SAFETY-37: correct a wall-clock tick and a false size claim
checks / unit (pull_request) Successful in 5m32s
checks / unit (pull_request) Successful in 5m32s
Two blocking findings from review, both in prose, both corrected at every site. 1. "trips on tick 7" was not what the fixture prints. It prints 11, five runs out of five, and the developer's own report says 11. ⚠️ But the deeper problem is that the number should never have been quoted: the tick is counted on the WALL CLOCK inside cycle() (hold_s 2 s, ticks 0.20 s apart), so it is load-dependent - 7 is what a box slow enough to stretch each tick to ~0.29 s would print - and nothing pins it. The DECISIONS transcript now says 11 because it is a transcript of a run; the CHANGELOG stops quoting a tick at all and states the checkable thing instead: it trips without the gate and never with it, which part 3 grades. 2. ⚠️ SURVIVOR 2's SIZE CLAIM WAS FALSE FOR ONE OF THE TWO CONSUMERS THIS CARD EXISTS TO PROTECT. It read "one contributing at most 250 W to a loop whose reporting floor is 700 W" at three sites. That bounds the COMMAND. Once the register is frozen its REPORTED value is unrelated to the command - which is exactly HW-01's shape: commanded ~0 W, register stuck on the last large number. Measured in review: a unit frozen at -1200 W beside a healthy +900 W sibling yields circulating_w = 1800 W against the 700 W floor, 2.6x OVER, with no gate armed. So the scoping is TRUE for the per-unit sign check and FALSE for circulation. Corrected to say exactly that, and the circulation consumer's exposure below MOVE_W is now recorded as a KNOWN GAP rather than a covered one. It survived because part 9's S2 check asserts only `not stale` and part 4 pairs the frozen unit with a RESTING sibling (circulating_w([A_FROZEN_W, 0.0]) == 0.0) - neither grades the size sentence. No behaviour change. Full suite: 22 passed, 0 failed. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
co-authored by
Claude Opus 5
parent
6864109a01
commit
8e241a3243
@@ -49,7 +49,10 @@ reports a different value.
|
||||
|
||||
At two or more inverters it also removes two false alarms that had no gate at
|
||||
all: [[SAFETY-30]]'s per-unit sign check no longer trips on a frozen reading
|
||||
(measured: it trips on tick 7 without the gate, never with it), and
|
||||
(measured: it trips without the gate and NEVER with it - the tick index is
|
||||
deliberately not quoted, because it is counted on the wall clock inside
|
||||
`cycle()` and is therefore load-dependent; the checkable statement is the
|
||||
presence or absence of the trip, which part 3 grades), and
|
||||
[[SAFETY-31]]'s circulating-power sensor reports `None` instead of a loop that is
|
||||
not happening.
|
||||
|
||||
|
||||
@@ -218,7 +218,7 @@ The counterfactual is run, not argued. `test_freshness.py` part 3 drives real
|
||||
```
|
||||
standing on A: [0, 445, 890, 1335, 1335, ...] (the shipped control law)
|
||||
gated : sign trip tick=None circulating_w=[1800, 1800, 1800, None, None, ...]
|
||||
counterfact : sign trip tick=7 circulating_w=[1800, 1800, 1800, 1800, 1800, ...]
|
||||
counterfact : sign trip tick=11 circulating_w=[1800, 1800, 1800, 1800, 1800, ...]
|
||||
```
|
||||
|
||||
---
|
||||
@@ -257,7 +257,7 @@ surprises.
|
||||
| # | kind | what survives | size |
|
||||
|---|---|---|---|
|
||||
| 1 | **false positive** | an inverter physically unable to follow — saturating, thermally derating, or a BMS refusing a charge — is declared stale while telling the truth | one spurious **site stop**, behind `stale_input_s`, self-clearing the moment the register moves. It cannot drive the battery anywhere |
|
||||
| 2 | **miss** | a register frozen under a command that never travels 250 W is never detected, for 400 s or for ever | scoped, not overlooked: such a unit is one no per-unit sign check can speak about (`unit_sign_disagree_w` = 250 W) and one contributing at most 250 W to a loop whose reporting floor is 700 W |
|
||||
| 2 | **miss** | a register frozen under a command that never travels 250 W is never detected, for 400 s or for ever | ⚠️ scoped for ONE consumer, NOT both, and the earlier claim here was wrong. TRUE for the per-unit sign check: no such check can speak about that unit (`unit_sign_disagree_w` = 250 W). **FALSE for circulation.** "Contributing at most 250 W" bounds the COMMAND; once the register is frozen its REPORTED value is unrelated to the command, which is exactly HW-01's shape - commanded ~0 W, register stuck on the last large number. Measured: a unit frozen at −1200 W beside a healthy +900 W sibling yields `circulating_w` = **1800 W against the 700 W floor, 2.6× over**, with no gate armed. Found in review; part 9's S2 check asserts only `not stale` and part 4 pairs the frozen unit with a RESTING sibling, so neither graded the sentence |
|
||||
| 3 | **miss — the largest** | a dead publisher whose last values **alternate**, or a cache replaying two old samples, never starts the unchanged clock at all | **this gate detects a value that STOPPED; it cannot detect a value that is WRONG.** Nothing in this add-on can. TEL-06's arrival stamp inside the firmware is the only layer that could |
|
||||
|
||||
Recorded because it looks like a survivor and is not: a publisher failure that
|
||||
|
||||
@@ -136,10 +136,19 @@ only one of them is WIRED - see `BOUNDS` below and the note on SoC.
|
||||
number here would be a guess wearing a measurement's clothes.
|
||||
|
||||
WHAT IT COSTS, stated rather than absorbed: a frozen 0x0518 on a unit that is
|
||||
never asked to move 250 W is not detected by this module at all. That unit is
|
||||
also one no per-unit sign check can speak about (`unit_sign_disagree_w` is
|
||||
250 W) and one contributing at most 250 W to a circulating loop whose floor is
|
||||
700 W. The gate is scoped to where the consumers can be misled, on purpose.
|
||||
never asked to move 250 W is not detected by this module at all.
|
||||
|
||||
⚠️ THAT COST IS BOUNDED FOR ONE CONSUMER AND NOT FOR THE OTHER, and an earlier
|
||||
version of this note claimed both. TRUE for the per-unit sign check: no such
|
||||
check can speak about that unit either, since `unit_sign_disagree_w` is 250 W.
|
||||
FALSE for circulation. "Contributing at most 250 W" bounds the COMMAND - but a
|
||||
frozen register's REPORTED value is unrelated to its command, and that is
|
||||
precisely HW-01's shape: commanded ~0 W, register stuck on the last large
|
||||
number. Measured in review: a unit frozen at -1200 W beside a healthy +900 W
|
||||
sibling gives `circulating_w` = 1800 W against a 700 W floor, 2.6x over, with
|
||||
no gate armed. So this gate is scoped to where the SIGN consumer can be misled;
|
||||
the circulation consumer keeps an unbounded exposure below MOVE_W and that is
|
||||
a known, stated gap rather than a covered one.
|
||||
|
||||