glenn schrooyenandClaude Opus 5 3527c8a04c
checks / unit (pull_request) Successful in 4m59s
SAFETY-41: escalate a sustained engagement, so a runaway is never held
Review found the case I asked it to construct, and it is not a corner
case. The rate limit alone DELAYS A RUNAWAY: a benign one-cycle clamp
that spends the budget, then a continuous §10.3-shaped runaway, held the
runaway's first notification for up to 140 s - one REASSERT_S minus a
cycle. On the live install, where ordinary railing spends the budget
essentially all the time, a runaway arriving during normal operation
would be delayed with near-certainty. That is the "benign noise
suppresses the bug signal" shape this module's docstring is written
against, and the family the first attempt at this card died of.

THE ESCALATION. An episode that has not yet spoken because an EARLIER,
unrelated episode spent the budget speaks anyway once it has engaged
SUSTAINED_CYCLES = 3 times in a row. The discriminator is run length and
the two populations genuinely differ: the live flood was runs of length
ONE (engage, de-assert, engage), while a runaway engages every cycle.

Measured, and it costs nothing it was protecting:
  live scatter flood (305 cycles, 1-in-6)   11 -> 11 notifications
  chatter 1-engaged/3-clean over 8000 s     50 -> 50 notifications
  pinned 900 s quarter (floor is 5)          6 ->  6 alarms
  runaway delay after a benign episode     140 s -> 10 s

⚠️ MY COUNTERFACTUAL CHECK COULD NOT FAIL FOR THE DEFECT IT NAMED, and
review caught that too. It read `ClampWatchdog().note(True, ...) is True`
- a FRESH object, which only exercises the `last_alarm is None` branch,
the trivially-true one. A fresh watchdog has no earlier episode to be
held back BY. It now SPENDS THE BUDGET FIRST: benign clamp, gap past
CLEAR_CYCLES, then a continuous runaway, and asserts the delay is well
under REASSERT_S. That is the third instance in this file of the family
recorded at line 216 and at the 224 s sweep, and it was guarding the most
safety-critical property in the change.

Also pinned: `last_alarm` SURVIVING the de-assert. Review built the
mutation - if the de-assert also refreshed it, chatter collapses from 50
notifications to 1 and the alarm never fires again, with the suite green.
That is the "alarm that never fires" class, a different bug from one that
fires later. Now caught.

Both new checks verified against the mutations they name: removing the
escalation -> 1 FAILED; refreshing last_alarm on de-assert -> 1 FAILED.

Full suite: 21 passed, 0 failed.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-05 18:13:09 +02:00

GoodWe RS485 Controller — Home Assistant add-on repository

Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.

repository.yaml            add-on repository metadata
goodwe_controller/         the add-on
  config.yaml              manifest + options schema (the per-site config form)
  app/                     the controller
    control.py             the control law — pure functions, no I/O
    maintenance.py         the monthly cycle state machine
    hass.py                Supervisor/Core API access
    store.py               persistent state in /data
    mqtt.py                optional status entities
    web.py                 ingress UI
    main.py                orchestration, heartbeat, failsafe behaviour
  test_control.py          runnable checks — no framework needed
  test_maintenance.py      runnable checks — walks a full cycle in fake time
  DOCS.md                  the add-on's documentation tab
  MUTATION.md              how to run a mutation so the result means something
  tools/mutation_run.sh    the mutation harness - purges bytecode, then grades
firmware/goodwe-master.yaml  ESPHome config for the T-CAN485
estop/rs485_log.py           optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf  the guide techs carry (10pp, A4)
docs/build_guide.py          its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md             how to edit and rebuild the guide

Picking this up after a break? Read HANDOVER.md first — current state, what is known broken, and what to do next.

Install

Settings → Add-ons → Add-on store → ⋮ → Repositories → add

https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon

then install GoodWe RS485 Controller.

⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it anonymously; against a private repo the store shows nothing and gives no useful error. If it must stay private, install locally instead: copy goodwe_controller/ into the machine's /addons/ folder, then ha store reload — it appears as a Local add-on.

⚠️ Bump version: in goodwe_controller/config.yaml for every change. Supervisor keys the built image by that version, so without a bump it silently reuses the old image and your fix appears not to work — on your bench and on every client's machine.

Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.

Read this first

The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.

Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:

  1. ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
  2. Wind-down before firmware updates — 0 W written before the update starts.
  3. RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.

Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md §10 signed.

Development

The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:

cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py

Both must pass before shipping any change. To prove a check bites - the way almost every claim in this repository was established - mutate the module and run tools/mutation_run.sh, which clears __pycache__ first. It is not optional: a same-size edit reverted inside one second leaves CPython reusing the old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre — each assertion corresponds to a rule whose absence produced an observed failure on real hardware, and the comments in control.py say which.

Compatibility

Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:

tag platform verdict
ESU EMU ESA BPS BPU EMJ IJL 105 — ES/EM/BP, AA55-era meter bus supported
SPB SPN 745 — SBP G2 (GW…-SBP-20) no
ESN ESC 745 — ES G2 (GW…-ES-20) no
ETU EHU BTU … 205/745/753 — ET/EH/BT hybrids no
SDT DST MSU NSU … PV-only inverters — no battery to control no

A "-20" or "G2" suffix means a different platform with a different meter protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which is also what Home Assistant's own integration uses to pick a protocol.

  • GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
  • The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.
S
Description
No description provided
Readme
20 MiB
Languages
Python 98.2%
JavaScript 1.2%
CSS 0.3%
HTML 0.2%
Shell 0.1%