Review fixes.
A. test_loop.py takes 73 s, not the ~35 s claimed in three places. That number
is the whole defence against a future developer deleting a slow test, so it was
understated by 2x in exactly the place it matters. Corrected - and it is now
~95 s (measured 93 s), because this commit adds the scenario below rather than
trimming windows to make an inconvenient number smaller. Both call sites carry
an instruction to re-measure if the windows change.
B. "242 checks" was test_p1's own count quoted as the total for all five
suites. The real figure is 395 across the five, plus 14 here.
And the finding this PR should have led with. stale_input_s and the
`inputs missing -> 0 W` claim both live INSIDE cycle(), so pre-fix, on a meter
whose value happened to repeat, that claim could not fire at all. Constant
meter, SoC entity dying at t=4 s, one binary:
pre-fix final target 220.0 W, reason 'loop -> 220 W'
post-fix final target 0.0 W, reason 'safety -> 0 W'
The old controller held 220 W through the whole input outage with its status
line still reading loop -> 220 W, and layer 1 does not cover that on a
`meter_source: off` install - no P1 age sensor is published, so the firmware has
nothing to veto on, while the heartbeat keeps its watchdog fed. The pre-fix
behaviour was not "holds a stale command safely"; it was a failsafe a repeating
meter switched off. Asserted in test_loop.py, both halves.
Three points of reasoning tightened, none of them wrong before:
- the re-tune is unreachable by construction, not merely by the reset: the
combined cycle rate is max(arrival rate, 1/floor), never the sum, and 1/15 s
is strictly slower than the ~1/5 s arrival rate. That holds only while the
floor exceeds the meter's update interval - and the schema minimum of 5 s is
exactly the reference meter's interval. Flagged for validate.py, not fixed
here.
- the ~11 s lower bracket is not only a dropped poll: a 5.0 s poller against a
4.97 s meter beats, so about every 14 minutes the poller steps over an update
entirely. Reaching 15 s takes a beat-skip AND a failed poll.
- the "freshness is decided upstream" guarantee is transport-conditional. On
`meter_source: off` the grid figure comes straight from hass.number() with no
age gate. Running the full law is still right; the claim is narrower than it
was stated.
The 15 s default is not independently justified - it rests on the firmware's
30 s ingest veto and moves if that ever does. Said beside the constant.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
test_loop.py proves the property in 35 s. This is the same three scenarios run
for six and three real minutes each, on one binary, and it is what AC2 and AC3
were actually asked for: 1 cycle before vs 24 after on a constant meter with the
command stuck at 220 W against a 350 W import, and byte-identical write
sequences on both the converged and the normally-changing meter.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
The pre-deploy command listed three of the five suites; test_validate and
test_p1 were never added when they arrived. Adds those and test_loop, with a
note that test_loop's ~35 s is the cost of proving a wall-clock property about a
loop that sleeps 1 s a tick rather than a sign something is wrong.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
run_control() ran cycle() only when the meter value differed from the previous
poll. A meter that repeats a value therefore ran no control cycles at all -
while the heartbeat kept re-emitting the last command and the firmware kept
putting it on the wire every 2 s. Layer 1 stayed fed and every indicator read
healthy, so a command computed from an old reading went on being executed
through whatever the load did next. TEL-05 measured it: 70 s at a literally
constant 350.0 W, 14 arrivals, zero cycles.
cycle_floor_s (default 15 s) is a deadline on the GAP between cycles, reset by
every cycle whichever trigger fired - not a second scheduler. On a healthy meter
it never elapses, so the cycle rate and the commanded sequence are unchanged;
test_loop.py asserts that by driving the real loop twice on one binary (a huge
cycle_floor_s reproduces the old behaviour) and diffing the writes.
15 s is bracketed: above the ~11 s worst gap on a merely-unlucky healthy meter
(~5 s arrivals, 1 s detection, one dropped poll retried on the next tick), below
meter_max_age_s and the firmware's 30 s ingest veto, and equal to stale_input_s.
A floor cycle runs the full law. Freshness is already decided upstream - past
meter_max_age_s the reading is None, which is a P_SAFETY 0 W claim - and the
integrator advances per cycle, not per second, so bounding the gap bounds the
accumulation.
Not a freeze detector: nothing here decides whether a repeated reading is true.
DOCS.md's "accepted deviation" passage is qualified rather than deleted - the
window is now bounded at 3 x cycle_floor_s instead of open-ended, and its
"nothing accumulates while it is stalled" argument is called out as having
covered windup and not staleness. Same correction in control.py's comment.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa