glenn schrooyenandClaude Opus 5 9aed43990b SAFETY-02: a loop can be fresh, tracking and inside its rating and still push the wrong way
The stale-input watchdog asks whether the meter is still talking. The saturation
freeze asks whether the inverter can follow. The output clamp asks whether the
number is too big. A loop can pass all three while charging the battery out of
the grid, because the only thing wrong is the sign.

On 2026-08-20 a commercial controller did exactly that four times in one day,
for up to 77 minutes at a stretch, reaching a commanded -14 768 W against a
±5000 W inverter. app/watchdog.py compares the emitted setpoint against the
authoritative P1 figure and, when they oppose each other with both over 300 W
for 180 s continuously, files a failsafe SET claim at P_SAFETY, commands 0 W and
latches there until an operator starts control again.

Validated against that day rather than against an argument: sim/replay_sign.py
in the infra repo drives this module over the committed captures of both
2026-08-20 and the healthy 2026-08-23 and reaches 18 trips on the fault day -
every one inside a window NOTES.md §4.7 accounts for - and 0 on the healthy day.
The four episodes do share one signature: 0.3 / 0.9 / 10.5 / 0.0 % sign
agreement inside them against 92.9 % healthy.

Three decisions the ticket could not make:

- It is DISARMED whenever the grid-following loop is not what is driving. Sign
  agreement is a property of a loop that follows the meter, and a maintenance
  grid charge opposes the meter by design - 2500 W of charge into a house
  drawing 500 W is +3000 W on the meter against a -2500 W command, for hours.
  The gate tests the emitted number, not the winning claim's name, because a
  limit claim can let the loop "win" and still replace its value.
- The trip LATCHES. Commanding 0 W removes the command side of the comparison,
  so the disagreement always clears the moment the trip works.
- sign_disagree_w at or above max_w is refused at startup. The arbiter never
  lets a command exceed max_w, so such a threshold leaves the watchdog incapable
  of firing while the status page still reports it armed.

What it does not catch, said out loud: an inverter that ACTS opposite to its
command moves the meter further the same way, leaving command and meter in
agreement. That is the saturation freeze's job.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-28 21:51:35 +02:00

249 lines
9.8 KiB
Python

"""Runnable check for the sign-disagreement watchdog. `python3 test_watchdog.py`
Every case here is either a fault this must catch or a piece of NORMAL behaviour
it must not mistake for one. The second list is the longer one on purpose: an
alarm that fires on ordinary operation is worse than no alarm, because the next
person switches it off.
The headline validation is not here - it is `sim/replay_sign.py` in the infra
repo, which drives this module over the two captured bus days. This file is the
table-driven half: boundaries, timers, the latch, and the arming gate.
"""
import sys
from datetime import datetime, timedelta, timezone
from app.watchdog import SignWatchdog, SignWatchdogConfig
fails = []
T0 = datetime(2026, 8, 20, 15, 0, 0, tzinfo=timezone.utc)
def check(name, cond):
print(f" {'ok ' if cond else 'FAIL'} {name}")
if not cond:
fails.append(name)
def drive(samples, cfg=None, following=True):
"""Feed (offset_s, commanded_w, grid_w) tuples. Returns (wd, trip_offset)."""
wd = SignWatchdog(cfg)
trip_at = None
for item in samples:
offset, cmd, grid = item[0], item[1], item[2]
f = item[3] if len(item) > 3 else following
if wd.evaluate(cmd, grid, f, T0 + timedelta(seconds=offset)) and trip_at is None:
trip_at = offset
return wd, trip_at
def opposed(duration_s, step=5, cmd=-1000, grid=1500, following=True, start=0):
return [(start + t, cmd, grid, following)
for t in range(0, int(duration_s) + 1, step)]
print("the fault it exists to catch")
wd, at = drive(opposed(300))
check("charging into an importing house trips", wd.tripped)
check("and trips at 180 s, not before", at == 180)
check("the reason names both signals", "-1000" in wd.reason and "+1500" in wd.reason)
print(f" e.g. {wd.reason!r}")
wd, at = drive(opposed(300, cmd=2000, grid=-2000))
check("discharging into an exporting house trips too", wd.tripped and at == 180)
print()
print("the boundaries")
wd, _ = drive(opposed(600, cmd=-300, grid=1500))
check("300 W exactly does NOT qualify (strictly greater)", not wd.tripped)
wd, _ = drive(opposed(600, cmd=-301, grid=1500))
check("301 W does", wd.tripped)
wd, _ = drive(opposed(600, cmd=-1000, grid=300))
check("a 300 W meter does not qualify either", not wd.tripped)
wd, _ = drive(opposed(175))
check("175 s of disagreement does not trip", not wd.tripped)
wd, _ = drive(opposed(180))
check("180 s does (>= hold_s)", wd.tripped)
print()
print("continuity - the rule that produced zero false positives on real data")
broken = opposed(175) + [(180, -1000, -1500)] + opposed(175, start=185)
wd, _ = drive(broken)
check("179 s, one agreeing sample, then 175 s more: no trip", not wd.tripped)
check("and the window really was reset", wd.disagree_since is not None)
long_enough = broken + opposed(200, start=365)
wd, _ = drive(long_enough)
check("but a full 180 s after the reset does trip", wd.tripped)
print()
print("things that are NOT faults")
# The load-step transient. Measured on the healthy capture: longest 30 s.
wd, _ = drive(opposed(30) + [(35 + t, 800, 900) for t in range(0, 300, 5)])
check("a 30 s load-step crossover does not trip", not wd.tripped)
# SoC 10 %, Standby, declining a 1350 W discharge. The battery does nothing, so
# the meter stays where it was and the command agrees with it.
wd, _ = drive([(t, 1350, 1350) for t in range(0, 900, 5)])
check("a battery refusing a discharge command cannot trip it", not wd.tripped)
# A frozen meter drives command and reading into agreement, not disagreement.
wd, _ = drive([(t, 800, 800) for t in range(0, 900, 5)])
check("a frozen meter cannot trip it", not wd.tripped)
# Maintenance grid charge: 2500 W of charge against an importing house, for
# hours. Opposed, both huge - and entirely correct.
wd, _ = drive(opposed(7200, cmd=-2500, grid=3000, following=False))
check("two hours of maintenance grid charge does not trip", not wd.tripped)
check("and the timer never even started", wd.disagree_since is None)
wd, _ = drive([(t, -1000, None) for t in range(0, 900, 5)])
check("a missing meter reading does not trip", not wd.tripped)
wd, _ = drive(opposed(175) + [(180, -1000, None)] + opposed(600, start=185))
check("a missing reading mid-window RESETS it rather than accumulating",
wd.tripped and wd.disagree_since is not None)
wd, at = drive(opposed(175) + [(180, -1000, None)] + opposed(600, start=185))
check("...so the trip lands 180 s after the gap, not after 180 s total",
at == 365)
wd, _ = drive([(t, 0.0, 3000) for t in range(0, 900, 5)])
check("a 0 W command is not a wrong-direction command", not wd.tripped)
print()
print("the latch")
wd, _ = drive(opposed(200))
check("tripped after the fault", wd.tripped)
# The trip commands 0 W, which removes the command side of the comparison.
for t in range(200, 900, 5):
wd.evaluate(0.0, 3000, True, T0 + timedelta(seconds=t))
check("stays tripped once the command is zeroed", wd.tripped)
for t in range(900, 1500, 5):
wd.evaluate(1000, 1000, True, T0 + timedelta(seconds=t))
check("stays tripped even once everything looks healthy again", wd.tripped)
wd.reset()
check("reset() is the only way out", not wd.tripped and wd.disagree_since is None)
check("and the reason is cleared with it", wd.reason == "")
print()
print("the thresholds are configuration, not constants")
cfg = SignWatchdogConfig(min_w=800.0, hold_s=60.0)
wd, at = drive(opposed(300, cmd=-1000, grid=1500), cfg=cfg)
check("a 60 s hold trips at 60 s", wd.tripped and at == 60)
wd, _ = drive(opposed(600, cmd=-700, grid=1500), cfg=cfg)
check("an 800 W gate ignores a 700 W command", not wd.tripped)
print()
print("the configuration that would disarm it is refused")
from app.validate import validate_startup_config # noqa: E402
base = {"setpoint_entity": "number.sp", "meter_source": "off",
"meter_phases": 1, "meter_max_age_s": 30}
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 300},
-5000, 5000)
check("300 W under a 2000 W ceiling is accepted", p == [])
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 2000},
-5000, 5000)
check("a threshold AT max_w is refused", len(p) == 1 and "never fire" in p[0])
p = validate_startup_config({**base, "max_w": 500, "sign_disagree_w": 3000},
-5000, 5000)
check("a threshold above max_w is refused", len(p) == 1 and "never fire" in p[0])
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 1999},
-5000, 5000)
check("one watt under the ceiling is reachable, so accepted", p == [])
print()
print("end to end: the trip is COMMAND ZERO, not alarm-only")
# ⚠️ THE FAULT INJECTED HERE IS A NEGATIVE GAIN, and that is not a contrivance -
# it is the minimal faithful model of what this watchdog is for. The check
# compares the loop's OUTPUT DIRECTION against the INPUT STATE it was regulating,
# so what it detects is a loop whose two ends have become decoupled in sign: a
# gain, a claim or a strategy with its polarity inverted, or an integrator so far
# wound up that unwinding takes minutes. (Illusmart's was the last one: it
# reached -14 768 W against a +-5000 W rail while writing once every 20-60 s, and
# that arithmetic alone is 5-15 minutes of wrong-direction command.)
#
# `gain` is float(0.05,1.0) in the schema, so this is not a reachable
# configuration - it is a stand-in for a code regression, which is the case a
# unit test can actually hold the line on.
import asyncio # noqa: E402
from app.main import Controller # noqa: E402
class _Hass:
def __init__(self):
self.writes = []
async def limits(self, entity):
return (-5000.0, 5000.0, 1.0)
async def number(self, entity, invert=False):
# A house importing 2000 W, steadily, whatever the battery does.
return {"sensor.grid": 2000.0, "sensor.soc": 50.0,
"sensor.batt": 0.0}.get(entity)
async def set_number(self, entity, value):
self.writes.append(float(value))
return True
class _S:
data = {}
def set(self, *a):
pass
def get_time(self, *a):
return None
class _P:
enabled = False
def publish(self, *a, **k):
pass
def close(self):
pass
async def _e2e():
hass = _Hass()
opts = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 2000, "gain": -0.6,
"sign_disagree_w": 300, "sign_disagree_s": 1, "auto_start": True}
c = Controller(opts, hass, _S(), _P(), stop=asyncio.Event())
c.auto = True
c.dev_min, c.dev_max = -5000.0, 5000.0
seen_wrong_way = False
for _ in range(12):
await c.read_inputs()
await c.cycle()
if c.target < -300 and not c.sign_wd.tripped:
seen_wrong_way = True
await asyncio.sleep(0.25)
return c, hass, seen_wrong_way
ctrl, hass, wrong_way = asyncio.run(_e2e())
check("the broken loop really did command charge into an import first", wrong_way)
check("the watchdog tripped", ctrl.sign_wd.tripped)
check("the commanded value is 0 W", ctrl.target == 0.0)
check("0 W actually reached the device", 0.0 in hass.writes)
check("and it got there through the failsafe claim, not by accident",
"failsafe" in ctrl.reason)
print(f" status line: {ctrl.reason!r}")
check("the status page says so in words",
any("SIGN-DISAGREEMENT FAILSAFE" in c["text"] for c in ctrl.checks()))
check("the banner leads with it",
"FAILSAFE" in ctrl.status_payload()["banner"])
check("MQTT reports the failsafe state", ctrl.sign_wd.tripped)
check("it stays at 0 W on later cycles too",
hass.writes[-1] == 0.0 and hass.writes.count(0.0) >= 1)
print()
if fails:
print(f"{len(fails)} FAILED: {', '.join(fails)}")
sys.exit(1)
print("all checks passed")