`pos, neg = opposing(...)` -> `([], [])` in main.py's `check_circulating()`
(-102 B) deletes the "Right now X is discharging while Y charges" clause from
the operator notification, and SURVIVED ALL 26 FILES. The commit that shipped
this card claimed "18 mutations, all RED"; the ledger has no entry for the
attribution, and this is that entry.
It is not dead code. Ledger M18 - the whole `await check_circulating()` call
removed - is red on four checks, so the function runs. The three checks on the
notification asserted METER CANNOT SEE, CONTROL HAS BEEN STOPPED and `isolator`,
and never an inverter name. `circulation.py`'s own docstring calls that sentence
the first thing somebody woken by this alarm needs and "impossible to
reconstruct from the number alone".
test_watchdog.py section 6a closes it on a fixture that can tell three failures
apart:
* the roster is ["garage", "shed", "cellar"] - operator names, none of them
`UNIT_A`, for test_maintenance.py section 11's reason: on a fixture whose
names are the module's own constants a check cannot tell the roster from
the constant;
* the site is run TWICE, MIRRORED, so the sentence is not symmetric and a
pos/neg swap is a different red from a deletion;
* a third pack rests at 5 W, so the floor that stops a pack in standby being
named as a participant in a 6 kW loop is graded too.
Mutations, on a tree with no __pycache__ mounted :ro into the checks image:
M20 pos, neg = opposing(...) -> ([], []) -102 B RED (2 checks)
M21 pos and neg exchanged +0 B RED (3 checks)
M22 opposing(..., min_w=cfg.min_w/2.0) -> 0.0 -25 B RED (3 checks)
26/26 files green with the block in place.
AND A DISCLOSURE, WHICH IS THE UNCOMFORTABLE HALF. DECISIONS section 3 records
that the 924-run campaign behind `circulation_w: 700` and `circulation_hold_s:
75` used a harness that is not committed in either repository. Two further
sweeps have now been run and no two of the three agree: peaks of 1700 W, 2750 W
and 1048 W, and worst-continuous figures above 700 W of 5.0 s, 15.0 s and 5.0 s.
That is NOT evidence of fabrication and is not reported as any. The committed
sweep measures why the spread is that wide: on one grid, changing only the
plant model and the write-stagger set, the worst legitimate peak is 1048 W, or
2250 W, or 0 W. The plant and the stagger are TERMS of the number. What the
spread does establish is that the claim cannot be adjudicated while the
instrument is missing.
The window argument survives and is now committed - all three sweeps trip zero
times, on 924 + 48 + 840 non-faulty runs. The threshold CURVE does not survive
as stated: `505.0 s at 100 W`, which is what the "knee at 400 W" argument rests
on, is 10.0 s on the committed grid. The curve still falls with the threshold,
so the knee is real in direction; its depth is established by nothing anybody
can run, and this commit says so rather than repeating it. The overclaiming
comment at test_watchdog.py's 1700 W fixture ("the worst single transient the
rig can produce") is replaced with what the fixture can support.
The committed, re-runnable half is admin/goodwe's `two_master_circulation`,
opened as a separate PR against that repository.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
GoodWe RS485 Controller — Home Assistant add-on repository
Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.
repository.yaml add-on repository metadata
goodwe_controller/ the add-on
config.yaml manifest + options schema (the per-site config form)
app/ the controller
control.py the control law — pure functions, no I/O
maintenance.py the monthly cycle state machine
hass.py Supervisor/Core API access
store.py persistent state in /data
mqtt.py optional status entities
web.py ingress UI — routes only, status and configuration
config_page.py the configuration page's markup, style and script
configui.py its field model, built from the Supervisor's own
schema + translations — owns no key, label or rule
selfconfig.py reading and writing this add-on's own options,
with the validate-first / compare-and-swap gate
main.py orchestration, heartbeat, failsafe behaviour
test_control.py runnable checks — no framework needed
test_maintenance.py runnable checks — walks a full cycle in fake time
DOCS.md the add-on's documentation tab
MUTATION.md how to run a mutation so the result means something
tools/mutation_run.sh the mutation harness - purges bytecode, then grades
tools/supervisor_selfapi_probe.py what the Supervisor really permits and
returns, run against its own release image
firmware/goodwe-master.yaml ESPHome config for the T-CAN485
estop/rs485_log.py optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf the guide techs carry (10pp, A4)
docs/build_guide.py its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md how to edit and rebuild the guide
Picking this up after a break? Read HANDOVER.md first — current state,
what is known broken, and what to do next.
Install
Settings → Add-ons → Add-on store → ⋮ → Repositories → add
https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install GoodWe RS485 Controller.
⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
goodwe_controller/ into the machine's /addons/ folder, then
ha store reload — it appears as a Local add-on.
⚠️ Bump version: in goodwe_controller/config.yaml for every change.
Supervisor keys the built image by that version, so without a bump it silently
reuses the old image and your fix appears not to work — on your bench and on
every client's machine.
Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.
Read this first
The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.
Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:
- ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
- Wind-down before firmware updates — 0 W written before the update starts.
- RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.
Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md
§10 signed.
Development
The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:
cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py
Both must pass before shipping any change. To prove a check bites - the way
almost every claim in this repository was established - mutate the module and
run tools/mutation_run.sh, which clears __pycache__ first. It is not
optional: a same-size edit reverted inside one second leaves CPython reusing the
old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md
has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre —
each assertion corresponds to a rule whose absence produced an observed failure
on real hardware, and the comments in control.py say which.
Compatibility
Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:
| tag | platform | verdict |
|---|---|---|
ESU EMU ESA BPS BPU EMJ IJL |
105 — ES/EM/BP, AA55-era meter bus | supported |
SPB SPN |
745 — SBP G2 (GW…-SBP-20) |
no |
ESN ESC |
745 — ES G2 (GW…-ES-20) |
no |
ETU EHU BTU … |
205/745/753 — ET/EH/BT hybrids | no |
SDT DST MSU NSU … |
PV-only inverters — no battery to control | no |
A "-20" or "G2" suffix means a different platform with a different meter
protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which
is also what Home Assistant's own integration uses to pick a protocol.
- GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
- The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.