checks / unit (pull_request) Successful in 3m29s
SAFETY-24: an energy floor under the peak guard's forced discharge
SAFETY-07 can command a discharge to hold a billed quarter down, and
nothing below it consulted the state of charge. On the 2026-08-20 replay
it asks for 878 Wh in a day. Relying on the BMS is not absurd - it is a
real floor and it works - but it is the pack's protection rather than the
operator's, and a month of aggressive quarters leaves the battery
repeatedly at that cut-out with no EMS-side record of why. The first
symptom is a pack never available when wanted, which is indistinguishable
from the SoC drift MAINT-01 exists to correct.

decide() now takes soc and soc_floor, both required and neither
defaulted, and discharge_permitted() is the one place the question is
answered. Above the floor nothing changes. At or below it the guard files
a 0 W floor instead of a sized one - one-directional, so charging stays
blocked and no discharge is capped - and reports floor_limited with the
reason it bound. It is not a trip: every stop in 11.2's table still
outranks the claim, and the floor is never negative, so 9.1's asymmetry
survives as a property of the object (0 negative floors over 1296 swept
combinations, SoC included).

The SoC is graded only after `wanted > 0` is established, so it is never
evaluated where it governs nothing. An unreadable SoC is floor-limited,
not a full battery - a full battery is exactly the value that would
disarm the floor, and this project shipped that defaulting once already.

Failing to shave is not silent: one notification per episode
(goodwe_peak_soc_floor), distinct from the saturation alarm because the
two ask for opposite operator actions, plus its own status row and an
action-log line.

Verified by replay. The 2026-08-20 capture is driven against a modelled
pack sized from the day's own measured appetite, so it genuinely
exhausts: without the floor it reaches the BMS cut-out and holds there
for 1227 guard cycles; with it the pack stops at 20.0 % and never touches
the BMS. The energy withheld equals the energy between the two floors to
within one cycle at the rail. The honest half is reported too - the worst
quarter goes 4338 W -> 5030 W, because a floor-limited guard shaves less
on purpose.

Two new options, mirrored once in peakguard.PEAK_OPTION_DEFAULTS
(TARIFF-02's pattern), imported by validate.py and main.py rather than
typed as literals and pinned to config.yaml by a check that reads the
file - so CFG-03 still tracks three places. validate.py rule 8 refuses
peak_soc_floor <= bms_soc_floor at startup, in CFG-01/MAINT-04's manner.
maintenance_soc_floor is deliberately not reused and not renamed: it is a
drain target, not a spend limit, and the rename is recorded as a decision
to revisit if a third floor appears.

Eleven mutations of the shipped source were run against the checks; all
eleven go red and there are no survivors.