glenn schrooyenandClaude Opus 5 88cd97cc7a SAFETY-12: the loop thinks on a clock, not only when the number moves
run_control() ran cycle() only when the meter value differed from the previous
poll. A meter that repeats a value therefore ran no control cycles at all -
while the heartbeat kept re-emitting the last command and the firmware kept
putting it on the wire every 2 s. Layer 1 stayed fed and every indicator read
healthy, so a command computed from an old reading went on being executed
through whatever the load did next. TEL-05 measured it: 70 s at a literally
constant 350.0 W, 14 arrivals, zero cycles.

cycle_floor_s (default 15 s) is a deadline on the GAP between cycles, reset by
every cycle whichever trigger fired - not a second scheduler. On a healthy meter
it never elapses, so the cycle rate and the commanded sequence are unchanged;
test_loop.py asserts that by driving the real loop twice on one binary (a huge
cycle_floor_s reproduces the old behaviour) and diffing the writes.

15 s is bracketed: above the ~11 s worst gap on a merely-unlucky healthy meter
(~5 s arrivals, 1 s detection, one dropped poll retried on the next tick), below
meter_max_age_s and the firmware's 30 s ingest veto, and equal to stale_input_s.

A floor cycle runs the full law. Freshness is already decided upstream - past
meter_max_age_s the reading is None, which is a P_SAFETY 0 W claim - and the
integrator advances per cycle, not per second, so bounding the gap bounds the
accumulation.

Not a freeze detector: nothing here decides whether a repeated reading is true.
DOCS.md's "accepted deviation" passage is qualified rather than deleted - the
window is now bounded at 3 x cycle_floor_s instead of open-ended, and its
"nothing accumulates while it is stalled" argument is called out as having
covered windup and not staleness. Same correction in control.py's comment.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-28 20:29:16 +02:00

175 lines
6.5 KiB
Python

"""Runnable check for the control loop's cadence. `python3 test_loop.py`
SAFETY-12: the loop must evaluate on a clock as well as on a change. Before the
fix, `run_control()` ran `cycle()` only when the meter value differed from the
previous poll, so a meter that repeats a value ran NO control cycles while the
heartbeat kept re-emitting the last command - measured on the rig during TEL-05
as 70 s at a literally constant 350.0 W with 14 arrivals and zero cycles.
⚠️ THIS TEST TAKES ~35 SECONDS OF WALL CLOCK, on purpose. The thing under test
is a wall-clock floor inside a loop that sleeps 1 s; mocking the clock would
leave the assertion testing the mock. It drives the real `run_control()` and
counts what actually happened.
`cycle_floor_s` is read from options with no lower bound in code, so a huge
value reproduces the pre-fix behaviour exactly. Every claim below is therefore
an A/B on one binary, not a comparison against a remembered old one.
"""
import asyncio
import sys
import time
from app.main import Controller
fails = []
NEVER = 1e9 # cycle_floor_s so large the floor can never elapse: pre-fix
def check(name, cond):
print(f" {'ok ' if cond else 'FAIL'} {name}")
if not cond:
fails.append(name)
class FakeHass:
"""A scripted meter and a plant that tracks the command instantly."""
def __init__(self, meter):
self.meter = meter
self.batt = 0.0
self.writes = []
self.t0 = time.monotonic()
async def limits(self, entity):
return (-5000.0, 5000.0, 1.0)
async def number(self, entity, invert=False):
if entity == "sensor.grid":
return self.meter(time.monotonic() - self.t0)
if entity == "sensor.batt":
return self.batt
if entity == "sensor.soc":
return 50.0
return None
async def set_number(self, entity, value):
self.writes.append(float(value))
self.batt = float(value)
return True
class _Store:
data = {}
def set(self, *a):
pass
class _Pub:
enabled = False
def publish(self, *a, **k):
pass
def close(self):
pass
BASE = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 2000, "gain": 0.6, "slew_w": 1000,
"deadband_w": 15, "target_grid_w": -10, "step_w": 10,
"heartbeat_s": 10, "stale_input_s": 15}
def drive(meter, floor, seconds):
"""Run the real control loop for `seconds`; return (cycle times, writes)."""
async def go():
hass = FakeHass(meter)
c = Controller(dict(BASE, cycle_floor_s=floor), hass, _Store(), _Pub(),
stop=asyncio.Event())
c.auto = True
stamps = []
real = c.cycle
async def counted():
stamps.append(time.monotonic() - hass.t0)
await real()
c.cycle = counted
task = asyncio.create_task(c.run_control())
await asyncio.sleep(seconds)
c.stopping = True
await asyncio.wait_for(task, timeout=10)
return stamps, hass.writes
return asyncio.run(go())
def worst_gap(stamps, seconds):
"""Longest stretch with no cycle, including the tail after the last one."""
edges = [0.0] + list(stamps) + [seconds]
return max(b - a for a, b in zip(edges, edges[1:]))
# --------------------------------------------------------------------------- #
print("a meter that repeats the same value")
FLAT = lambda t: 350.0 # noqa: E731
FLOOR, SECONDS = 3.0, 12.0
pre_stamps, pre_writes = drive(FLAT, NEVER, SECONDS)
# The defect itself, demonstrated rather than described: one cycle at startup
# and then nothing for the rest of the window, while writes keep happening.
check("pre-fix: a constant meter runs exactly one cycle, at startup",
len(pre_stamps) == 1)
check("...while the heartbeat keeps writing anyway, so nothing looks wrong",
len(pre_writes) >= 2)
post_stamps, post_writes = drive(FLAT, FLOOR, SECONDS)
check("post-fix: the same constant meter runs cycles throughout",
len(post_stamps) >= int(SECONDS / FLOOR) - 1)
# The actual acceptance criterion: a BOUND on the gap, not a count.
gap = worst_gap(post_stamps, SECONDS)
check(f"...with no gap longer than the floor ({gap:.1f}s <= {FLOOR + 1.5:.1f}s)",
gap <= FLOOR + 1.5)
check("...and the loop actually corrected, instead of holding a stale command",
len(post_writes) > len(pre_writes))
# --------------------------------------------------------------------------- #
print("a meter that changes normally - nothing may move")
# ⚠️ THE REGRESSION GUARD, and the more important half. The floor is a deadline
# on the gap between cycles, reset by every cycle whichever trigger fired - not
# a second scheduler. On a healthy meter it must never elapse, so the cycle
# count, the write count and the commanded values must be IDENTICAL either side
# of the fix. Anything else is a new write cadence, which SAFETY-12 forbids:
# the deadband, step_w and the 10 s force-write decide what reaches the wire,
# and this change is only allowed to alter when the loop thinks.
STEPS = [0.0, 300.0, 850.0, -400.0, 120.0, -900.0, 60.0]
LIVE = lambda t: STEPS[int(t // 2) % len(STEPS)] # noqa: E731
a_stamps, a_writes = drive(LIVE, NEVER, 12.0)
b_stamps, b_writes = drive(LIVE, FLOOR, 12.0)
check("a changing meter runs the same number of cycles as before the fix",
len(a_stamps) == len(b_stamps))
check("...commanding exactly the same sequence of values", a_writes == b_writes)
# --------------------------------------------------------------------------- #
print("a meter parked at the target - the converged operating point")
# The case TEL-05 warned about: at the converged target the power figure
# legitimately repeats for minutes. The loop must still run, and must still
# write nothing but the heartbeat, because the deadband - not the arrival
# trigger - is what holds the command still.
AT_TARGET = lambda t: -10.0 # noqa: E731
c_stamps, c_writes = drive(AT_TARGET, NEVER, 12.0)
d_stamps, d_writes = drive(AT_TARGET, FLOOR, 12.0)
check("the loop evaluates at the converged point too", len(d_stamps) > len(c_stamps))
check("...and the deadband still holds the command, so writes are unchanged",
d_writes == c_writes)
# --------------------------------------------------------------------------- #
print()
if fails:
print(f"{len(fails)} FAILED: " + "; ".join(fails))
sys.exit(1)
print("all checks passed")