EV-19: no floor alarm when the batteries first reach the reserve early in a Manual car session
EV-15 rig F-B, reproduced on 43b0db7 (tools/ev19_reserve.py, T1 grid). At
the reserve inverter-b goes on following the house, so its output rises
in that cycle. The battery reading shows the rise one cycle before the P1
sample does, and EV-18's house figure (held - car + now - min(now, prev))
counted the new battery power as house load. `_car_need_house` latched:
one PEAK_GUARD_FLOOR_LIMITED ERROR and goodwe_peak_soc_floor at R+1, red
until the guard stopped wanting power.

ctl_car._car_explains_alarm: for the house latch only, a reading above
both earlier readings counts as house only up to the higher of them. The
credit stays the lower of the last two readings. The claim, floor,
setpoints and charger writes are unchanged (342 runs, same digests).

test_ev19.py: T1-T17, T20, N1-N6 of reports/EV-19-test-plan.md; 49
checks red on 43b0db7, 124 of 124 green here.