run_control() ran cycle() only when the meter value differed from the previous poll. A meter that repeats a value therefore ran no control cycles at all - while the heartbeat kept re-emitting the last command and the firmware kept putting it on the wire every 2 s. Layer 1 stayed fed and every indicator read healthy, so a command computed from an old reading went on being executed through whatever the load did next. TEL-05 measured it: 70 s at a literally constant 350.0 W, 14 arrivals, zero cycles. cycle_floor_s (default 15 s) is a deadline on the GAP between cycles, reset by every cycle whichever trigger fired - not a second scheduler. On a healthy meter it never elapses, so the cycle rate and the commanded sequence are unchanged; test_loop.py asserts that by driving the real loop twice on one binary (a huge cycle_floor_s reproduces the old behaviour) and diffing the writes. 15 s is bracketed: above the ~11 s worst gap on a merely-unlucky healthy meter (~5 s arrivals, 1 s detection, one dropped poll retried on the next tick), below meter_max_age_s and the firmware's 30 s ingest veto, and equal to stale_input_s. A floor cycle runs the full law. Freshness is already decided upstream - past meter_max_age_s the reading is None, which is a P_SAFETY 0 W claim - and the integrator advances per cycle, not per second, so bounding the gap bounds the accumulation. Not a freeze detector: nothing here decides whether a repeated reading is true. DOCS.md's "accepted deviation" passage is qualified rather than deleted - the window is now bounded at 3 x cycle_floor_s instead of open-ended, and its "nothing accumulates while it is stalled" argument is called out as having covered windup and not staleness. Same correction in control.py's comment. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
21 KiB
Changelog
0.4.0
CFG-01. The add-on now refuses to start on a configuration it cannot honour,
instead of logging a line and carrying on. validate_startup_config() runs in
amain() before the broker, the web server or any task exists, so a refusal
cannot leave half a controller running behind a UI.
It refuses only where continuing produces one of two outcomes: (a) a stated
limit is untrue - the operator configured a bound and a lower layer silently
enforces a different one - or (b) the add-on is inert and indistinguishable
from healthy. (b) is not a special case of (a): with no setpoint_entity, layer
1 pinning the inverter at 0 W is the failsafe working. The system does not
become unsafe, it becomes a convincing impression of a working controller.
Four things qualify:
max_wabove (or below) the setpoint device's own rating. This is the one that changed behaviour. It used to warnthe device winsand run anyway, withwrite_setpoint()silently clamping, so the configured ceiling was never the real one and the only evidence had scrolled off the log. The refusal names the configured value, the device's value, and which wins.- No
setpoint_entity. A controller with no actuator: every write is a no-op, the device rating is never read, and the ESP32 heartbeat that holds off the layer-1 failsafe never happens. It ran, looked healthy, and moved nothing. - A
meter_sourcethat can never produce a reading - missingp1_host, missingp1_net_entity, a blank MQTT topic, a phase list disagreeing withmeter_phases, an unknown source name, or ameter_poll_sat or pastmeter_max_age_s. These were already caught, but they only disabled ingestion, which leaves the grid reading None forever: permanent "inputs missing", 0 W, and a status page indistinguishable from a healthy meter nobody has sent anything to yet. meter_max_age_sabove the firmware's ingest veto. The schema acceptsint(5,300); the ESP32's threshold is a compile-timemax_age_s: "30"and it trips layer 1 atp1_age_s >= 30. Set 120 and the add-on treats a 119 s reading as fresh and keeps commanding, while the firmware has already vetoed and is holding the inverter at 0 W - healthy meter, running controller, nothing moving, and no line anywhere saying the number you set was overruled. Structurally the same fault as themax_wcase. Only above the veto is refused: below it the add-on gives up first, which is fail-safe and visible on its own status page. Mirrored asvalidate.FIRMWARE_INGEST_VETO_S- it cannot be imported from a compile-time YAML substitution, so it carries a note about the one direction in which it can go stale.
max_w at or below zero is refused too. Schema-blocked on a real install, but
validate_startup_config() is now also the simulation suite's entry point, and
a non-positive max_w inverts the arbiter's supervised bounds into a
contradiction that resolves to 0 W - i.e. it would read as a safety trip rather
than as the typo it is.
The predicates for the meter group still live in p1.validate_meter_options(),
which build_source() also calls - one definition, two callers, not two
competing validators. Two transports gained a check they never had: ha_dsmr
with only one of its two entities, and mqtt_p1 with a blank topic, both of
which previously built a transport that could never read.
Deliberately not refused, because it is untidy rather than unsafe:
integrator_max_w above max_w (the arbiter still bounds the wire to ±max_w,
so the cost is unwind latency, not amperage - warned), a missing soc_entity /
batt_entity (fail-safe, and already a red NOT READY banner naming it), a
setpoint_entity that has not appeared on the Core API yet (ESPHome is routinely
late; refusing would make a slow boot need a human - re-checked once the real
rating arrives), and a thin-but-nonzero meter_poll_s margin.
A refusal is legible as a refusal: a banner that says in words that this is a
configuration problem and nothing is broken, the numbered problems, no traceback,
and exit status 78 (EX_CONFIG).
SAFETY-12. The control loop now evaluates on a clock as well as on a change.
run_control() ran cycle() only when the meter value differed from the
previous poll, so a meter that repeated a value ran no control cycles at
all - while the heartbeat went on re-emitting the last command and the
firmware went on putting it on the wire every 2 s. Layer 1 stayed fed, every
indicator read healthy, and a command computed from an old reading kept being
executed through whatever the load did next. Measured on the rig during TEL-05:
70 s at a literally constant 350.0 W with 14 arrivals and zero cycles.
cycle_floor_s (default 15 s) is a deadline on the gap between cycles, not
a second scheduler: every cycle resets it, whichever trigger fired. On a healthy
meter it never elapses, so the cycle rate, the write sequence and therefore the
per-cycle gain the tuning was measured against are unchanged - asserted in
test_loop.py by driving the real loop twice on one binary (a huge
cycle_floor_s reproduces the old behaviour exactly) and comparing the
commanded values.
15 s is bracketed, not round. Below it: arrivals are ~5 s (NOTES.md measures
4.97 s), detected up to 1 s late by the 1 s poll, and one dropped poll is
retried on the next tick - about 11 s worst case on a meter that is merely
unlucky, which the floor must not fire on. Above it: meter_max_age_s is 30 s,
past which there is no reading to evaluate, and the firmware's ingest veto is
also 30 s - so the loop is guaranteed to have re-decided at least twice inside
any window in which layer 1 might otherwise be the only thing deciding. It is
also exactly stale_input_s, this system's existing answer to "how long may we
hold without re-deciding".
A floor cycle runs the full law on the same inputs, integrator included. The
freshness question is already answered upstream and answered harder - past
meter_max_age_s the reading is None, which is "inputs missing", which is a
P_SAFETY 0 W claim - so a floor cycle can only ever run on a reading this
system already calls fresh. The integrator advances per cycle, not per second,
so bounding the gap bounds the accumulation; integrator_max_w bounds it after
that. A gentler second law for floor cycles would be a second set of dynamics
nobody can test on this hardware.
⚠️ This is not a freeze detector, and TEL-05 established one cannot be built
here: at the converged -10 W target a 1 Wh register needs ~6 minutes to move
while the power figure legitimately repeats, so any threshold on unchanged_s
false-trips at the exact operating point we run at. Nothing in this change
decides whether a repeated reading is true. It stops "the number is the same"
from meaning "do not think". The consequence, stated plainly: against a meter
genuinely frozen at a wrong value the loop will now correct toward that wrong
value rather than hold a stale command, bounded by max_w, the arbiter and the
device rating. That was already what happened to a lying meter whose value
merely jittered; bit-exact repetition was never a safety property.
DOCS.md's "Saturation is counted in cycles, not seconds" section documented
the old behaviour as an accepted deviation. It is qualified, not deleted:
the deviation survives (the window is still counted in cycles, and 3 x 15 s is
still not the specification's 10 s) but it is now bounded at 45 s instead of
open-ended, and the passage's second justification - "nothing accumulates while
it is stalled" - is called out as having covered integrator windup and not
staleness, which was the actual hazard. The same wrong argument in
control.py's saturation comment is corrected too.
TEL-04. meter_source: ha_signed reads a single signed power entity, which
is the shape a HomeWizard P1 publishes. Both transports 0.3.0 shipped require two
unsigned registers and refuse negatives, so neither fits the meter installed here.
TEL-05. meter_source: homewizard_local polls the meter's own local API
directly. This exists because of something the HA paths cannot do: Home Assistant
fires no state change for a repeated reading and exposes no arrival signal at
all, so sensor.p1_sample_age_s on those transports measures time since the
value changed, not since the meter reported. Real captured data has gaps of
42 s and 97 s between changes on a perfectly healthy meter - long enough for a
30 s staleness threshold to command 0 W for no reason. Every HTTP response to the
local API is a genuine arrival, so the age means what it says.
Verified on the rig against a literally constant 350.0 W for 70 s - the exact state where the HA path recorded zero samples in 45 s - with 14 arrivals and the age never exceeding the poll cadence.
Set p1_host to the meter's address and meter_poll_s (default 5 s, matching
the meter's own ~5 s update). Still defaults to off; nothing changes for an
install that does not opt in.
Freeze detection is separate and deliberately not thresholded: a meter answering
200 OK with a stale number is arriving, so no arrival stamp can flag it. The
energy registers carry that as unchanged_s, surfaced on the status line for a
human to read rather than alarmed on - at a converged -10 W a 1 Wh register needs
about six minutes to move, so any threshold would false-trip at the target
operating point.
Unreleased
TEL-05. A fourth meter_source, homewizard_local, which polls a
HomeWizard P1's own local API (GET /api/v1/data) instead of watching a
Home Assistant entity. Set p1_host to the meter's address; meter_poll_s
(default 5 s, the meter's own update rate) sets the cadence.
✅ This is the first transport whose sensor.p1_sample_age_s measures when
the meter reported, and therefore the first one a firmware watchdog may
threshold. Every HTTP response is an arrival: the meter answered, now, with
its current reading, and whether the number moved is not consulted. Home
Assistant cannot express that at all — a repeated reading emits no
state_changed, advances last_reported on neither serialiser, and
state_reported is not subscribable ("Event filter is required"). On
ha_signed that made a healthy meter under a flat load indistinguishable from
a dead one, and our own capture of this house's meter goes 42.2 s and 97.0 s
between changes — both past the default meter_max_age_s of 30, i.e. a false
trip to 0 W on a meter that is fine. If you have a HomeWizard P1, move to this
mode.
Everything TEL-01 established is reused, not re-implemented: ingest
timestamping, meter_max_age_s, the clock-recomputed age, the plausibility
bounds and the §20 unsigned-decode rejection, and the same split_signed sign
convention ha_signed uses. A failed or timed-out poll submits nothing, so it
is a missing reading — never 0 W — and it does not reset the age.
Verified on the ENV-01 rig against sim/hwsim.py, steady and with --fault freeze injected. Still defaults to off.
⚠️ An arrival stamp still cannot see a frozen meter, and no arrival
detector can: a meter answering 200 OK forever with a stale number is
arriving. The local API does expose what the HA path never had — the
total_power_*_kwh registers stop advancing — and the transport tracks it as
unchanged_s, but that is deliberately not folded into the age and not
thresholded: this controller regulates grid power toward ~0 W, and at a
converged −10 W the export register needs six minutes to move by its 1 Wh
resolution while the power figure legitimately repeats. Thresholding it at 30 s
would rebuild the false-trip limit cycle at the exact operating point we aim
for. Freeze detection needs the low-power case solved first, separately. It is
shown on the status page's P1 line instead — leaving it unthresholded only
holds up if a human can read it, so now they can.
TEL-04. A third meter_source, ha_signed, reading one signed Home
Assistant entity: positive = import, negative = export. That is the shape a
HomeWizard P1 publishes (sensor.p1_meter_active_power), and it is the meter
actually fitted here - which neither TEL-01 transport can read, because
ha_dsmr needs two unsigned registers and refuses a negative one, i.e. every
exporting telegram. Set p1_net_entity, and p1_phase_net_entities for the
per-phase capacity-tariff figures on a three-phase connection.
Everything TEL-01 established is inherited rather than re-implemented - the
new transport is a subclass of the ha_dsmr one overriding only which
entities it wants and how they become a sample. So ingest timestamping,
meter_max_age_s, sensor.p1_sample_age_s recomputed against the clock and
republished once a second, the plausibility bounds, and unavailable /
unknown treated as a missing reading and never 0 W all behave identically
across the three sources.
Still defaults to off; an existing install is unaffected until it opts in.
⚠️ sensor.p1_sample_age_s is published on ha_signed, but must not yet be
thresholded by the ESP32 stale-input watchdog. On the HA WebSocket paths the
age is stamped from state_changed, so it measures time since the value
changed, not since the meter reported - and Home Assistant exposes no
arrival signal for a repeated reading (no state_changed, no last_reported
movement on either serialiser, and state_reported is not subscribable over
the WebSocket). Measured on the ENV-01 rig against the real HomeWizard
integration. ha_dsmr mostly escapes it because a telegram moves several
entities at once; ha_signed has one, so a healthy meter under a flat load is
indistinguishable from a dead one. Our own capture has the house meter going
42.2 s and 97.0 s between changes. Raising meter_max_age_s does not fix that,
it only chooses which error you get; the fix is an arrival stamp from the meter
itself and is a separate ticket. Full detail in DOCS.md.
0.3.0
SAFETY-04. The control law's integrator is now an explicit accumulator,
bounded independently of the output clamp instead of inheriting whatever
headroom the clamp happened to leave. It also freezes while the inverter is
not tracking, rather than continuing to wind up against a command nothing is
acting on. integrator_max_w (default 0) governs the bound; 0 means
"follow max_w", which is the existing behaviour.
Behaviour is unchanged at the defaults - a 4,928-case equivalence sweep
against the previous control law confirms it decides identically at
integrator_max_w: 0.
TEL-01. P1 meter ingestion, so a Belgian P1's two unsigned registers
(consumption, injection) no longer need a hand-written signed template
sensor: the subtraction moves into the add-on, done once and tested. Two
transports, chosen with the new meter_source option: ha_dsmr subscribes
to the DSMR integration over the HA WebSocket, mqtt_p1 reads a topic.
Defaults to off, which keeps the existing meter_entity path untouched -
nothing changes for an install that does not opt in.
Enabling it publishes sensor.p1_sample_age_s: seconds since the newest
accepted telegram, recomputed against the clock and republished roughly once
a second rather than only when a telegram lands. That is deliberate - Home
Assistant only pushes a state on change, so a meter sitting at a genuinely
constant reading would otherwise look identical to a dead one. Watching the
age instead means a frozen meter shows a climbing age, not a flat line. The
firmware watchdog subscribes to this exact entity id.
Known limits, both already in DOCS.md: on mqtt_p1, a bridge stuck
republishing its last telegram still "arrives", so the age cannot detect
that particular failure - prefer ha_dsmr where both are available. And a
dead P1 meter takes 45 s to reach 0 W commanded (30 s for meter_max_age_s
to call the reading stale, then 15 s of stale_input_s on top), which is
meter_max_age_s and stale_input_s stacking, not either one alone.
0.2.1
target_grid_w (default -10 W): what the meter should rest at. The deadband
holds any resting point inside it indefinitely, and the meter bills import and
export on separate registers, so resting at +14 W import costs 0.34 kWh/day
with the loop behaving perfectly. Biasing the target slightly negative moves
that residue onto the export register. Configurable in the Configuration tab;
see DOCS.md for the trade-off table.
Behaviour is unchanged at target_grid_w: 0.
0.2.0
Precedence between strategies is now a first-class object instead of an if/else ladder, ahead of there being more than three of them.
Every strategy returns a CLAIM each cycle - set ("I want X") or limit ("the
result must stay within these bounds") - and arbiter.py resolves them by one
rule:
- Highest-priority
setwins; no claim at all means 0 W. - Then every
limitwhose priority is >= that set's priority applies, most restrictive first. - Contradictory limits are a BUG: command 0 W and say so.
Clause 2 is why "money outranks maintenance" is now a consequence of the priorities rather than a special case in a Jinja template: the maintenance charge-only limit binds the loop, but will not bind a higher-priority peak shaving claim when one exists.
- Maintenance shaping (charge-only, cheap-window floor) moved out of the control
law.
control.pyis once again only a controller that tracks the meter. - The loop computes from the ARBITER's last output, not its own last wish. If something outranked it, that is what the hardware actually did, and tracking anything else makes it jump when it regains control.
- Every decision is explainable: "loop -> 0 W, limited by maintenance (charge-only)" now appears in the UI and the log, instead of a bare number.
- Safety limits (device rating, supervised max_w) bind every strategy including the highest, and are still enforced a second time at the point of writing.
0.1.6
Findings from installing this on a live system, replacing a working YAML implementation. Every one of these was silent - the add-on looked healthy while being completely unable to do its job.
run.shmust use#!/usr/bin/with-contenv sh. The HA base images run s6-overlay, which starts services with a SANITISED environment. With a plain shebang, SUPERVISOR_TOKEN is simply absent and every Home Assistant call returns 401 - whilehomeassistant_api: truemakes the permissions look correctly granted. Startup now logs the token length and probes the Core API, so the next person sees it in one line.- Bump
version:for every change. Supervisor keys the built image by version, so editing source and rebuilding silently reuses the old image. Two fixes appeared not to work because of this. - Dependencies come from apk, not pip. Alpine is musl and there are no musl wheels for aiohttp; pip would compile it on the client's Pi.
- paho-mqtt 1.x and 2.x are both supported. Alpine ships 1.x, which has no
CallbackAPIVersion; that raised and took the whole add-on down with it. - MQTT can no longer take down control. Publisher construction is wrapped - observability must never stop the controller.
- MQTT discovery is published from
on_connect. paho drops QoS-0 publishes issued before the CONNACK, so announcing straight afterconnect()published nothing at all while logging "MQTT connected". - Repeated failures log at most once a minute. The control loop retries every second; unthrottled warnings rolled the log buffer and destroyed the startup diagnostics needed to debug the 401 above.
auto_startworks. The store's defaults suppliedauto: False, so the fallback to the option could never fire.
Known issue: after deleting the MQTT entities from the registry during development, Home Assistant would not re-adopt them from retained discovery - not even after clearing the retained topics and reconnecting. The add-on publishes correct discovery and live state (verified on the broker); this is an HA-side adoption problem and affects status entities only, never control.
0.1.0
First packaged release. Ports the control loop and the monthly maintenance cycle from the reference Home Assistant implementation into an add-on.
- Grid-following control: gain/slew/clamp/deadband with anti-windup, all tuned against measured hardware behaviour (see FIELD-GUIDE.md §14).
- Saturation freeze with the duration term — three consecutive diverging cycles, not one. The instantaneous test fires on every large correction, because the plant itself needs 3-6 s to settle.
- Monthly maintenance cycle as an ownership state machine: drain / charge / hold, with exactly one writer of the setpoint at any moment.
- Capacity-tariff awareness: the maintenance charge is capped by quarter-hour peak headroom, and peak shaving outranks the maintenance schedule.
- Failsafe behaviour: commands 0 W on missing inputs, on stop, and on shutdown. Never replays a stale setpoint - the reference implementation did, and the hardware watchdog cannot catch that.
- Ingress UI with a commissioning checklist that names problems in words.
- Optional MQTT discovery for status entities.
Known limits:
- Home Assistant OS / Supervised only (add-ons cannot run on Container/Core).
- The inverter protocol is reverse-engineered; no vendor contract.
- Without the optional RS485 e-stop, nothing covers the host machine dying.