVIOUR CHANGES AT THE SHIPPED ROSTER OF ONE, and it is named rather than hidden: a FROZEN register now stops the site where it used to read as a healthy measurement for ever. That is HW-01, which was a one-inverter site. A healthy install is unchanged, asserted over sixty reads of a dithering register under a reversing command. A false verdict fails toward 0 W behind the existing stale_input_s hold and clears itself on the register's next move. ⚠️ BOTH UNITS IN EVERY TWO-INVERTER FIXTURE ARE INVERTER A with different numbers passed in; inverter B does not physically exist (~2026-09-12). MUTATION: 16 mutations against a purged, :ro, python3 -B tree, fingerprinted before and after every revert. One survivor, and it is the finding - dropping the magnitude term left every check green because no fixture separated "the command travelled 250 W" from "the command ended up above 250 W". Closed, and recorded as MUTATION.md habit 17. A second process defect is habit 18: a mutation run that timed out between the edit and the revert left the module mutated on disk and nothing announced it. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
a4290d39ac |
Merge pull request 'SAFETY-39: slew_w is a ratio to the rail, and gain is the constant that is still wrong' (#56) from SAFETY-39 into release/1.0
|
||
|
|
834e7ca44b |
SAFETY-39: correct the gain figures, which were not the measured ones
checks / unit (pull_request) Successful in 5m15s
Review found validate.py:288-289 carrying numbers that appear nowhere else in the PR's evidence and could not be reproduced: over-absorption "1233 W at slew 1000 and 1344 W at slew 250 ... 1495 W at 0.6, 961 W at 0.3, ~0 W at 0.2". A grep for 1233/1344/1495 found them ONLY in that comment - the DECISIONS record, the PR body, test_control.py's audit table and slew_sim's own output all carried the correct ones. The measured values, from re-running tools/slew_sim.py on the real plant model at the stated conditions (max_w 5000, 2 s tick, 51 export steps 1.0-4.2 kW): slew column 958 (slew 1000) and 1081 (slew 250); gain column 987 (0.6), 876 (0.3), 435 (0.2). ⚠️ "~0 W at 0.2" WAS WRONG IN THE UNSAFE DIRECTION. It invited a future reader to conclude that dropping gain to 0.2 removes over-absorption. It does not: 435 W remains, which is 44 % of the figure at 0.6, not zero. The corrected text says so at the line rather than leaving a round number to be trusted. The conclusion the paragraph draws is unchanged and still holds on the measured figures: over-absorption is flat in slew_w and falls in gain, so `gain` is the constant that would have to move, and SAFETY-39 deliberately does not move it. No behaviour change; comment only. Full suite: 21 passed, 0 failed. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
5d7e275df4 |
SAFETY-39: slew_w is a ratio to the rail, and gain is what is still wrong
checks / unit (pull_request) Successful in 5m16s
`slew_w: 1000` was derived on 2026-08-22 against a clamp of 1500 W, where "capping how far the loop can jump ahead of the inverter" was true because the rail itself bounded the excursion. The live install went to max_w 5000 and the constant did not move, so the loop crosses its whole output range in 10 s against a plant NOTES.md §5.10 measured at ~18 s. Measured on the owner's system 2026-09-05 11:43-11:46: a 3.4 kW export drove the setpoint 380 -> 5000 W in five 2 s ticks, the battery to -5154 W past a 5000 VA rating, and the grid from 3.4 kW of EXPORT to 2.8 kW of IMPORT. Nothing was broken; the rail moved. REPRODUCED FIRST, and one half of it is not reproducible at all. On plantsim.Plant and on an independent in-repo model: the setpoint stepping a full 1000 W per tick to the rail (48 of 51 export steps), and the meter crossing from export into import. The -5154 W figure is NOT reproducible in either model, because both clamp the plant at its rating - so the card's AC "battery no longer exceeds max_w in simulation" is unfalsifiable and was rewritten rather than met. THE DELIVERABLE IS THE RELATIONSHIP. SLEW_RAIL_FRAC = LOOP_TICK_S / PLANT_SETTLE_S = 2 s / 18 s = 1/9 slew_w = 0 now means FOLLOW THE RAIL - SLEW_RAIL_FRAC * max_w - exactly as integrator_max_w = 0 already means follow max_w. It is the shipped default: 222 W at max_w 2000, 556 W at 5000, 1067 W at a ~9600 W two-inverter site. validate.py rule 10 refuses an explicit value faster than that, graded against sum(unit_caps(opts)) - the roster sum, i.e. Controller.site_max_w - so a second inverter moves the bound with no operator action. VERIFIED BY BREAKING IT: restoring slew_w 1000 at max_w 5000 is refused, and the refusal names the rail, the crossing time, the measurement and what to do. Equality, one watt of slack, the live interim 400 and slew_w 0 at every rating all still start. GAIN IS THE CONSTANT THAT IS STILL WRONG, and it is NOT changed here. Over 51 export steps the over-absorption is FLAT in slew (958 W at 1000, 1081 W at 250) and monotone in gain (987 W at 0.6, 876 at 0.3, 435 at 0.2): slew_w bounds the OUTPUT, while the integrator moves gain*error per cycle and reaches a 5000 W rail in under three ticks whatever the slew is. Two control-law constants moving in one release on a running house makes the next measurement uninterpretable. ⚠️ N=2: the site rail becomes sum(max_w) ~ 9600 W (inverter B FROM DATASHEET AND SERIAL, not measured, and sim/plantsim.py's INVERTER_B is A copied), and the enforced ratio produces 1067 W there automatically. But a growing rail LOOSENS this bound, and the >= 900 W symptom goes stale at N=2 the same way the constant did - both stated in the record rather than left to be discovered. Nothing reached the inverter. The live install still runs the interim slew_w 400 applied by hand on 2026-09-05, which rule 10 accepts unchanged. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
24c3d87d60 |
Merge pull request 'SAFETY-38: pin site_standing with shares that cannot answer for the site' (#53) from SAFETY-38 into release/1.0
|
||
|
|
d5b9317d57 |
SAFETY-38: correct the survivor count, which was stated four ways
checks / unit (pull_request) Successful in 5m11s
Review found the summary lines miscounted, and one of the miscounts filed
a KILL among the survivors. The authoritative tables in §7e and §7f were
right throughout; only the sentences a reader actually relies on were
wrong.
Arithmetic, from §7f's own ledger:
14 measured = 10 surviving
+ 1 already caught (C3 allocator.py:162, red in test_alloc.py)
+ 3 caught by round 4 (C6 clamp.py:253, C7 peakguard.py:493,
B12 arbiter.py:264)
Survivors by file: TWO in allocator.py (C1 :154, C2 :160), three in
arbiter.py (C4a/C4b :344, C5 :392), two in tariff.py (C8, C9), two in
arbitrage.py (B17, B18), one in main.py (B19). Two, not three, in
allocator.py - C3 is the kill.
Before: DECISIONS §6c said "Nine" while listing eleven; the CHANGELOG said
"11 SURVIVORS" while listing eleven. Both counted C3 as a survivor.
⚠️ KEPT VISIBLE RATHER THAN QUIETLY FIXED. This is this card's own
recurring defect in prose rather than in code - a claim wider than the
measurement beneath it - and it is the second false statement this ticket
has put into its own decision record. The correction says so at the line,
because a document whose whole value is that it can be trusted should
record when it could not be.
No app/ change; no test change. Full suite: 21 passed, 0 failed.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
e2efc765af |
SAFETY-38 round 4: the enumeration covered one sink, and it was not the one this codebase uses
checks / unit (pull_request) Successful in 5m12s
The scanner's two censuses between them scored ONE syntactic sink and called it
the family. Every one of census B's 16 members was a sentence that is APPENDED,
ASSIGNED to a `reason`-shaped name, or passed as a LOG ARGUMENT. Not one was
RETURNED - and census A's return bucket only ever held a callee formatting its
own PARAMETERS, so a method formatting its own ATTRIBUTES and handing the string
back was invisible to both. That is the whole describe() / explain() /
reason-builder family, which is where this repository actually keeps its
operator sentences. Worse than the gap: it was in NONE of the five blind spots
the tool printed about itself.
THE SCANNER, WIDENED - and it rediscovered both members without being told:
* CENSUS C, the return sink, resolved through the returning method's CALL
SITES so a returned KEY (store.unit_key, mqtt.unit_state_key - MAINT-05's
card) is not mistaken for a returned SENTENCE. 53 returned pairs, 39
reaching an operator, 16 of those sharing a format spec.
* A sentence handed to a constructor as `reason=` or placed under a "text"
dict key is a MESSAGE. That one line of the sink walker was hiding SIX more
caller-built members, census B 16 -> 22.
* Every census B and C row now prints whether the two interpolations share a
FORMAT SPEC - the difference between a transposition that is silent and one
that merely looks broken.
* The blind-spot list is now TWO lists: what it scans (printed from the
constants, so they cannot drift) and WHAT IT DOES NOT SCAN AT ALL, largest
hole first - `%s`-style lazy logging, MEASURED at 31 calls across 8 modules
and each one listed, not asserted.
CLOSED, both zero-byte survivors of a green 21-file suite:
* clamp.py:253 ClampResult.describe(), requested_w <-> applied_w. No
test_*.py mentioned describe() at all. It is the SS15 action-log row
(main.py:1366) AND the ClampWatchdog notification reason (main.py:2452) -
the alarm SAFETY-40 and SAFETY-41 are about. Under the swap the guard
reports a setpoint clamped UPWARD, to +9999 W by a bound whose rating the
same sentence gives as 2000 W. Pinned on the ORDERED PAIR on the contiguous
literal at BOTH consumers, operands read off ctl.target and
hass.writes[-1] - what the loop asked and what the device was sent - not
off the ClampResult the swap lives in. 4 checks red.
* peakguard.py:493 PeakDecision.explain(), projected_w <-> ceiling_w. "peak
guard idle" was in no test_*.py. The row then reads "projects 5013 W under
a 2300 W ceiling" - 2713 W OVER - on a row whose own words say idle and
whose own flag says ok. Pinned on the decision and on the shipped status
row. 3 checks red.
* test_arbiter.py's scope-violation check, whose CLAIM was wider than its
ASSERTION. Measured this round rather than left at source level: 0 bytes,
21/21 green before, red now. 2 checks.
DISCLOSED, NOT CLOSED - 11 measured zero-byte survivors, each with its file
fingerprint and its 21/21 verdict, in the decision doc SS7e-SS7g. Three in
allocator.py's UnitPlan.explain(), three across arbiter.py's two explain()s,
two in tariff.py, two in arbitrage.py's trade reasons, one in main.py's
SoC-floor notification. An enumerated list with honest gaps beats a fifth round
finding a fifth instance.
CORRECTIONS THIS ROUND OWES:
* The idle sentence does NOT reach main.py:3299/3302 - those are the
floor-limited branch, where explain() returns self.reason before the idle
literal is built. It reaches main.py:3313 and, on the release edge, 1951.
1951 is disclosed unpinned.
* SS4's "Every one of the ten is red" sat under a twelve-row table: it is the
ten site_standing entries.
* SS6b said "weaker evidence than A1-A3"; A4 was measured, so SS7d's
"A1-A4 and B1" is the right list and SS6b now says it.
* AND THE PROBE THAT GRADES THESE MUTATIONS WAS THE DEFECT, ONCE. Its first
cut numbered the operands BY ORDER OF APPEARANCE, so after a transposition
the other leaf took the same number and all thirteen mutant renders came
back byte-identical - which reads exactly like "the edit is inert". Keying
the value to the NAME fixed it. Habit 4, in the measuring instrument:
MUTATION.md habit 16 is the new entry, and the count there is corrected to
eleven rather than inflated.
14 mutations measured: fresh full-repo copy each, mounted :ro, bytecode purged
and the purge COUNT printed, the edit re-read from disk, length and sha256
printed on both sides, and every one required to change the EMITTED SENTENCE
and not merely the bytes. 12 survived the pre-round suite, 1 was already
caught, 3 are caught now. Full 21-file suite green on the final tree.
NOT ONE BYTE OF app/ MOVES. This card changes coverage only.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
357cb4f07f |
SAFETY-38 round 3: pin the banner the SHIPPED install actually prints
checks / unit (pull_request) Successful in 5m12s
Round 2 pinned the operand order of `SignWatchdog.evaluate()` at main.py:1620 -
the SITE detector. Part 9c asserts that detector is never armed at a roster of
one, so on every install this add-on has, the PER-UNIT banner is the only
sign-disagreement sentence that can ever be printed, and its call site is a
different line. main.py:1560 was left unpinned.
1. THE SAME ZERO-BYTE DEFECT ONE CALL SITE OVER.
`evaluate(stood, against, ...)` -> `evaluate(against, stood, ...)`:
app/main.py 234 542 bytes before and after, delta 0, fingerprint
61aa413f... -> e57e6026..., bytecode purged, tree mounted :ro, line re-read
from disk. On the round-2 tree the FULL 21-FILE SUITE PASSES.
Nothing behavioural could ever have caught it. `watchdog.disagrees()` is
SYMMETRIC in its first two arguments - `commanded_w * against_w < 0` with an
abs() gate on both - so the mutant takes identical actions on every input.
Not "no fixture happens to separate them": no fixture CAN.
What moves is the sentence. Measured by diffing the suite's own printed
banners between the round-3 tree and the same tree carrying only this edit:
9 emitted banner lines invert, in 3 distinct sentences.
shipped commanded -2000 W against a meter reading +2000 W
swapped commanded +2000 W against a meter reading -2000 W
shipped commanded +1000 W against its own measured power -1000 W
swapped commanded -1000 W against its own measured power +1000 W
shipped commanded -2000 W against a meter reading +4000 W (the N=1 arm)
swapped commanded +4000 W against a meter reading -2000 W
Persisted to `sign_reason` and re-read after the restart the latch exists to
survive; also the action log, `_LOG.error` and `status_payload()`'s headline.
CLOSED by the ORDERED PAIR on both per-unit banners, both operands read off
the OBSERVED CYCLE - `inv.last_write` and `inv.batt` off the objects the
plant moved, never off the arguments the detector was handed, which would
compare the swap against itself:
- part 3, the N>=2 trip: "commanded {stood:+.0f} W against its own
measured power {meas:+.0f} W", plus the persisted namespaced copy;
- part 7, the N=1 controller-driven trip: "commanded {stood:+.0f} W
against a meter reading {grid:+.0f} W", plus the namespaced key AND the
flat rollback mirror;
- a PRECONDITION on each that the two operands are different numbers of
opposite sign - without it a transposition produces the same string and
the check is decoration.
Measured after the fix: RED on four named checks in test_watchdog.py, GREEN
in the other twenty files. M11 (the site swap) re-measured on this tree:
still red. Round 1's and round 2's kills are intact.
2. A FALSE STATEMENT ROUND 2 INTRODUCED, AND IT WAS WORSE THAN REPORTED.
Section 4 said "three of these left the whole suite green - M1, M2 and M3 -
and the remaining seven were caught by SAFETY-30's own N>=2 checks". Round
1's vaguer wording was harmless; naming three made it specific and wrong.
Re-measured mutation by mutation on clean release/1.0 @
|
||
|
|
564ba11c11 |
SAFETY-38 round 2: assert the ordered pair, and correct the M3 attribution
Two blockers, one of them mine to fix and one a mis-measurement to undo. No
`app/` change in either: the shipped `sum` is correct.
1. A ZERO-BYTE SURVIVOR AT THE CALL SITE ONE LINE BELOW THE PINNED VALUE.
Round 1 pinned `site_standing` and never pinned WHERE IT GOES. Swapping the
detector's first two arguments at main.py:1620 -
`evaluate(site_standing, self.grid, ...)` -> `evaluate(self.grid, site_standing, ...)`
- is a ZERO-BYTE edit and left the round-1 tree fully green. The cost is the
banner: the site stands at -500 W of charge into a +2500 W import and the
LATCHING, SITE-STOPPING alarm reads "commanded +2500 W against a meter
reading -500 W" - which instrument read what, inverted, on the one line
somebody woken by it reads first (watchdog.py:658-665).
Round 1's check could not reach it. It asserted `"-500 W"` appears SOMEWHERE
in the sentence; under the swap it still does, IN THE METER SLOT. A substring
test grades PRESENCE, never ARRANGEMENT. It now asserts the ORDERED PAIR:
`f"commanded {sum:+.0f} W against a meter reading {grid:+.0f} W"`. Measured:
red in test_watchdog.py on that one named check, green in the other twenty.
2. THE M3 ATTRIBUTION WAS FALSE, AND HOW IT BECAME FALSE IS THE USEFUL PART.
Round 1 recorded `list(standing.values())[0]` as closed by SAFETY-32's
package-wide pin and told future authors NOT TO RE-COVER IT. Re-measured on
release/1.0 @
|
||
|
|
3033420dd7 |
SAFETY-38: record the CI-06 false red, and where each mutation lands
All ten mutations of `site_standing` are red in test_watchdog.py and in nothing else - the other 19 files are green under every one of them, which is the measurement of how unpinned the line was. One exception, recorded rather than dropped: in the batch run M10 (`sorted(standing.values())[-1]`) also reported FAIL test_peakguard.py. Re-run in isolation three times and once more through tools/mutation_run.sh - four clean passes. The batch script had discarded the failure detail so the check cannot be named; what can be said is that it did not reproduce in four attempts and that no claim in this card rests on it. That is CI-06's file behaving the way CI-06 records. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
a8bd2b9330 |
SAFETY-38: pin site_standing with shares that cannot answer for the site
`app/main.py:1598`'s `site_standing = float(sum(standing.values()))` is the
first argument of SAFETY-30's latching, site-stopping sign detector AND the
`commanded_w` handed to SAFETY-18's `looks_frozen()`. It was pinned by nothing.
Coverage only: not one byte of `app/` moves - the shipped `sum` is correct.
WHY THE SUITE COULD NOT SEE IT. `_sign_site`, the only N>=2 site fixture in the
repository, runs shares of about -2500 W EACH - every one individually over its
320 W gate - so sum, mean and max(key=abs) all agree on it. Its values happen to
be equal, and a check comparing two things that happen to be equal cannot see
the difference it names. MUTATION.md habit 4, ninth instance, inside the site
half of the card that names the rule in its own text. At N=1 it is arithmetic
rather than a fixture defect: sum == mean == max == the one share, identically.
THE FIXTURE (test_watchdog.py part 9). Two SIMULATED units rated 220 W and
280 W, both obeying exactly, inverted gain, house importing 2000 W: the site
commands -500 W against a +2500 W meter and NO SINGLE SHARE clears the shipped
300 W gate. Four candidate reductions, four distinct answers, one over the gate
- sum -500, mean -250, max(key=abs) -280, [0] -220 - asserted as a precondition.
The asymmetry is load-bearing, and the smaller unit is first so [0] stays
distinct from max(key=abs). Gate shipped; only the hold is shortened.
BOTH CONSUMERS. 9b drives the same discrimination at SAFETY-18's threshold: the
site rail is 0.95 x 500 = 475 W, so the sum rails it while 250, 280 and 220 do
not. Shipped: BLIND_FROZEN, floor 0 W. Under both surviving mutations: not blind
at all, no floor filed - the battery may keep importing through a quarter whose
billed average is unobservable. The open quarter is backfilled with the stuck
reading so the mutant cannot reach the same action by the coverage route and
mask the difference. 9c asserts the N=1 identity on a real one-inverter tree.
SAFETY-32 already closes `list(standing.values())[0]` structurally and this card
does not claim it. Its disclosed blind spot - semantics are invisible to a shape
pin, permanently - is why the mean and max(key=abs) needed a behavioural set.
AND THE SEARCH FOR THE NEXT SURVIVOR FOUND ONE. `float(self.target)` - the
arbiter's site target instead of the sum of what stands on the wire - is -11 B
and survives all 20 files on untouched release/1.0 @
|
||
|
|
9e42cecc24 | Merge pull request 'CI-06: test_peakguard.py answered two of its checks with the wall clock' (#54) from CI-06 into release/1.0 | ||
|
|
9b270a66a5 |
CI-06: test_peakguard.py answered two of its checks with the wall clock
checks / unit (pull_request) Successful in 4m56s
`test_peakguard.py` is flaky on the required `checks / unit (pull_request)`
context. Reproduced, measured and removed - not widened, and nothing skipped:
the file still carries all of SAFETY-07 and SAFETY-25, and gains a check.
TWO MECHANISMS, both the control law's own gain `900 / remaining` applied to a
wall-clock gap this file never meant to have.
1. THE CROSS-TIME PROJECTION (the "one cycle of the intent form..." check).
`_proj3` was a SECOND `PeakTracker.project(b3.p1.averager, datetime.now())`
taken after the real cycle had already returned, and its result was compared
against a floor decided from the FIRST projection - while the comment three
lines above says both forms run "against the same frozen projection".
`excess = 900 x (projected - ceiling) / remaining` moves at `excess /
remaining` W/s, so at a 1500 W floor the 1.5 W tolerance bought exactly
`remaining / 1000` seconds: 333 ms with 880 s left in the quarter and 6 ms
with 10 s left (measured by bisection, probe in the PR). The gap between the
two statements measured 12.7-39.5 ms over 26 instrumented runs, so the check
was decided by WHERE IN THE QUARTER it ran, about `gap_ms / 900` of the time.
FIX: `_recording_decide` keeps the Projection OBJECT the real cycle graded.
Both forms are now decided from it, the clock is out of the comparison, and
the tolerance is EXACT rather than 1.5 W. Measured on a real cycle: the
delivered form re-decided from that object reproduces the controller's own
floor to 0.000000000000 W, and the identity holds to 0.000000000000 W.
It also gains a check - that re-decide now pins `_kw` as main.py's actual
call rather than an approximation of it.
2. THE FIXTURE'S OWN ROOM (the three `wired_over_limit` checks named on the
card: "the real cycle files the peak claim...", "...and the number written to
the inverter is the guard's floor", "the STATUS PAGE row for a floor-limited
guard..."). `range(0, span + 1, 5)` leaves 0-5 s of the open block uncovered
by construction, and `excess` multiplies an uncovered second back up by
`900 / remaining`:
floor ~ want x (1 - uncovered/900) - net_w x uncovered / remaining
Measured on this tree, shipped: at 12 s of remaining a fixture that asked for
a 1500 W floor delivered 613 W (-59 %), and at 2 s the guard did not engage
at all - which fails all three of those checks together. The four-attempt
retry cannot help, because four attempts take ~40 ms and all land in the same
dying quarter.
FIX: one telegram stamped at `now` (which is what a real meter does and what
the docstring already claimed), plus FIXTURE_ROOM_S - the helper waits out
the tail of a quarter it cannot size a fixture in. 24 s is DERIVED from the
1 % accuracy the helper promises, at this file's smallest fixture and the
measured 0.1 s worst-case lag, not picked:
net_w x lag / (remaining x want) <= 0.01 - lag/900
remaining >= 3500 x 0.1 / (1500 x 0.00989) = 23.6 s
Same probe after the fix: -0.3 % at 12 s, -0.5 % at 8 s, still engaged at 2 s.
NO TIMEOUT WAS WIDENED, no check skipped, no xfail. One tolerance was made
STRICTER (1.5 W -> exact) because removing the clock made exactness possible.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
bbc903b2b4 | Merge pull request 'PKG-06: bump 0.6.0 -> 0.7.0, because the schema changed and nobody bumped' (#55) from PKG-06-version-0.7.0 into release/1.0 | ||
|
|
d8e02ad3f8 |
PKG-06: bump 0.6.0 -> 0.7.0, because the schema changed and nobody bumped
checks / unit (pull_request) Successful in 5m2s
Six merges landed since 0.6.0 was deployed and the version never moved. Disk and box both read 0.6.0, so `ha apps update` would have been a NO-OP: Supervisor keys the built image by `version:`, and the update path installs `version_latest`, which cannot differ from `version` without a bump. Found while pre-checking the deploy, not after it silently did nothing. ⚠️ MINOR RATHER THAN PATCH, BECAUSE THE SCHEMA CHANGED. SAFETY-32 added `bms_soc_floor: int(0,50)` as a REQUIRED per-entry key on the `inverters` roster - no trailing `?` - so a config declaring a roster and omitting it on any entry is refused at startup. Verified against the deployed |
||
|
|
4482cd8201 | Merge pull request 'SAFETY-41: raise the clamp alarm's re-assert 30 s -> 150 s' (#52) from SAFETY-41-reassert into release/1.0 | ||
|
|
3527c8a04c |
SAFETY-41: escalate a sustained engagement, so a runaway is never held
checks / unit (pull_request) Successful in 4m59s
Review found the case I asked it to construct, and it is not a corner case. The rate limit alone DELAYS A RUNAWAY: a benign one-cycle clamp that spends the budget, then a continuous §10.3-shaped runaway, held the runaway's first notification for up to 140 s - one REASSERT_S minus a cycle. On the live install, where ordinary railing spends the budget essentially all the time, a runaway arriving during normal operation would be delayed with near-certainty. That is the "benign noise suppresses the bug signal" shape this module's docstring is written against, and the family the first attempt at this card died of. THE ESCALATION. An episode that has not yet spoken because an EARLIER, unrelated episode spent the budget speaks anyway once it has engaged SUSTAINED_CYCLES = 3 times in a row. The discriminator is run length and the two populations genuinely differ: the live flood was runs of length ONE (engage, de-assert, engage), while a runaway engages every cycle. Measured, and it costs nothing it was protecting: live scatter flood (305 cycles, 1-in-6) 11 -> 11 notifications chatter 1-engaged/3-clean over 8000 s 50 -> 50 notifications pinned 900 s quarter (floor is 5) 6 -> 6 alarms runaway delay after a benign episode 140 s -> 10 s ⚠️ MY COUNTERFACTUAL CHECK COULD NOT FAIL FOR THE DEFECT IT NAMED, and review caught that too. It read `ClampWatchdog().note(True, ...) is True` - a FRESH object, which only exercises the `last_alarm is None` branch, the trivially-true one. A fresh watchdog has no earlier episode to be held back BY. It now SPENDS THE BUDGET FIRST: benign clamp, gap past CLEAR_CYCLES, then a continuous runaway, and asserts the delay is well under REASSERT_S. That is the third instance in this file of the family recorded at line 216 and at the 224 s sweep, and it was guarding the most safety-critical property in the change. Also pinned: `last_alarm` SURVIVING the de-assert. Review built the mutation - if the de-assert also refreshed it, chatter collapses from 50 notifications to 1 and the alarm never fires again, with the suite green. That is the "alarm that never fires" class, a different bug from one that fires later. Now caught. Both new checks verified against the mutations they name: removing the escalation -> 1 FAILED; refreshing last_alarm on de-assert -> 1 FAILED. Full suite: 21 passed, 0 failed. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
8790c4d38f |
SAFETY-41: rate-limit the RISING EDGE, which is where the flood came from
checks / unit (pull_request) Successful in 5m9s
Review falsified the first version of this change, and the correction is the substance of it. Raising REASSERT_S 30 -> 150 removed NONE of the owner's notifications. The re-assert interval governs only the still-engaged path; the rising edge fired unconditionally. At the measured ~5 s cycle the live pattern - 48 engagements in ~25 minutes, about one cycle in six - leaves ~25 s of clean cycles between engagements, past CLEAR_CYCLES x 5 s = 15 s. So the alarm DE-ASSERTED between almost every engagement and each one returned as a fresh rising edge. Measured on the shipped class over that window: 48 episodes, 48 notifications at REASSERT_S = 30, and still 48 at 150. The interval now bounds the NOTIFICATION RATE rather than the repeat rate within one episode: `last_alarm` survives a de-assert, and a new episode speaks only if the interval has elapsed. Same window afterwards: 51 episodes, 51 engagements, 11 notifications. ⚠️ NOTHING IS DROPPED, AND THE TWO PROPERTIES THAT MATTER ARE PINNED: - a PINNED loop still speaks 6 times in the 900 s billing quarter, against a floor of 5 (part 2, unchanged); - a rising edge from a COLD watchdog still fires IMMEDIATELY, so a runaway beginning from quiet is never held back by a budget spent on an earlier, unrelated episode. That check is the counterfactual and it is the half that would go red if the limit ignored elapsed silence. Every engagement is still counted, every episode still increments, and the action-log row is still written on every engaged cycle. The budget is on notifications, never on evidence. The new pin is written in wall-clock seconds and in the shape the field produced, so it does not move when the constant does. Verified by reverting the rising edge to unconditional: 2 checks go RED naming it. Full suite: 21 passed, 0 failed. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |