Files
goodwe-addon/goodwe_controller
glenn schrooyenandClaude 5b6cb0bf08 SAFETY-129: find readings 30 s late within about 90 s at a 5 s meter
The meter's delay fit needed 16 new values in 60 s, so at the owner's 5 s P1
only the batteries' fit ran and 30 s late was found after about 3 minutes
(export to -420 W). A meter that slow is now also fitted over 120 s; it calls
a delay late only over 16 s, on two fits in a row, with the same corroboration
as before, and never ends a verdict, so a slow battery (R2-1) runs as before.
Found about 90 s after the start, export above -200 W. 10 s late at a 5 s
meter is not found (nothing swings; it cannot be told from a 10 s battery).

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-06 19:38:21 +01:00
..
2026-11-02 17:52:41 +01:00