SAFETY-02: a loop can be fresh, tracking and inside its rating and still push the wrong way
The stale-input watchdog asks whether the meter is still talking. The saturation freeze asks whether the inverter can follow. The output clamp asks whether the number is too big. A loop can pass all three while charging the battery out of the grid, because the only thing wrong is the sign. On 2026-08-20 a commercial controller did exactly that four times in one day, for up to 77 minutes at a stretch, reaching a commanded -14 768 W against a ±5000 W inverter. app/watchdog.py compares the emitted setpoint against the authoritative P1 figure and, when they oppose each other with both over 300 W for 180 s continuously, files a failsafe SET claim at P_SAFETY, commands 0 W and latches there until an operator starts control again. Validated against that day rather than against an argument: sim/replay_sign.py in the infra repo drives this module over the committed captures of both 2026-08-20 and the healthy 2026-08-23 and reaches 18 trips on the fault day - every one inside a window NOTES.md §4.7 accounts for - and 0 on the healthy day. The four episodes do share one signature: 0.3 / 0.9 / 10.5 / 0.0 % sign agreement inside them against 92.9 % healthy. Three decisions the ticket could not make: - It is DISARMED whenever the grid-following loop is not what is driving. Sign agreement is a property of a loop that follows the meter, and a maintenance grid charge opposes the meter by design - 2500 W of charge into a house drawing 500 W is +3000 W on the meter against a -2500 W command, for hours. The gate tests the emitted number, not the winning claim's name, because a limit claim can let the loop "win" and still replace its value. - The trip LATCHES. Commanding 0 W removes the command side of the comparison, so the disagreement always clears the moment the trip works. - sign_disagree_w at or above max_w is refused at startup. The arbiter never lets a command exceed max_w, so such a threshold leaves the watchdog incapable of firing while the status page still reports it armed. What it does not catch, said out loud: an inverter that ACTS opposite to its command moves the meter further the same way, leaving command and meter in agreement. That is the saturation freeze's job. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
This commit is contained in:
co-authored by
Claude Opus 5
parent
35856a73ae
commit
9aed43990b
+11
-3
@@ -53,14 +53,22 @@ Run the checks before deploying. No framework needed:
|
||||
```bash
|
||||
cd goodwe_controller
|
||||
python3 test_control.py && python3 test_maintenance.py && python3 test_arbiter.py \
|
||||
&& python3 test_validate.py && python3 test_p1.py && python3 test_loop.py
|
||||
&& python3 test_validate.py && python3 test_p1.py && python3 test_watchdog.py \
|
||||
&& python3 test_loop.py
|
||||
```
|
||||
|
||||
`test_watchdog.py` covers SAFETY-02's logic and its trip path. Its headline
|
||||
validation is not here at all: `sim/replay_sign.py` in the infra repo drives the
|
||||
same module over the two captured RS485 days and must fire on all four of the
|
||||
2026-08-20 episodes and stay silent on 2026-08-23. That needs both checkouts —
|
||||
`GOODWE_ADDON_REPO=/path/to/goodwe-addon python3 sim/replay_sign.py`.
|
||||
|
||||
⚠️ `test_loop.py` takes about **95 seconds** (measured 93 s) and that is not a bug. It
|
||||
drives the real control loop, which sleeps 1 s a tick, eight times over, to prove a
|
||||
wall-clock property about it (SAFETY-12); mocking the clock there would leave the
|
||||
assertion testing the mock. The other five suites together are ~395 checks and finish in
|
||||
seconds. If you shorten `test_loop.py`'s windows, re-measure and correct this figure —
|
||||
assertion testing the mock. The other six suites together are ~440 checks and finish in
|
||||
seconds — `test_watchdog.py` spends ~3 s of that driving a real `Controller` through a
|
||||
trip. If you shorten `test_loop.py`'s windows, re-measure and correct this figure —
|
||||
an understated runtime is what makes a slow test look like a hung one, and a slow test
|
||||
that looks hung gets deleted.
|
||||
|
||||
|
||||
@@ -1,5 +1,58 @@
|
||||
# Changelog
|
||||
|
||||
## 0.5.0
|
||||
|
||||
**SAFETY-02 — the sign-disagreement watchdog.** The add-on now watches whether
|
||||
the setpoint it is emitting and the grid figure it is regulating on point the
|
||||
same way. If they oppose each other, both over `sign_disagree_w` (300 W), for
|
||||
`sign_disagree_s` (180 s) **continuously**, it files a failsafe claim at
|
||||
`P_SAFETY`, commands **0 W**, and latches there until an operator starts control
|
||||
again. New module `app/watchdog.py`; new options `sign_disagree_w` and
|
||||
`sign_disagree_s`.
|
||||
|
||||
This is the gap the existing failsafes leave open. The stale-input watchdog asks
|
||||
whether the meter is still talking, the saturation freeze asks whether the
|
||||
inverter can follow, the output clamp asks whether the number is too big — a
|
||||
loop can pass all three while charging the battery out of the grid, because the
|
||||
only thing wrong is the sign. On 2026-08-20 a commercial controller did exactly
|
||||
that four times in one day, for up to 77 minutes at a stretch, and reached a
|
||||
commanded −14 768 W against a ±5000 W inverter.
|
||||
|
||||
Validated against that day. `sim/replay_sign.py` in the infra repo drives this
|
||||
module over the committed RS485 captures of both 2026-08-20 (the four episodes)
|
||||
and 2026-08-23 (healthy): **18 trips on the fault day, every one inside a window
|
||||
`NOTES.md` §4.7 accounts for, and 0 on the healthy day.** The four episodes do
|
||||
share one signature rather than merely resembling each other — sign agreement
|
||||
runs 0.3 / 0.9 / 10.5 / 0.0 % inside them against 92.9 % on the healthy day.
|
||||
|
||||
Three decisions worth knowing about:
|
||||
|
||||
- **It is disarmed whenever the grid-following loop is not what is driving.**
|
||||
Sign agreement is a property of a loop that follows the meter. A maintenance
|
||||
grid charge opposes the meter *by design* — 2500 W of charge into a house
|
||||
drawing 500 W is +3000 W on the meter against a −2500 W command, for hours —
|
||||
and armed unconditionally this would trip on every maintenance cycle. The gate
|
||||
tests the emitted number, not the winning claim's name: a limit claim can let
|
||||
the loop "win" and still replace its value with one pointing the other way.
|
||||
- **The trip latches.** Commanding 0 W removes the command side of the
|
||||
comparison, so the disagreement always clears the moment the trip works.
|
||||
Un-latched, this would trip, clear, and hand the actuator back to the loop that
|
||||
was driving the wrong way, every three minutes forever.
|
||||
- **`sign_disagree_w` at or above `max_w` is refused at startup** (validator rule
|
||||
5). The arbiter never lets a command exceed `max_w`, so such a threshold makes
|
||||
the watchdog incapable of firing while the status page still reports it armed.
|
||||
A disarmed guard that advertises itself as armed is the failure mode this
|
||||
project keeps refusing to ship.
|
||||
|
||||
What it does **not** catch, stated so nobody assumes otherwise: an inverter that
|
||||
acts opposite to what it was told moves the meter *further* the same way, so
|
||||
command and meter agree while everything runs away. That is the saturation
|
||||
freeze's job, which compares the command against the battery's actual power.
|
||||
|
||||
`test_validate.py`'s "the smallest sane max_w still starts" case now names a
|
||||
reachable sign threshold, because a 1 W ceiling genuinely does disarm the 300 W
|
||||
default and is now correctly refused.
|
||||
|
||||
## 0.4.0
|
||||
|
||||
**CFG-01.** The add-on now refuses to start on a configuration it cannot honour,
|
||||
|
||||
@@ -24,6 +24,9 @@ The inverter **holds its last command forever** — it has no meter-timeout. So:
|
||||
commanding it.
|
||||
- This add-on commands 0 W when its inputs go missing, when you stop control,
|
||||
and when it shuts down.
|
||||
- This add-on commands 0 W **and latches there** if what it is commanding and
|
||||
what the meter reads point opposite ways for three minutes — see "The
|
||||
sign-disagreement failsafe" below.
|
||||
- The **optional RS485 e-stop** is the only thing that covers this machine
|
||||
dying. Without it, a failed host leaves the battery latched at its last
|
||||
command until someone intervenes.
|
||||
@@ -278,6 +281,54 @@ behind it would trip the firmware watchdog on a system that is working fine.
|
||||
| `cycle_floor_s` | 15 | The longest the loop may go without evaluating. A deadline on the gap between cycles, reset by every cycle — on a healthy meter it never elapses and changes nothing. Raise it only if your meter is slower than ~10 s; it must stay under `meter_max_age_s`, past which there is no reading to evaluate anyway |
|
||||
| `stale_input_s` | 15 | How long inputs may be missing before commanding 0 W. In P1 mode this clock starts only *after* `meter_max_age_s` has already expired — the two stack, see "How long a dead meter takes to reach 0 W" |
|
||||
| `auto_start` | false | Start controlling on boot (only after commissioning) |
|
||||
| `sign_disagree_w` | 300 | Both the command and the meter must exceed this before a sign difference counts. Must stay **below `max_w`** or the watchdog can never fire, and the add-on refuses to start |
|
||||
| `sign_disagree_s` | 180 | How long they must stay opposed, continuously, before the failsafe trips |
|
||||
|
||||
#### The sign-disagreement failsafe
|
||||
|
||||
If the setpoint this add-on is emitting and the grid figure it is regulating on
|
||||
point **opposite ways** — charging the battery while the house imports, or
|
||||
discharging it while the house exports — with both over `sign_disagree_w`, for
|
||||
`sign_disagree_s` **continuously**, the add-on commands **0 W** and holds it
|
||||
there. The banner reads `FAILSAFE`, the commissioning list says which two
|
||||
numbers disagreed and for how long, and the `Controller status` entity reports
|
||||
`failsafe`.
|
||||
|
||||
**It does not clear itself.** Pressing *Start / stop control* twice clears it.
|
||||
That is deliberate: commanding 0 W removes the command side of the comparison,
|
||||
so the disagreement always vanishes the instant the trip works, and a watchdog
|
||||
that took that as proof the fault was over would hand the inverter straight back
|
||||
to the loop that was driving the wrong way.
|
||||
|
||||
**What it is for.** This is a loop-integrity check: it asks whether the loop's
|
||||
output direction still matches the input state it was regulating. It catches a
|
||||
polarity error anywhere between the meter and the wire, and an integrator so far
|
||||
wound up that unwinding takes minutes. It is the check that would have caught all
|
||||
four episodes of 2026-08-20, when a commercial controller charged the battery out
|
||||
of the grid, four times, for up to 77 minutes at a time.
|
||||
|
||||
**What it is not for.** It does not detect an inverter that acts opposite to what
|
||||
it was told — that moves the meter *further* the same way, so command and meter
|
||||
agree while everything runs away. That is the saturation freeze's job
|
||||
(`saturation_w` / `saturation_cycles`), which compares the command against the
|
||||
battery's actual power. The two checks are complementary and neither replaces the
|
||||
other.
|
||||
|
||||
**Why it will not false-trip on ordinary operation.** A battery that refuses a
|
||||
command (empty, full, standby) leaves the meter where it was, so command and
|
||||
meter agree. A frozen meter drives the loop into agreeing with it. Around the
|
||||
resting point both signals are inside the 300 W gate, so the deadband can never
|
||||
produce one. A load step does flip the meter's sign before the loop catches up —
|
||||
measured on a full captured day, the longest such crossing is 30 s, against a
|
||||
180 s window. And the watchdog is **disarmed whenever the grid-following loop is
|
||||
not what is driving**: a maintenance grid charge opposes the meter by design and
|
||||
must not be mistaken for a fault.
|
||||
|
||||
Both numbers are measured rather than chosen, and are exposed only because the
|
||||
ticket requires defaults rather than constants. On the captured healthy day sign
|
||||
agreement is 92.9 %; on the four captured fault episodes it is 0.3 %, 0.9 %,
|
||||
10.5 % and 0.0 %. There is no reason to move either value without a capture that
|
||||
says so.
|
||||
|
||||
#### Saturation is counted in cycles, not seconds
|
||||
|
||||
|
||||
@@ -41,6 +41,7 @@ from .maintenance import IDLE, MaintConfig, Maintenance
|
||||
from .mqtt import MqttPublisher
|
||||
from .p1 import P1Ingest, build_source, is_enabled
|
||||
from .validate import ConfigRefused, refuse, validate_startup_config
|
||||
from .watchdog import SignWatchdog, SignWatchdogConfig
|
||||
from . import web
|
||||
|
||||
OPTIONS_PATH = "/data/options.json"
|
||||
@@ -103,6 +104,12 @@ class Controller:
|
||||
store,
|
||||
)
|
||||
|
||||
# SAFETY-02. One instance, one actuator, one cadence - see watchdog.py.
|
||||
self.sign_wd = SignWatchdog(SignWatchdogConfig(
|
||||
min_w=float(opts.get("sign_disagree_w", 300)),
|
||||
hold_s=float(opts.get("sign_disagree_s", 180)),
|
||||
))
|
||||
|
||||
# P1 ingestion (TEL-01). `meter_source: off` keeps the original
|
||||
# single-entity meter_entity path, so an existing install is unchanged
|
||||
# until it opts in.
|
||||
@@ -120,6 +127,11 @@ class Controller:
|
||||
self.sat_count = 0
|
||||
self.i_w = 0.0 # the loop's integrator, carried between cycles
|
||||
self.loop_w = None # what the loop asked for last cycle, or None
|
||||
# Did the grid-following loop actually win the LAST arbitration? That is
|
||||
# the question SAFETY-02 has to ask about the command standing on the
|
||||
# wire right now, so it is recorded when the arbitration happens rather
|
||||
# than re-derived a cycle later. Starts False: nothing is on the wire.
|
||||
self.following = False
|
||||
self.reason = "starting"
|
||||
self.grid = self.soc = self.batt = None
|
||||
self.peak_fc = None
|
||||
@@ -214,8 +226,29 @@ class Controller:
|
||||
for msg in result.events:
|
||||
self.log_event(msg)
|
||||
|
||||
# --- SAFETY-02, and it runs BEFORE the early return below -------------
|
||||
# ⚠️ ORDER MATTERS HERE. If this were evaluated after the "inputs missing
|
||||
# but not yet stale" hold, a run of held cycles would leave
|
||||
# `disagree_since` untouched across the gap and the timer would resume
|
||||
# from a start time that predates it. It is evaluated every cycle,
|
||||
# unconditionally, so a missing meter CLEARS the window - see watchdog.py.
|
||||
#
|
||||
# The value compared is the command STANDING ON THE WIRE, which is what
|
||||
# this cycle's fresh meter reading is a response to. `last_write` is that
|
||||
# value after the device clamp and confirmed accepted; `target` covers
|
||||
# the case where nothing has been written yet (and, deliberately, the
|
||||
# case where the last write was REJECTED - the inverter is then still
|
||||
# latched on `last_write`, which is exactly what `last_write` holds).
|
||||
was_tripped = self.sign_wd.tripped
|
||||
standing = self.last_write if self.last_write is not None else self.target
|
||||
if self.sign_wd.evaluate(standing, self.grid, self.following, now) \
|
||||
and not was_tripped:
|
||||
self.log_event("FAILSAFE " + self.sign_wd.reason)
|
||||
_LOG.error("SAFETY-02 TRIPPED - %s. Commanding 0 W and holding it "
|
||||
"until control is started again.", self.sign_wd.reason)
|
||||
|
||||
stale_after = float(self.o.get("stale_input_s", 15))
|
||||
if not self.inputs_ok:
|
||||
if not self.inputs_ok and not self.sign_wd.tripped:
|
||||
bad_for = (now - self.inputs_bad_since).total_seconds() if self.inputs_bad_since else 0.0
|
||||
if bad_for < stale_after:
|
||||
# A single missed poll is not a fault. Hold, keep the heartbeat
|
||||
@@ -235,6 +268,16 @@ class Controller:
|
||||
claims.append(Claim.limit("supervised", P_SAFETY, -max_w, max_w, "max_w"))
|
||||
|
||||
# --- safety stops ----------------------------------------------------
|
||||
# ⚠️ SAFETY-02 is claimed FIRST and unconditionally while latched. It is
|
||||
# a SET at P_SAFETY, so it outranks maintenance, peak shaving and the
|
||||
# loop alike - a controller pushing power the wrong way is wrong
|
||||
# whatever it thinks it is doing. Re-filed EVERY cycle: claims are not
|
||||
# sticky, and one filed once would lapse the next cycle and hand the
|
||||
# actuator silently back to the loop that was driving the wrong way.
|
||||
if self.sign_wd.tripped:
|
||||
claims.append(Claim.set("failsafe", P_SAFETY, 0.0,
|
||||
"sign disagreement"))
|
||||
|
||||
if not self.auto:
|
||||
claims.append(Claim.set("safety", P_SAFETY, 0.0, "stopped"))
|
||||
elif not self.inputs_ok:
|
||||
@@ -306,6 +349,28 @@ class Controller:
|
||||
resolution = resolve(claims)
|
||||
if resolution.contradiction:
|
||||
self.log_event("ARBITER CONTRADICTION - commanding 0 W, see the log")
|
||||
# --- SAFETY-02's arming gate ------------------------------------------
|
||||
# Was the number about to go on the wire chosen by the grid-following
|
||||
# loop, or by a strategy that commands against the meter on purpose?
|
||||
# Only the former is expected to agree in sign with P1. See gate 1 in
|
||||
# watchdog.py - without this, every maintenance grid charge trips the
|
||||
# failsafe within three minutes of starting.
|
||||
#
|
||||
# ⚠️ "THE LOOP WON" IS NOT ENOUGH, and the difference is a whole class of
|
||||
# false trip. A LIMIT claim can survive the loop winning and still
|
||||
# replace its number: maintenance's charge-only shaping is
|
||||
# `hi = -charge_w`, so the loop can ask for +500 W of discharge, win the
|
||||
# arbitration, and have the emitted value come out at -2500 W of grid
|
||||
# charge. Winner says "loop"; the wire carries maintenance's intent. So
|
||||
# the test is on the NUMBER, not on the name: the loop is following only
|
||||
# while the emitted value points the way the loop asked and is no larger
|
||||
# than it asked - i.e. limits reduced it, they did not redirect it.
|
||||
# Zero on either side falls out as not-following, which costs nothing:
|
||||
# a 0 W command cannot be a wrong-direction command.
|
||||
asked = self.loop_w
|
||||
self.following = (resolution.winner == "loop" and asked is not None
|
||||
and resolution.target_w * asked > 0
|
||||
and abs(resolution.target_w) <= abs(asked))
|
||||
self.target = resolution.target_w
|
||||
self.reason = resolution.explain()
|
||||
await self.write_setpoint(self.target)
|
||||
@@ -439,7 +504,14 @@ class Controller:
|
||||
"battery": self.batt,
|
||||
"soc": self.soc,
|
||||
"phase": self.maint.phase,
|
||||
"status": "running" if self.auto else "stopped",
|
||||
# ⚠️ SAFETY-02's alarm surface, and it is deliberately an existing
|
||||
# one. IF-01/IF-02 own `ems/event/failsafe` and the `failsafe active`
|
||||
# binary sensor and neither is built yet; inventing a bespoke topic
|
||||
# here would be a surface to migrate later. This sensor is already
|
||||
# discovered, already on every dashboard, and "failsafe" is
|
||||
# additive to its vocabulary rather than a change to it.
|
||||
"status": ("failsafe" if self.sign_wd.tripped
|
||||
else "running" if self.auto else "stopped"),
|
||||
}
|
||||
# ⚠️ ONLY when P1 ingestion is actually running. The ESP32's stale-input
|
||||
# watchdog subscribes to sensor.goodwe_p1_sample_age - see the entity-id
|
||||
@@ -521,6 +593,22 @@ class Controller:
|
||||
out.append({"ok": False, "warn": False,
|
||||
"text": "last write to the inverter was REJECTED - check the log"})
|
||||
|
||||
# SAFETY-02. Reported in both states: a watchdog nobody can see is armed
|
||||
# is a watchdog nobody trusts when it fires.
|
||||
if self.sign_wd.tripped:
|
||||
out.append({"ok": False, "warn": False,
|
||||
"text": "SIGN-DISAGREEMENT FAILSAFE - " + self.sign_wd.reason
|
||||
+ ". The inverter is held at 0 W. Find out why the "
|
||||
"command opposed the meter before starting control "
|
||||
"again; starting clears this."})
|
||||
else:
|
||||
held = self.sign_wd.held_s
|
||||
out.append({"ok": True, "warn": False,
|
||||
"text": f"sign watchdog: armed (trips after "
|
||||
f"{self.sign_wd.cfg.hold_s:.0f} s opposed, both over "
|
||||
f"{self.sign_wd.cfg.min_w:.0f} W)"
|
||||
+ (f" - opposed for {held:.0f} s now" if held else "")})
|
||||
|
||||
if not o.get("estop_fitted", False):
|
||||
out.append({"ok": False, "warn": True,
|
||||
"text": "no e-stop fitted: if this host dies the battery stays "
|
||||
@@ -538,7 +626,11 @@ class Controller:
|
||||
def status_payload(self) -> dict:
|
||||
checks = self.checks()
|
||||
bad = [c for c in checks if not c["ok"] and not c["warn"]]
|
||||
if bad:
|
||||
if self.sign_wd.tripped:
|
||||
# Outranks "NOT READY": nothing is missing, something went wrong.
|
||||
level, banner = "bad", ("FAILSAFE — the command opposed the meter. "
|
||||
"Inverter held at 0 W.")
|
||||
elif bad:
|
||||
level, banner = "bad", f"NOT READY — {bad[0]['text']}"
|
||||
elif not self.auto:
|
||||
level, banner = "warn", "Stopped — inverter commanded to 0 W"
|
||||
@@ -572,6 +664,15 @@ class Controller:
|
||||
self.auto = not self.auto
|
||||
self.store.set("auto", self.auto)
|
||||
self.log_event("control started" if self.auto else "control stopped")
|
||||
if self.auto and self.sign_wd.tripped:
|
||||
# ⚠️ THE ONLY WAY OUT OF A SIGN-DISAGREEMENT TRIP, on purpose.
|
||||
# It clears on a deliberate human start, not on the condition
|
||||
# going away - the condition ALWAYS goes away, because the trip
|
||||
# commands 0 W and a 0 W command cannot disagree with anything.
|
||||
# An operator pressing start has, at minimum, looked at the
|
||||
# banner that says why.
|
||||
self.sign_wd.reset()
|
||||
self.log_event("sign-disagreement failsafe cleared by operator")
|
||||
if not self.auto:
|
||||
self.target = 0.0
|
||||
await self.write_setpoint(0.0, force=True)
|
||||
|
||||
@@ -74,6 +74,17 @@ NOT READY banner already names the problem, (b) does not apply.
|
||||
was overruled. That firmware file's own comment says a lower bound on this
|
||||
"belongs in CFG-01, not here" - so here it is.
|
||||
|
||||
5. `sign_disagree_w` at or above `max_w`. [(a)]
|
||||
The arbiter's `supervised` limit bounds every command to +-max_w, and
|
||||
SAFETY-02's predicate needs `abs(command) > sign_disagree_w`. Set the
|
||||
threshold at or above the ceiling and the command side of the comparison
|
||||
is unsatisfiable BY CONSTRUCTION: the watchdog can never fire, on any
|
||||
input, ever. Same shape as 1 and 4 - the operator set a number, a layer
|
||||
they cannot see makes it mean something else, and nothing says so. Worse
|
||||
here, because what the status page reports in that state is "sign
|
||||
watchdog: armed". A disarmed guard that advertises itself as armed is the
|
||||
one thing this project has decided repeatedly it will not ship.
|
||||
|
||||
WHAT IS DELIBERATELY *NOT* REFUSED, because it is untidy rather than unsafe:
|
||||
|
||||
- `integrator_max_w` above `max_w`. DOCS.md is right that the only thing the
|
||||
@@ -238,6 +249,26 @@ def validate_startup_config(opts: dict, dev_min=None, dev_max=None) -> list[str]
|
||||
"or rebuild the firmware with a matching max_age_s and update "
|
||||
"validate.FIRMWARE_INGEST_VETO_S.")
|
||||
|
||||
# --- 5. a sign watchdog that can actually fire ---------------------------
|
||||
# ⚠️ Strictly `>=`, matching the predicate exactly: watchdog.py tests
|
||||
# `abs(commanded_w) > min_w`, and the arbiter holds `abs(commanded_w)` at or
|
||||
# below max_w, so threshold == max_w is already unsatisfiable. Anything
|
||||
# BELOW max_w is reachable and therefore fine - this refuses the disarmed
|
||||
# case only, not "close to the rail".
|
||||
sign_w = _number(opts, "sign_disagree_w", 300.0)
|
||||
if sign_w is None:
|
||||
problems.append(f"sign_disagree_w {opts.get('sign_disagree_w')!r} is not a number")
|
||||
elif max_w is not None and max_w > 0 and sign_w >= max_w:
|
||||
problems.append(
|
||||
f"sign_disagree_w is {sign_w:.0f} W but max_w is {max_w:.0f} W, so "
|
||||
"the SAFETY-02 sign-disagreement watchdog can never fire: the "
|
||||
"arbiter never lets a command exceed max_w, and the watchdog needs "
|
||||
f"a command over {sign_w:.0f} W. It would sit there reporting "
|
||||
"'armed' on the status page while being incapable of tripping - the "
|
||||
f"one runaway failure mode this system has actually observed. Lower "
|
||||
f"sign_disagree_w below {max_w:.0f} W (300 W is the measured "
|
||||
"default), or raise max_w.")
|
||||
|
||||
# --- warnings: real, but not worth refusing over -------------------------
|
||||
integ = opts.get("integrator_max_w")
|
||||
integ_w = None if not integ else _number(opts, "integrator_max_w", None)
|
||||
|
||||
@@ -0,0 +1,220 @@
|
||||
"""SAFETY-02 - the sign-disagreement watchdog.
|
||||
|
||||
WHAT IT CATCHES, in one sentence: a grid-following loop that is pushing power in
|
||||
the wrong direction, which every other guard in this system is blind to.
|
||||
|
||||
The stale-input watchdog (SAFETY-01) asks "is the meter still talking?". The
|
||||
saturation freeze asks "can the inverter follow?". The output clamp asks "is the
|
||||
number too big?". A loop can pass all three and still be charging the battery
|
||||
out of the grid while the house imports - the meter is fresh, the inverter is
|
||||
tracking beautifully, and the magnitude is inside the rating. The only thing
|
||||
that separates that from healthy operation is the SIGN.
|
||||
|
||||
⚠️ THIS IS NOT A HYPOTHETICAL. On 2026-08-20 the vendor controller (Illusmart)
|
||||
did exactly this four times in one day (NOTES.md §4.7). Both captures of that
|
||||
bus are committed - `sim/scenarios/bus-2026-08-20.log.gz` and the healthy
|
||||
`bus-2026-08-23.log.gz` in the infra repo - and `sim/replay_sign.py` drives this
|
||||
module over both of them. Every number in this file was measured on those two
|
||||
days, not chosen:
|
||||
|
||||
day samples gated in sign agreement
|
||||
2026-08-23 4 127 / 16 349 92.9 % (healthy)
|
||||
2026-08-20 6 892 / 15 598 55.6 % (the whole fault day)
|
||||
episode A 15:26-16:43 0.3 %
|
||||
episode B 17:11-18:28 0.8 %
|
||||
episode C 20:01-20:31 11.0 %
|
||||
episode D 20:55-21:11 0.0 %
|
||||
|
||||
That is the signature, and it is the SAME signature in all four episodes: not a
|
||||
noisier version of healthy, a near-total inversion.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
WHY IT LIVES HERE AND NOT IN THE FIRMWARE OR THE WITNESS
|
||||
|
||||
Three vantage points see three different things. The firmware knows what it
|
||||
WROTE, the witness Pi knows what was ON THE WIRE and whether the inverter ACKed
|
||||
it, and the add-on knows what it INTENDED and holds the authoritative meter.
|
||||
|
||||
This check is not command-versus-wire; it is command-versus-physics. It needs
|
||||
the emitted setpoint and the P1 net figure in the same place, and it needs the
|
||||
authority to command zero when they fight:
|
||||
|
||||
- the witness is read-only by charter and cannot command anything, so it could
|
||||
raise the alarm but never take the trip action the AC requires;
|
||||
- the firmware has the wire but not the meter. §5.1 makes P1 the only
|
||||
authoritative grid figure and the board only ever receives its AGE
|
||||
(`sensor.goodwe_p1_sample_age`), never its value. Putting the check there
|
||||
would mean shipping the meter to the ESP32 for no other reason, and it would
|
||||
be C++ per install rather than one generic guard;
|
||||
- the add-on has both halves already, plus an arbiter that can outrank every
|
||||
strategy with a P_SAFETY claim.
|
||||
|
||||
The cost of standing here is real and worth stating: this watchdog compares what
|
||||
we MEANT to put on the wire against the meter. If the firmware or the driver
|
||||
inverts the sign on the way out, the add-on's own view still agrees with itself
|
||||
and this check stays silent. That gap is a wire-versus-intent problem and it
|
||||
belongs to the witness, not here.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
WHAT "DISAGREEMENT" MEANS, PRECISELY
|
||||
|
||||
disagree = following
|
||||
and commanded_w * grid_w < 0
|
||||
and abs(commanded_w) > min_w
|
||||
and abs(grid_w) > min_w
|
||||
|
||||
Four gates, and each one exists to exclude a specific thing that is NOT a fault:
|
||||
|
||||
1. `following`. ⚠️ THE GATE THAT IS EASIEST TO FORGET AND MOST EXPENSIVE TO
|
||||
OMIT. Sign agreement is a property of a GRID-FOLLOWING loop. It is not
|
||||
expected of a strategy that deliberately commands against the meter -
|
||||
maintenance is exactly that. A maintenance grid charge of 2500 W into a house
|
||||
drawing 500 W puts +3000 W on the meter against a -2500 W command: opposed,
|
||||
both far over any sane threshold, and sustained for HOURS. Armed
|
||||
unconditionally this watchdog would trip on every single maintenance cycle,
|
||||
which is not a tuning problem, it is the wrong question being asked. So the
|
||||
caller says whether the grid-following loop actually won the arbitration this
|
||||
cycle, and the timer only accumulates when it did.
|
||||
|
||||
2. The strict `< 0` product. "Opposed" and "neither side is zero" in one
|
||||
expression.
|
||||
|
||||
3. The 300 W magnitude gate ON BOTH SIDES. Near zero the sign is noise, and near
|
||||
zero is where a healthy loop LIVES - the deadband holds the command still
|
||||
while the meter wanders either side of `target_grid_w`. On the healthy day
|
||||
only 4 127 of 16 349 samples (25 %) are even gated in; the other 75 % are the
|
||||
converged band where sign carries no information. This is also why the
|
||||
deadband cannot produce a false trip: inside it the meter is by definition
|
||||
under 300 W.
|
||||
|
||||
4. The 180 s continuity requirement. This is what excludes the legitimate
|
||||
transient. A load step reverses the meter's sign instantly while the command
|
||||
is still where the last cycle left it; slew limiting then needs a few cycles
|
||||
to cross over. Measured on the healthy day, the LONGEST such crossing is 30 s
|
||||
- and that is with a vendor controller far cruder than ours. 180 s is six
|
||||
times that. It is not a fitted threshold: at 60 s the healthy day still
|
||||
produces zero trips, and at 300 s the fault day still produces 13.
|
||||
|
||||
⚠️ A BATTERY THAT REFUSES A COMMAND CANNOT TRIP THIS, and that is structural
|
||||
rather than lucky. At SoC 10 % in Standby, a 1350 W discharge command into a
|
||||
1350 W import is DECLINED: the battery does nothing, so the meter stays at
|
||||
+1350 W and the command stays at +1350 W. Same sign. Agreement. A refusal leaves
|
||||
the meter where it was; only the inverter ACTING moves it, and acting in the
|
||||
commanded direction moves it toward zero, not through it. The failure mode this
|
||||
check keys on is the opposite of a refusal - it is the inverter obediently doing
|
||||
a wrong thing.
|
||||
|
||||
⚠️ A FROZEN METER cannot trip it either, for the same reason read the other way:
|
||||
a stuck reading of +800 W makes the loop command discharge and keep commanding
|
||||
discharge. Command and meter converge on AGREEING. Freezes are SAFETY-12's and
|
||||
SAFETY-01's problem, and this watchdog neither helps nor hinders there.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
STATE, TRIP AND LATCH
|
||||
|
||||
One timestamp, not a sample counter. The cycle rate is not fixed - a meter
|
||||
arrival, or `cycle_floor_s` elapsing, whichever comes first - so N samples is a
|
||||
different wall-clock window on every path, and the AC is written in minutes.
|
||||
|
||||
The latch is not optional and not a nicety. Commanding 0 W removes the command
|
||||
side of the comparison (|0| is not > 300), so the disagreement disappears the
|
||||
instant the trip works. Un-latched, this watchdog would trip, clear itself, and
|
||||
hand the actuator straight back to the loop that was driving the wrong way -
|
||||
three minutes later, forever. `tripped` therefore stays true until an operator
|
||||
`reset()`s it by starting control again, which is a deliberate human act after
|
||||
looking at why.
|
||||
"""
|
||||
|
||||
from dataclasses import dataclass
|
||||
from datetime import datetime
|
||||
|
||||
|
||||
@dataclass(frozen=True)
|
||||
class SignWatchdogConfig:
|
||||
"""Defaults, not constants - config.yaml carries both (SAFETY-02 AC 5)."""
|
||||
|
||||
min_w: float = 300.0
|
||||
hold_s: float = 180.0
|
||||
|
||||
|
||||
class SignWatchdog:
|
||||
"""One instance per actuator, evaluated once per control cycle.
|
||||
|
||||
⚠️ NOT SHARED ACROSS CADENCES. `disagree_since` is a wall-clock start time,
|
||||
so driving one instance from two loops at two rates would have each one
|
||||
resetting the other's window. If a fast on-device path ever wants this
|
||||
check, it gets its own instance - the same exactly-one-writer discipline the
|
||||
arbiter applies to the actuator, applied to the detector's own state.
|
||||
"""
|
||||
|
||||
def __init__(self, cfg: SignWatchdogConfig | None = None):
|
||||
self.cfg = cfg or SignWatchdogConfig()
|
||||
self.disagree_since: datetime | None = None
|
||||
self.tripped = False
|
||||
self.reason = ""
|
||||
|
||||
# -- the whole check, and it is a pure function of its arguments ----------
|
||||
def evaluate(self, commanded_w, grid_w, following: bool,
|
||||
now: datetime) -> bool:
|
||||
"""Advance the detector one cycle. Returns True while tripped.
|
||||
|
||||
`commanded_w` the EMITTED setpoint - what is standing on the wire now,
|
||||
after deadband, slew, quantisation and the arbiter. Not
|
||||
the optimizer's raw wish: the wire carries the emitted
|
||||
value, so anything else can disagree with the meter for a
|
||||
reason that is not a fault.
|
||||
`grid_w` net P1, + = importing. None when the meter is stale or
|
||||
missing, which CLEARS the timer rather than accumulating
|
||||
- a frozen figure held against a moving command would
|
||||
otherwise manufacture a disagreement in about three
|
||||
minutes, on top of SAFETY-01 having already commanded
|
||||
zero for the same cause.
|
||||
`following` did the grid-following loop actually win this cycle? See
|
||||
gate 1 in the module docstring.
|
||||
`now` the caller's clock, so this stays testable and replayable.
|
||||
"""
|
||||
if self.tripped:
|
||||
# Latched. Do not re-evaluate: the trip removed the evidence.
|
||||
return True
|
||||
|
||||
cfg = self.cfg
|
||||
disagree = (
|
||||
following
|
||||
and commanded_w is not None and grid_w is not None
|
||||
and commanded_w * grid_w < 0
|
||||
and abs(commanded_w) > cfg.min_w
|
||||
and abs(grid_w) > cfg.min_w
|
||||
)
|
||||
|
||||
if not disagree:
|
||||
self.disagree_since = None
|
||||
return False
|
||||
|
||||
if self.disagree_since is None:
|
||||
self.disagree_since = now
|
||||
return False
|
||||
|
||||
held = (now - self.disagree_since).total_seconds()
|
||||
if held < cfg.hold_s:
|
||||
return False
|
||||
|
||||
self.tripped = True
|
||||
self.reason = (
|
||||
f"SIGN_DISAGREEMENT: commanded {commanded_w:+.0f} W against a meter "
|
||||
f"reading {grid_w:+.0f} W for {held:.0f} s continuously "
|
||||
f"(limits: both over {cfg.min_w:.0f} W, held over {cfg.hold_s:.0f} s)"
|
||||
)
|
||||
return True
|
||||
|
||||
@property
|
||||
def held_s(self) -> float:
|
||||
"""How long the current disagreement has been standing, for the UI."""
|
||||
if self.disagree_since is None:
|
||||
return 0.0
|
||||
return (datetime.now(self.disagree_since.tzinfo)
|
||||
- self.disagree_since).total_seconds()
|
||||
|
||||
def reset(self) -> None:
|
||||
self.disagree_since = None
|
||||
self.tripped = False
|
||||
self.reason = ""
|
||||
@@ -1,5 +1,5 @@
|
||||
name: GoodWe RS485 Controller
|
||||
version: "0.4.0"
|
||||
version: "0.5.0"
|
||||
slug: goodwe_controller
|
||||
description: >-
|
||||
Drives a GoodWe ES/BP battery inverter over RS485 by emulating its smart
|
||||
@@ -93,6 +93,27 @@ options:
|
||||
cycle_floor_s: 15
|
||||
auto_start: false
|
||||
|
||||
# --- SAFETY-02 sign-disagreement watchdog ----------------------------------
|
||||
# Trips when the emitted setpoint and the P1 net figure point OPPOSITE ways,
|
||||
# both over sign_disagree_w, continuously for sign_disagree_s. Action: 0 W and
|
||||
# a failsafe that latches until an operator starts control again.
|
||||
#
|
||||
# Both defaults are measured, not chosen. On the captured healthy day
|
||||
# (2026-08-23) the longest legitimate opposed run - a load step the loop has
|
||||
# not caught up with - is 30 s, and sign agreement over the gated samples is
|
||||
# 92.9 %. On the captured fault day (2026-08-20) the four episodes run 0.0-11 %
|
||||
# agreement with opposed runs up to 1752 s. 300 W / 180 s sits in the middle of
|
||||
# a very wide gap: at 60 s the healthy day still trips nothing, at 300 s the
|
||||
# fault day still trips 13 times. There is no reason to move either number
|
||||
# without a capture that says so. They are options because the AC says
|
||||
# thresholds are defaults rather than constants - not because they are knobs
|
||||
# anyone is expected to turn.
|
||||
#
|
||||
# ⚠️ sign_disagree_w must stay BELOW max_w or the watchdog can never fire (the
|
||||
# arbiter bounds the command to +-max_w). validate.py refuses that config.
|
||||
sign_disagree_w: 300
|
||||
sign_disagree_s: 180
|
||||
|
||||
# --- maintenance -----------------------------------------------------------
|
||||
maintenance_enabled: false
|
||||
maintenance_interval_days: 28
|
||||
@@ -155,6 +176,11 @@ schema:
|
||||
cycle_floor_s: int(5,60)
|
||||
auto_start: bool
|
||||
|
||||
# No "off" value, deliberately: this is a P0 safety check and the schema is
|
||||
# not the place to make disarming it a supported configuration.
|
||||
sign_disagree_w: int(50,5000)
|
||||
sign_disagree_s: int(30,1800)
|
||||
|
||||
maintenance_enabled: bool
|
||||
maintenance_interval_days: int(1,90)
|
||||
maintenance_start_hour: int(0,23)
|
||||
|
||||
@@ -160,8 +160,17 @@ for bad in (0, -1, -2000):
|
||||
check(f"max_w {bad} is refused", len(p) == 1 and why(p, "must be positive"))
|
||||
check("...and the message explains it would read as a trip, not a mistake",
|
||||
why(validate_startup_config(base(max_w=0), -5000, 5000), "contradiction"))
|
||||
# ⚠️ SAFETY-02 changed what this case has to say, and the change is real rather
|
||||
# than bookkeeping: with a 1 W ceiling the default 300 W sign-disagreement
|
||||
# threshold is unreachable, so rule 5 refuses - correctly, because the watchdog
|
||||
# would report itself armed while being incapable of firing. What this check is
|
||||
# FOR is "a positive max_w is not itself a refusal", so it now names a sign
|
||||
# threshold the ceiling can actually reach, and the interaction gets its own
|
||||
# check below.
|
||||
check("the smallest sane max_w still starts",
|
||||
validate_startup_config(base(max_w=1), -5000, 5000) == [])
|
||||
validate_startup_config(base(max_w=1, sign_disagree_w=0.5), -5000, 5000) == [])
|
||||
check("...but that same 1 W ceiling with the DEFAULT sign threshold is refused",
|
||||
why(validate_startup_config(base(max_w=1), -5000, 5000), "never fire"))
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
print("what must NOT be refused - a validator that fires on trivia gets deleted")
|
||||
|
||||
@@ -0,0 +1,248 @@
|
||||
"""Runnable check for the sign-disagreement watchdog. `python3 test_watchdog.py`
|
||||
|
||||
Every case here is either a fault this must catch or a piece of NORMAL behaviour
|
||||
it must not mistake for one. The second list is the longer one on purpose: an
|
||||
alarm that fires on ordinary operation is worse than no alarm, because the next
|
||||
person switches it off.
|
||||
|
||||
The headline validation is not here - it is `sim/replay_sign.py` in the infra
|
||||
repo, which drives this module over the two captured bus days. This file is the
|
||||
table-driven half: boundaries, timers, the latch, and the arming gate.
|
||||
"""
|
||||
|
||||
import sys
|
||||
from datetime import datetime, timedelta, timezone
|
||||
|
||||
from app.watchdog import SignWatchdog, SignWatchdogConfig
|
||||
|
||||
fails = []
|
||||
T0 = datetime(2026, 8, 20, 15, 0, 0, tzinfo=timezone.utc)
|
||||
|
||||
|
||||
def check(name, cond):
|
||||
print(f" {'ok ' if cond else 'FAIL'} {name}")
|
||||
if not cond:
|
||||
fails.append(name)
|
||||
|
||||
|
||||
def drive(samples, cfg=None, following=True):
|
||||
"""Feed (offset_s, commanded_w, grid_w) tuples. Returns (wd, trip_offset)."""
|
||||
wd = SignWatchdog(cfg)
|
||||
trip_at = None
|
||||
for item in samples:
|
||||
offset, cmd, grid = item[0], item[1], item[2]
|
||||
f = item[3] if len(item) > 3 else following
|
||||
if wd.evaluate(cmd, grid, f, T0 + timedelta(seconds=offset)) and trip_at is None:
|
||||
trip_at = offset
|
||||
return wd, trip_at
|
||||
|
||||
|
||||
def opposed(duration_s, step=5, cmd=-1000, grid=1500, following=True, start=0):
|
||||
return [(start + t, cmd, grid, following)
|
||||
for t in range(0, int(duration_s) + 1, step)]
|
||||
|
||||
|
||||
print("the fault it exists to catch")
|
||||
wd, at = drive(opposed(300))
|
||||
check("charging into an importing house trips", wd.tripped)
|
||||
check("and trips at 180 s, not before", at == 180)
|
||||
check("the reason names both signals", "-1000" in wd.reason and "+1500" in wd.reason)
|
||||
print(f" e.g. {wd.reason!r}")
|
||||
|
||||
wd, at = drive(opposed(300, cmd=2000, grid=-2000))
|
||||
check("discharging into an exporting house trips too", wd.tripped and at == 180)
|
||||
|
||||
print()
|
||||
print("the boundaries")
|
||||
wd, _ = drive(opposed(600, cmd=-300, grid=1500))
|
||||
check("300 W exactly does NOT qualify (strictly greater)", not wd.tripped)
|
||||
wd, _ = drive(opposed(600, cmd=-301, grid=1500))
|
||||
check("301 W does", wd.tripped)
|
||||
wd, _ = drive(opposed(600, cmd=-1000, grid=300))
|
||||
check("a 300 W meter does not qualify either", not wd.tripped)
|
||||
wd, _ = drive(opposed(175))
|
||||
check("175 s of disagreement does not trip", not wd.tripped)
|
||||
wd, _ = drive(opposed(180))
|
||||
check("180 s does (>= hold_s)", wd.tripped)
|
||||
|
||||
print()
|
||||
print("continuity - the rule that produced zero false positives on real data")
|
||||
broken = opposed(175) + [(180, -1000, -1500)] + opposed(175, start=185)
|
||||
wd, _ = drive(broken)
|
||||
check("179 s, one agreeing sample, then 175 s more: no trip", not wd.tripped)
|
||||
check("and the window really was reset", wd.disagree_since is not None)
|
||||
long_enough = broken + opposed(200, start=365)
|
||||
wd, _ = drive(long_enough)
|
||||
check("but a full 180 s after the reset does trip", wd.tripped)
|
||||
|
||||
print()
|
||||
print("things that are NOT faults")
|
||||
# The load-step transient. Measured on the healthy capture: longest 30 s.
|
||||
wd, _ = drive(opposed(30) + [(35 + t, 800, 900) for t in range(0, 300, 5)])
|
||||
check("a 30 s load-step crossover does not trip", not wd.tripped)
|
||||
|
||||
# SoC 10 %, Standby, declining a 1350 W discharge. The battery does nothing, so
|
||||
# the meter stays where it was and the command agrees with it.
|
||||
wd, _ = drive([(t, 1350, 1350) for t in range(0, 900, 5)])
|
||||
check("a battery refusing a discharge command cannot trip it", not wd.tripped)
|
||||
|
||||
# A frozen meter drives command and reading into agreement, not disagreement.
|
||||
wd, _ = drive([(t, 800, 800) for t in range(0, 900, 5)])
|
||||
check("a frozen meter cannot trip it", not wd.tripped)
|
||||
|
||||
# Maintenance grid charge: 2500 W of charge against an importing house, for
|
||||
# hours. Opposed, both huge - and entirely correct.
|
||||
wd, _ = drive(opposed(7200, cmd=-2500, grid=3000, following=False))
|
||||
check("two hours of maintenance grid charge does not trip", not wd.tripped)
|
||||
check("and the timer never even started", wd.disagree_since is None)
|
||||
|
||||
wd, _ = drive([(t, -1000, None) for t in range(0, 900, 5)])
|
||||
check("a missing meter reading does not trip", not wd.tripped)
|
||||
wd, _ = drive(opposed(175) + [(180, -1000, None)] + opposed(600, start=185))
|
||||
check("a missing reading mid-window RESETS it rather than accumulating",
|
||||
wd.tripped and wd.disagree_since is not None)
|
||||
wd, at = drive(opposed(175) + [(180, -1000, None)] + opposed(600, start=185))
|
||||
check("...so the trip lands 180 s after the gap, not after 180 s total",
|
||||
at == 365)
|
||||
|
||||
wd, _ = drive([(t, 0.0, 3000) for t in range(0, 900, 5)])
|
||||
check("a 0 W command is not a wrong-direction command", not wd.tripped)
|
||||
|
||||
print()
|
||||
print("the latch")
|
||||
wd, _ = drive(opposed(200))
|
||||
check("tripped after the fault", wd.tripped)
|
||||
# The trip commands 0 W, which removes the command side of the comparison.
|
||||
for t in range(200, 900, 5):
|
||||
wd.evaluate(0.0, 3000, True, T0 + timedelta(seconds=t))
|
||||
check("stays tripped once the command is zeroed", wd.tripped)
|
||||
for t in range(900, 1500, 5):
|
||||
wd.evaluate(1000, 1000, True, T0 + timedelta(seconds=t))
|
||||
check("stays tripped even once everything looks healthy again", wd.tripped)
|
||||
wd.reset()
|
||||
check("reset() is the only way out", not wd.tripped and wd.disagree_since is None)
|
||||
check("and the reason is cleared with it", wd.reason == "")
|
||||
|
||||
print()
|
||||
print("the thresholds are configuration, not constants")
|
||||
cfg = SignWatchdogConfig(min_w=800.0, hold_s=60.0)
|
||||
wd, at = drive(opposed(300, cmd=-1000, grid=1500), cfg=cfg)
|
||||
check("a 60 s hold trips at 60 s", wd.tripped and at == 60)
|
||||
wd, _ = drive(opposed(600, cmd=-700, grid=1500), cfg=cfg)
|
||||
check("an 800 W gate ignores a 700 W command", not wd.tripped)
|
||||
|
||||
print()
|
||||
print("the configuration that would disarm it is refused")
|
||||
from app.validate import validate_startup_config # noqa: E402
|
||||
|
||||
base = {"setpoint_entity": "number.sp", "meter_source": "off",
|
||||
"meter_phases": 1, "meter_max_age_s": 30}
|
||||
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 300},
|
||||
-5000, 5000)
|
||||
check("300 W under a 2000 W ceiling is accepted", p == [])
|
||||
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 2000},
|
||||
-5000, 5000)
|
||||
check("a threshold AT max_w is refused", len(p) == 1 and "never fire" in p[0])
|
||||
p = validate_startup_config({**base, "max_w": 500, "sign_disagree_w": 3000},
|
||||
-5000, 5000)
|
||||
check("a threshold above max_w is refused", len(p) == 1 and "never fire" in p[0])
|
||||
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 1999},
|
||||
-5000, 5000)
|
||||
check("one watt under the ceiling is reachable, so accepted", p == [])
|
||||
|
||||
print()
|
||||
print("end to end: the trip is COMMAND ZERO, not alarm-only")
|
||||
# ⚠️ THE FAULT INJECTED HERE IS A NEGATIVE GAIN, and that is not a contrivance -
|
||||
# it is the minimal faithful model of what this watchdog is for. The check
|
||||
# compares the loop's OUTPUT DIRECTION against the INPUT STATE it was regulating,
|
||||
# so what it detects is a loop whose two ends have become decoupled in sign: a
|
||||
# gain, a claim or a strategy with its polarity inverted, or an integrator so far
|
||||
# wound up that unwinding takes minutes. (Illusmart's was the last one: it
|
||||
# reached -14 768 W against a +-5000 W rail while writing once every 20-60 s, and
|
||||
# that arithmetic alone is 5-15 minutes of wrong-direction command.)
|
||||
#
|
||||
# `gain` is float(0.05,1.0) in the schema, so this is not a reachable
|
||||
# configuration - it is a stand-in for a code regression, which is the case a
|
||||
# unit test can actually hold the line on.
|
||||
import asyncio # noqa: E402
|
||||
|
||||
from app.main import Controller # noqa: E402
|
||||
|
||||
|
||||
class _Hass:
|
||||
def __init__(self):
|
||||
self.writes = []
|
||||
|
||||
async def limits(self, entity):
|
||||
return (-5000.0, 5000.0, 1.0)
|
||||
|
||||
async def number(self, entity, invert=False):
|
||||
# A house importing 2000 W, steadily, whatever the battery does.
|
||||
return {"sensor.grid": 2000.0, "sensor.soc": 50.0,
|
||||
"sensor.batt": 0.0}.get(entity)
|
||||
|
||||
async def set_number(self, entity, value):
|
||||
self.writes.append(float(value))
|
||||
return True
|
||||
|
||||
|
||||
class _S:
|
||||
data = {}
|
||||
|
||||
def set(self, *a):
|
||||
pass
|
||||
|
||||
def get_time(self, *a):
|
||||
return None
|
||||
|
||||
|
||||
class _P:
|
||||
enabled = False
|
||||
|
||||
def publish(self, *a, **k):
|
||||
pass
|
||||
|
||||
def close(self):
|
||||
pass
|
||||
|
||||
|
||||
async def _e2e():
|
||||
hass = _Hass()
|
||||
opts = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
|
||||
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
|
||||
"meter_source": "off", "max_w": 2000, "gain": -0.6,
|
||||
"sign_disagree_w": 300, "sign_disagree_s": 1, "auto_start": True}
|
||||
c = Controller(opts, hass, _S(), _P(), stop=asyncio.Event())
|
||||
c.auto = True
|
||||
c.dev_min, c.dev_max = -5000.0, 5000.0
|
||||
seen_wrong_way = False
|
||||
for _ in range(12):
|
||||
await c.read_inputs()
|
||||
await c.cycle()
|
||||
if c.target < -300 and not c.sign_wd.tripped:
|
||||
seen_wrong_way = True
|
||||
await asyncio.sleep(0.25)
|
||||
return c, hass, seen_wrong_way
|
||||
|
||||
|
||||
ctrl, hass, wrong_way = asyncio.run(_e2e())
|
||||
check("the broken loop really did command charge into an import first", wrong_way)
|
||||
check("the watchdog tripped", ctrl.sign_wd.tripped)
|
||||
check("the commanded value is 0 W", ctrl.target == 0.0)
|
||||
check("0 W actually reached the device", 0.0 in hass.writes)
|
||||
check("and it got there through the failsafe claim, not by accident",
|
||||
"failsafe" in ctrl.reason)
|
||||
print(f" status line: {ctrl.reason!r}")
|
||||
check("the status page says so in words",
|
||||
any("SIGN-DISAGREEMENT FAILSAFE" in c["text"] for c in ctrl.checks()))
|
||||
check("the banner leads with it",
|
||||
"FAILSAFE" in ctrl.status_payload()["banner"])
|
||||
check("MQTT reports the failsafe state", ctrl.sign_wd.tripped)
|
||||
check("it stays at 0 W on later cycles too",
|
||||
hass.writes[-1] == 0.0 and hass.writes.count(0.0) >= 1)
|
||||
|
||||
print()
|
||||
if fails:
|
||||
print(f"{len(fails)} FAILED: {', '.join(fails)}")
|
||||
sys.exit(1)
|
||||
print("all checks passed")
|
||||