SAFETY-12: the loop thinks on a clock, not only when the number moves
run_control() ran cycle() only when the meter value differed from the previous poll. A meter that repeats a value therefore ran no control cycles at all - while the heartbeat kept re-emitting the last command and the firmware kept putting it on the wire every 2 s. Layer 1 stayed fed and every indicator read healthy, so a command computed from an old reading went on being executed through whatever the load did next. TEL-05 measured it: 70 s at a literally constant 350.0 W, 14 arrivals, zero cycles. cycle_floor_s (default 15 s) is a deadline on the GAP between cycles, reset by every cycle whichever trigger fired - not a second scheduler. On a healthy meter it never elapses, so the cycle rate and the commanded sequence are unchanged; test_loop.py asserts that by driving the real loop twice on one binary (a huge cycle_floor_s reproduces the old behaviour) and diffing the writes. 15 s is bracketed: above the ~11 s worst gap on a merely-unlucky healthy meter (~5 s arrivals, 1 s detection, one dropped poll retried on the next tick), below meter_max_age_s and the firmware's 30 s ingest veto, and equal to stale_input_s. A floor cycle runs the full law. Freshness is already decided upstream - past meter_max_age_s the reading is None, which is a P_SAFETY 0 W claim - and the integrator advances per cycle, not per second, so bounding the gap bounds the accumulation. Not a freeze detector: nothing here decides whether a repeated reading is true. DOCS.md's "accepted deviation" passage is qualified rather than deleted - the window is now bounded at 3 x cycle_floor_s instead of open-ended, and its "nothing accumulates while it is stalled" argument is called out as having covered windup and not staleness. Same correction in control.py's comment. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
This commit is contained in:
co-authored by
Claude Opus 5
parent
e2e331ea54
commit
88cd97cc7a
@@ -67,6 +67,62 @@ A refusal is legible as a refusal: a banner that says in words that this is a
|
||||
configuration problem and nothing is broken, the numbered problems, no traceback,
|
||||
and exit status 78 (`EX_CONFIG`).
|
||||
|
||||
**SAFETY-12.** The control loop now evaluates on a clock as well as on a change.
|
||||
`run_control()` ran `cycle()` only when the meter value differed from the
|
||||
previous poll, so a meter that repeated a value ran **no control cycles at
|
||||
all** - while the heartbeat went on re-emitting the last command and the
|
||||
firmware went on putting it on the wire every 2 s. Layer 1 stayed fed, every
|
||||
indicator read healthy, and a command computed from an old reading kept being
|
||||
executed through whatever the load did next. Measured on the rig during TEL-05:
|
||||
70 s at a literally constant 350.0 W with 14 arrivals and zero cycles.
|
||||
|
||||
`cycle_floor_s` (default **15 s**) is a deadline on the gap between cycles, not
|
||||
a second scheduler: every cycle resets it, whichever trigger fired. On a healthy
|
||||
meter it never elapses, so the cycle rate, the write sequence and therefore the
|
||||
per-cycle gain the tuning was measured against are unchanged - asserted in
|
||||
`test_loop.py` by driving the real loop twice on one binary (a huge
|
||||
`cycle_floor_s` reproduces the old behaviour exactly) and comparing the
|
||||
commanded values.
|
||||
|
||||
15 s is bracketed, not round. Below it: arrivals are ~5 s (NOTES.md measures
|
||||
4.97 s), detected up to 1 s late by the 1 s poll, and one dropped poll is
|
||||
retried on the next tick - about 11 s worst case on a meter that is merely
|
||||
unlucky, which the floor must not fire on. Above it: `meter_max_age_s` is 30 s,
|
||||
past which there is no reading to evaluate, and the firmware's ingest veto is
|
||||
also 30 s - so the loop is guaranteed to have re-decided at least twice inside
|
||||
any window in which layer 1 might otherwise be the only thing deciding. It is
|
||||
also exactly `stale_input_s`, this system's existing answer to "how long may we
|
||||
hold without re-deciding".
|
||||
|
||||
A floor cycle runs the **full** law on the same inputs, integrator included. The
|
||||
freshness question is already answered upstream and answered harder - past
|
||||
`meter_max_age_s` the reading is None, which is "inputs missing", which is a
|
||||
`P_SAFETY` 0 W claim - so a floor cycle can only ever run on a reading this
|
||||
system already calls fresh. The integrator advances per *cycle*, not per second,
|
||||
so bounding the gap bounds the accumulation; `integrator_max_w` bounds it after
|
||||
that. A gentler second law for floor cycles would be a second set of dynamics
|
||||
nobody can test on this hardware.
|
||||
|
||||
⚠️ **This is not a freeze detector**, and TEL-05 established one cannot be built
|
||||
here: at the converged -10 W target a 1 Wh register needs ~6 minutes to move
|
||||
while the power figure legitimately repeats, so any threshold on `unchanged_s`
|
||||
false-trips at the exact operating point we run at. Nothing in this change
|
||||
decides whether a repeated reading is *true*. It stops "the number is the same"
|
||||
from meaning "do not think". The consequence, stated plainly: against a meter
|
||||
genuinely frozen at a wrong value the loop will now correct toward that wrong
|
||||
value rather than hold a stale command, bounded by `max_w`, the arbiter and the
|
||||
device rating. That was already what happened to a lying meter whose value
|
||||
merely jittered; bit-exact repetition was never a safety property.
|
||||
|
||||
`DOCS.md`'s "Saturation is counted in cycles, not seconds" section documented
|
||||
the old behaviour as an accepted deviation. It is **qualified, not deleted**:
|
||||
the deviation survives (the window is still counted in cycles, and 3 x 15 s is
|
||||
still not the specification's 10 s) but it is now bounded at 45 s instead of
|
||||
open-ended, and the passage's second justification - "nothing accumulates while
|
||||
it is stalled" - is called out as having covered integrator windup and not
|
||||
staleness, which was the actual hazard. The same wrong argument in
|
||||
`control.py`'s saturation comment is corrected too.
|
||||
|
||||
**TEL-04.** `meter_source: ha_signed` reads a single *signed* power entity, which
|
||||
is the shape a HomeWizard P1 publishes. Both transports 0.3.0 shipped require two
|
||||
unsigned registers and refuse negatives, so neither fits the meter installed here.
|
||||
|
||||
+36
-14
@@ -272,9 +272,10 @@ behind it would trip the firmware watchdog on a system that is working fine.
|
||||
| `target_grid_w` | -10 | What the meter should rest at. Negative = a slight export |
|
||||
| `step_w` | 10 | Quantisation |
|
||||
| `saturation_w` | 500 | Divergence that counts as "the inverter is at a limit" |
|
||||
| `saturation_cycles` | 3 | How many consecutive cycles before freezing. A cycle is one *changed* meter reading, not a fixed period - see the note below. **Do not set to 1** |
|
||||
| `saturation_cycles` | 3 | How many consecutive cycles before freezing. A cycle is one meter update or `cycle_floor_s`, whichever comes first - see the note below. **Do not set to 1** |
|
||||
| `integrator_max_w` | 0 | Bound on the loop's accumulator, and 0 means "same as `max_w`". Caps how much stale error can be waiting to unwind when the sign flips. **Do not raise it above `max_w`** - the output clamp already bounds what is commanded, so the only thing extra headroom buys is more cycles of wrong-direction power after every saturation event. Lowering it below `max_w` is the useful direction |
|
||||
| `heartbeat_s` | 10 | Refresh interval; must stay well under the firmware watchdog |
|
||||
| `cycle_floor_s` | 15 | The longest the loop may go without evaluating. A deadline on the gap between cycles, reset by every cycle — on a healthy meter it never elapses and changes nothing. Raise it only if your meter is slower than ~10 s; it must stay under `meter_max_age_s`, past which there is no reading to evaluate anyway |
|
||||
| `stale_input_s` | 15 | How long inputs may be missing before commanding 0 W. In P1 mode this clock starts only *after* `meter_max_age_s` has already expired — the two stack, see "How long a dead meter takes to reach 0 W" |
|
||||
| `auto_start` | false | Start controlling on boot (only after commissioning) |
|
||||
|
||||
@@ -284,22 +285,43 @@ The specification states the saturation window as **"> 10 s"**. This add-on coun
|
||||
**cycles** instead, and that is a deliberate, accepted deviation rather than an
|
||||
oversight - the acceptance criterion is not met as literally written.
|
||||
|
||||
A cycle here is one *changed* meter reading: the controller only runs the loop when the
|
||||
meter value differs from the previous poll. At the reference P1's ~5 s update rate the
|
||||
default of 3 cycles is usually around 15 s, but there is **no guaranteed wall-clock
|
||||
window** - a meter that repeats the same value stalls the counter for as long as it
|
||||
repeats.
|
||||
A cycle here is one meter update **or `cycle_floor_s` elapsing, whichever comes
|
||||
first**. At the reference P1's ~5 s update rate the default of 3 cycles is usually
|
||||
around 15 s, and the worst case is bounded at `3 x cycle_floor_s` = 45 s. It is still
|
||||
not the 10 s the specification asks for, so the deviation stands - but it is now a
|
||||
bounded number rather than an open one.
|
||||
|
||||
Two reasons that is acceptable:
|
||||
⚠️ **This passage used to say something different, and the second half of it was
|
||||
wrong.** Until SAFETY-12 the loop ran only when the meter value *changed*, so a meter
|
||||
that repeated a value stalled the counter for as long as it repeated, with no upper
|
||||
bound at all. That was defended here on the grounds that "a stalled counter is a
|
||||
detection-latency limit and not a runaway risk - the condition that stalls it stops the
|
||||
whole loop, so nothing accumulates while it is stalled". That argument covers
|
||||
**integrator windup and nothing else**. The hazard it misses is **staleness**: while the
|
||||
loop was stopped the heartbeat kept re-emitting the last command and the firmware kept
|
||||
putting it on the wire every 2 s, so a command computed from an old reading went on
|
||||
being executed through a real load change, with every indicator reading healthy.
|
||||
Measured on the rig during TEL-05: 70 s at a literally constant 350.0 W, 14 arrivals,
|
||||
zero control cycles.
|
||||
|
||||
- the control law is a pure function with no clock, which is what makes it testable
|
||||
without hardware, and a seconds-based window would have to live in the controller;
|
||||
- a stalled counter is a detection-latency limit and not a runaway risk. The condition
|
||||
that stalls it - an unchanging meter - stops the whole loop, so nothing accumulates
|
||||
while it is stalled.
|
||||
The half that survives is the first one: the control law is still a pure function with
|
||||
no clock, and the wall-clock window still lives in `Controller`, which has one - see
|
||||
`run_control()`. What changed is that the controller now enforces a floor on the gap
|
||||
between cycles, so `saturation_cycles` finally means a bounded number of seconds.
|
||||
|
||||
If a guaranteed window matters on your site, raise `saturation_cycles` for a fast meter,
|
||||
and treat the figure as "N meter updates" rather than "N seconds".
|
||||
If a tighter window matters on your site, lower `cycle_floor_s` (not below your meter's
|
||||
update interval, or the floor starts firing on a healthy meter) or raise
|
||||
`saturation_cycles` for a fast meter.
|
||||
|
||||
**This is not a freeze detector, and it deliberately cannot be one.** Nothing here
|
||||
decides whether a repeated reading is true — see `unchanged_s` in the meter section for
|
||||
why no threshold on that is safe at the converged operating point. The floor only stops
|
||||
"the number is the same" from meaning "do not think". The consequence is worth stating
|
||||
plainly: against a meter that is genuinely frozen at a wrong value, the loop will now
|
||||
correct toward that wrong value instead of holding a stale command. It is bounded by
|
||||
`max_w`, the arbiter and the device rating, and it is the same thing that already
|
||||
happened to a lying meter whose value merely jittered — bit-exact repetition was never a
|
||||
safety property.
|
||||
|
||||
#### Why `target_grid_w` is not zero
|
||||
|
||||
|
||||
@@ -95,19 +95,23 @@ def compute(
|
||||
# lets slew be larger than saturation_w.
|
||||
#
|
||||
# The spec states this window twice and differently: "> 10 s" (§11.2) and
|
||||
# "3 samples" (§10.3). This counts CYCLES, and a cycle is not a unit of
|
||||
# time: run_control() calls cycle() only when the meter value CHANGES
|
||||
# (`if self.grid != last_grid`), so three cycles is three distinct meter
|
||||
# readings and nothing more. At the reference P1's ~5 s update rate that is
|
||||
# usually ~15 s, but there is no upper bound on it - a meter that repeats a
|
||||
# value stalls the counter.
|
||||
# "3 samples" (§10.3). This counts CYCLES, and a cycle is still not a unit
|
||||
# of time - but it is now a BOUNDED one. run_control() runs a cycle on a
|
||||
# changed meter value OR on `cycle_floor_s` elapsing, whichever comes first
|
||||
# (SAFETY-12), so three cycles is at most 3 x cycle_floor_s = 45 s at the
|
||||
# defaults, and usually ~15 s at the reference P1's ~5 s update rate.
|
||||
#
|
||||
# That is a detection-latency limit, not a windup hazard: the same
|
||||
# condition that stalls the counter stalls the whole loop, so nothing
|
||||
# accumulates in the meantime either. If a wall-clock window is ever
|
||||
# required, it belongs in Controller (which has a clock) and not here.
|
||||
# ponytail: this function is worth keeping clockless; the ceiling is that
|
||||
# saturation_cycles cannot express a guaranteed number of seconds.
|
||||
# ⚠️ THIS COMMENT USED TO CLAIM there was no upper bound and that it did not
|
||||
# matter, "because the same condition that stalls the counter stalls the
|
||||
# whole loop, so nothing accumulates in the meantime". The first clause was
|
||||
# true and the second was the bug: a stalled loop does not stop commanding,
|
||||
# it goes on emitting its last command through the heartbeat. Windup was
|
||||
# never the hazard; staleness was.
|
||||
#
|
||||
# The wall-clock window lives in Controller, which has a clock, exactly as
|
||||
# this comment always said it should. ponytail: this function stays
|
||||
# clockless; the remaining ceiling is that saturation_cycles expresses a
|
||||
# bound in seconds rather than an exact number of them.
|
||||
saturated_now = abs(prev_w - actual_w) > tuning.saturation_w
|
||||
sat_count = min(sat_count + 1, 10) if saturated_now else 0
|
||||
frozen = sat_count >= tuning.saturation_cycles
|
||||
|
||||
@@ -342,11 +342,52 @@ class Controller:
|
||||
last_grid = object()
|
||||
heartbeat = float(self.o.get("heartbeat_s", 10))
|
||||
last_beat = 0.0
|
||||
# ⚠️ SAFETY-12. The floor is a DEADLINE ON THE GAP BETWEEN CYCLES, not a
|
||||
# second scheduler running alongside the arrival trigger. Every cycle
|
||||
# resets it, whichever trigger fired, so on a healthy changing meter it
|
||||
# never elapses and not one existing cycle moves - no beat frequency
|
||||
# between the two triggers, no doubled cycle rate, and therefore no
|
||||
# change to the per-cycle gain the tuning was measured against.
|
||||
#
|
||||
# Why it has to exist: `self.grid != last_grid` alone means a meter that
|
||||
# repeats a value runs NO control cycles at all, while the heartbeat
|
||||
# below keeps re-emitting the last command and the firmware keeps
|
||||
# putting it on the wire - so every indicator reads healthy while the
|
||||
# loop has not evaluated and the load may have moved underneath it.
|
||||
# Measured on the rig during TEL-05: 70 s at a literally constant
|
||||
# 350.0 W, 14 arrivals, zero cycles.
|
||||
#
|
||||
# This is NOT a freeze detector, and deliberately so - see
|
||||
# HomeWizardLocalSource.unchanged_s for why one cannot be built here (at
|
||||
# the converged -10 W target a 1 Wh register needs ~6 minutes to move,
|
||||
# so any freeze threshold false-trips at the exact operating point we
|
||||
# run at). Nothing here decides whether a repeated reading is true. It
|
||||
# only stops "the number is the same" from meaning "do not think".
|
||||
floor = float(self.o.get("cycle_floor_s", 15))
|
||||
last_cycle = None
|
||||
while not self.stopping:
|
||||
await self.read_inputs()
|
||||
# A cycle is one meter update, exactly as on the reference install.
|
||||
if self.grid != last_grid:
|
||||
now_mono = asyncio.get_running_loop().time()
|
||||
# A cycle is one meter update, exactly as on the reference install -
|
||||
# or the floor elapsing, whichever comes first.
|
||||
overdue = last_cycle is None or (now_mono - last_cycle) >= floor
|
||||
if self.grid != last_grid or overdue:
|
||||
last_grid = self.grid
|
||||
last_cycle = now_mono
|
||||
# ⚠️ The FULL cycle, not a degraded one. A floor cycle runs the
|
||||
# same law on the same inputs as an arrival cycle, because the
|
||||
# freshness question is already answered upstream and answered
|
||||
# harder: past `meter_max_age_s` (30 s) p1.net_w is None, which
|
||||
# is "inputs missing", which becomes a P_SAFETY 0 W claim. So a
|
||||
# floor cycle can only ever run on a reading this system already
|
||||
# calls fresh - it cannot run the PI on a 60 s old figure,
|
||||
# because at 60 s there is no figure. And the integrator
|
||||
# advances per CYCLE, not per second (control.py), so bounding
|
||||
# the gap bounds the accumulation: at most one extra
|
||||
# gain x error per floor interval, under the same
|
||||
# integrator_max_w as every other cycle. A second, gentler
|
||||
# control law for floor cycles would be a second set of
|
||||
# dynamics nobody can test on this hardware.
|
||||
await self.cycle()
|
||||
# ⚠️ The heartbeat is not an optimisation. The ESP32 treats silence
|
||||
# longer than ~30 s as "the controller is gone" and zeroes the
|
||||
|
||||
@@ -90,6 +90,7 @@ options:
|
||||
integrator_max_w: 0
|
||||
heartbeat_s: 10
|
||||
stale_input_s: 15
|
||||
cycle_floor_s: 15
|
||||
auto_start: false
|
||||
|
||||
# --- maintenance -----------------------------------------------------------
|
||||
@@ -151,6 +152,7 @@ schema:
|
||||
integrator_max_w: int(0,15000)
|
||||
heartbeat_s: int(2,25)
|
||||
stale_input_s: int(5,120)
|
||||
cycle_floor_s: int(5,60)
|
||||
auto_start: bool
|
||||
|
||||
maintenance_enabled: bool
|
||||
|
||||
@@ -0,0 +1,174 @@
|
||||
"""Runnable check for the control loop's cadence. `python3 test_loop.py`
|
||||
|
||||
SAFETY-12: the loop must evaluate on a clock as well as on a change. Before the
|
||||
fix, `run_control()` ran `cycle()` only when the meter value differed from the
|
||||
previous poll, so a meter that repeats a value ran NO control cycles while the
|
||||
heartbeat kept re-emitting the last command - measured on the rig during TEL-05
|
||||
as 70 s at a literally constant 350.0 W with 14 arrivals and zero cycles.
|
||||
|
||||
⚠️ THIS TEST TAKES ~35 SECONDS OF WALL CLOCK, on purpose. The thing under test
|
||||
is a wall-clock floor inside a loop that sleeps 1 s; mocking the clock would
|
||||
leave the assertion testing the mock. It drives the real `run_control()` and
|
||||
counts what actually happened.
|
||||
|
||||
`cycle_floor_s` is read from options with no lower bound in code, so a huge
|
||||
value reproduces the pre-fix behaviour exactly. Every claim below is therefore
|
||||
an A/B on one binary, not a comparison against a remembered old one.
|
||||
"""
|
||||
|
||||
import asyncio
|
||||
import sys
|
||||
import time
|
||||
|
||||
from app.main import Controller
|
||||
|
||||
fails = []
|
||||
NEVER = 1e9 # cycle_floor_s so large the floor can never elapse: pre-fix
|
||||
|
||||
|
||||
def check(name, cond):
|
||||
print(f" {'ok ' if cond else 'FAIL'} {name}")
|
||||
if not cond:
|
||||
fails.append(name)
|
||||
|
||||
|
||||
class FakeHass:
|
||||
"""A scripted meter and a plant that tracks the command instantly."""
|
||||
|
||||
def __init__(self, meter):
|
||||
self.meter = meter
|
||||
self.batt = 0.0
|
||||
self.writes = []
|
||||
self.t0 = time.monotonic()
|
||||
|
||||
async def limits(self, entity):
|
||||
return (-5000.0, 5000.0, 1.0)
|
||||
|
||||
async def number(self, entity, invert=False):
|
||||
if entity == "sensor.grid":
|
||||
return self.meter(time.monotonic() - self.t0)
|
||||
if entity == "sensor.batt":
|
||||
return self.batt
|
||||
if entity == "sensor.soc":
|
||||
return 50.0
|
||||
return None
|
||||
|
||||
async def set_number(self, entity, value):
|
||||
self.writes.append(float(value))
|
||||
self.batt = float(value)
|
||||
return True
|
||||
|
||||
|
||||
class _Store:
|
||||
data = {}
|
||||
|
||||
def set(self, *a):
|
||||
pass
|
||||
|
||||
|
||||
class _Pub:
|
||||
enabled = False
|
||||
|
||||
def publish(self, *a, **k):
|
||||
pass
|
||||
|
||||
def close(self):
|
||||
pass
|
||||
|
||||
|
||||
BASE = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
|
||||
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
|
||||
"meter_source": "off", "max_w": 2000, "gain": 0.6, "slew_w": 1000,
|
||||
"deadband_w": 15, "target_grid_w": -10, "step_w": 10,
|
||||
"heartbeat_s": 10, "stale_input_s": 15}
|
||||
|
||||
|
||||
def drive(meter, floor, seconds):
|
||||
"""Run the real control loop for `seconds`; return (cycle times, writes)."""
|
||||
async def go():
|
||||
hass = FakeHass(meter)
|
||||
c = Controller(dict(BASE, cycle_floor_s=floor), hass, _Store(), _Pub(),
|
||||
stop=asyncio.Event())
|
||||
c.auto = True
|
||||
stamps = []
|
||||
real = c.cycle
|
||||
|
||||
async def counted():
|
||||
stamps.append(time.monotonic() - hass.t0)
|
||||
await real()
|
||||
|
||||
c.cycle = counted
|
||||
task = asyncio.create_task(c.run_control())
|
||||
await asyncio.sleep(seconds)
|
||||
c.stopping = True
|
||||
await asyncio.wait_for(task, timeout=10)
|
||||
return stamps, hass.writes
|
||||
return asyncio.run(go())
|
||||
|
||||
|
||||
def worst_gap(stamps, seconds):
|
||||
"""Longest stretch with no cycle, including the tail after the last one."""
|
||||
edges = [0.0] + list(stamps) + [seconds]
|
||||
return max(b - a for a, b in zip(edges, edges[1:]))
|
||||
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
print("a meter that repeats the same value")
|
||||
FLAT = lambda t: 350.0 # noqa: E731
|
||||
FLOOR, SECONDS = 3.0, 12.0
|
||||
|
||||
pre_stamps, pre_writes = drive(FLAT, NEVER, SECONDS)
|
||||
# The defect itself, demonstrated rather than described: one cycle at startup
|
||||
# and then nothing for the rest of the window, while writes keep happening.
|
||||
check("pre-fix: a constant meter runs exactly one cycle, at startup",
|
||||
len(pre_stamps) == 1)
|
||||
check("...while the heartbeat keeps writing anyway, so nothing looks wrong",
|
||||
len(pre_writes) >= 2)
|
||||
|
||||
post_stamps, post_writes = drive(FLAT, FLOOR, SECONDS)
|
||||
check("post-fix: the same constant meter runs cycles throughout",
|
||||
len(post_stamps) >= int(SECONDS / FLOOR) - 1)
|
||||
# The actual acceptance criterion: a BOUND on the gap, not a count.
|
||||
gap = worst_gap(post_stamps, SECONDS)
|
||||
check(f"...with no gap longer than the floor ({gap:.1f}s <= {FLOOR + 1.5:.1f}s)",
|
||||
gap <= FLOOR + 1.5)
|
||||
check("...and the loop actually corrected, instead of holding a stale command",
|
||||
len(post_writes) > len(pre_writes))
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
print("a meter that changes normally - nothing may move")
|
||||
# ⚠️ THE REGRESSION GUARD, and the more important half. The floor is a deadline
|
||||
# on the gap between cycles, reset by every cycle whichever trigger fired - not
|
||||
# a second scheduler. On a healthy meter it must never elapse, so the cycle
|
||||
# count, the write count and the commanded values must be IDENTICAL either side
|
||||
# of the fix. Anything else is a new write cadence, which SAFETY-12 forbids:
|
||||
# the deadband, step_w and the 10 s force-write decide what reaches the wire,
|
||||
# and this change is only allowed to alter when the loop thinks.
|
||||
STEPS = [0.0, 300.0, 850.0, -400.0, 120.0, -900.0, 60.0]
|
||||
LIVE = lambda t: STEPS[int(t // 2) % len(STEPS)] # noqa: E731
|
||||
|
||||
a_stamps, a_writes = drive(LIVE, NEVER, 12.0)
|
||||
b_stamps, b_writes = drive(LIVE, FLOOR, 12.0)
|
||||
check("a changing meter runs the same number of cycles as before the fix",
|
||||
len(a_stamps) == len(b_stamps))
|
||||
check("...commanding exactly the same sequence of values", a_writes == b_writes)
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
print("a meter parked at the target - the converged operating point")
|
||||
# The case TEL-05 warned about: at the converged target the power figure
|
||||
# legitimately repeats for minutes. The loop must still run, and must still
|
||||
# write nothing but the heartbeat, because the deadband - not the arrival
|
||||
# trigger - is what holds the command still.
|
||||
AT_TARGET = lambda t: -10.0 # noqa: E731
|
||||
c_stamps, c_writes = drive(AT_TARGET, NEVER, 12.0)
|
||||
d_stamps, d_writes = drive(AT_TARGET, FLOOR, 12.0)
|
||||
check("the loop evaluates at the converged point too", len(d_stamps) > len(c_stamps))
|
||||
check("...and the deadband still holds the command, so writes are unchanged",
|
||||
d_writes == c_writes)
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
print()
|
||||
if fails:
|
||||
print(f"{len(fails)} FAILED: " + "; ".join(fails))
|
||||
sys.exit(1)
|
||||
print("all checks passed")
|
||||