SAFETY-12: a minimum loop cadence - the loop thinks on a clock, not only when the number moves #7
@@ -84,6 +84,18 @@ per-cycle gain the tuning was measured against are unchanged - asserted in
|
||||
`cycle_floor_s` reproduces the old behaviour exactly) and comparing the
|
||||
commanded values.
|
||||
|
||||
Observed over six real minutes on the same rig, one binary, meter held at a
|
||||
literally constant 350.0 W: **before, 1 cycle** (at startup) and then nothing,
|
||||
the command stuck at 220 W against a 350 W import for the rest of the window.
|
||||
**After, 24 cycles**, worst gap 15.14 s, and the ordinary PI ramp doing its job -
|
||||
220, 430, 650, 860, 1080, 1300, 1510, 1730, 1940, 2000 W, one step per cycle,
|
||||
rail at t=136 s and flat after. Three minutes with the meter parked at the
|
||||
target instead: **1 cycle before, 12 after, and 19 writes either way - the same
|
||||
19**. Three minutes on a normally-changing meter: **36 cycles and 49 writes on
|
||||
both sides, the same values in the same order.** The heartbeat write count never
|
||||
moves; the only writes the fix adds are the ten the loop was supposed to be
|
||||
making all along.
|
||||
|
||||
15 s is bracketed, not round. Below it: arrivals are ~5 s (NOTES.md measures
|
||||
4.97 s), detected up to 1 s late by the 1 s poll, and one dropped poll is
|
||||
retried on the next tick - about 11 s worst case on a meter that is merely
|
||||
|
||||