Nothing had ever run the real `Controller` through the transition inverter B's commissioning performs on 2026-09-12. `tools/rehearse_roster.py` does, over a COPY of a state file given as an input path, and reports the difference: every store key that moved, appeared, vanished or was STRANDED under a name no machine reads; every entity id before and after with orphans named; and whether the maintenance history MAINT-05 moved once survived being moved again. ⭐ WHAT IT FOUND, AND IT IS SAFETY-44's ANSWER. A store that ran pre-DEV-02 flat and declares a multi-inverter roster comes up with its SAFETY-02 latch DISARMED unless the first roster entry happens to be called `inverter-a`. `Controller.__init__` hands `migrate_unit_keys()` the hardcoded `UNIT_A`, so the latch lands in `unit/inverter-a/sign_tripped`; a roster of ["garage","shed"] reads `unit/garage/sign_tripped`, which is absent. And `_grade_store_migration()` - the guard written for exactly this - sees the migration's OWN misdirected key satisfy its `namespaced_latched` test and returns without re-arming. Measured, not argued: the file says `sign_tripped: true`, no inverter is latched, nothing is held at 0 W. The same state file onto a roster whose first entry IS `inverter-a` comes up latched, so the finding is attributable to the name. The staged upgrade reaches it too: the flat start stamps `schema_version`, and the roster start's migration then takes its early return. ⚠️ NO RUNTIME CODE IS CHANGED HERE. The fix to `migrate_unit_keys()` belongs to SAFETY-44 reopened as a defect, shown red before it; this commit is the instrument that shows it red. THE CHECK CAN FAIL, AND WAS SEEN TO. `test_rehearse.py` establishes two CLEAN CONTROLS first - two transitions the shipped code gets right, on which the harness must say nothing - and then breaks the shipped migration and the entity-id composition six ways in a private copy of the tree, requiring each to turn its control from green to red WITH THE RIGHT FINDING NAMED. One mutation is required to SURVIVE, with the reason written down. The synthetic state carries maintenance history and a legacy-shaped latched `sign_tripped` with no `schema_version` beside it, because state built by the happy path cannot detect a migration that only mishandles legacy shapes. ⚠️ THE FIRST DRAFT OF THE HARNESS HAD HABIT 4 IN IT and its own battery caught it - MUTATION.md's thirteenth instance, third in an instrument. The entity diff composed both sides with the same build, so renaming the MQTT device moved every id equally and it reported "no orphans" about a change that orphans everything. `--live-entities` is the fix: a reference that does not move with the code. THE RETREAT is supported and does not corrupt state - the flat rollback view keeps the latch and the first pack's history live - but it orphans eight HA entities, and the ROUND TRIP is not supported: a maintenance cycle completed while rolled back is discarded on re-advance. Stated in DOCS.md as a decision. Fetching /data/state.json, the options blob and the entity list are OWNER STEPS and are written down. ⚠️ Nothing here was run against real state and nothing here claims to have been. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
GoodWe RS485 Controller — Home Assistant add-on repository
Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.
repository.yaml add-on repository metadata
goodwe_controller/ the add-on
config.yaml manifest + options schema (the per-site config form)
app/ the controller
control.py the control law — pure functions, no I/O
maintenance.py the monthly cycle state machine
hass.py Supervisor/Core API access
store.py persistent state in /data
mqtt.py optional status entities
web.py ingress UI — routes only, status and configuration
config_page.py the configuration page's markup, style and script
configui.py its field model, built from the Supervisor's own
schema + translations — owns no key, label or rule
selfconfig.py reading and writing this add-on's own options,
with the validate-first / compare-and-swap gate
main.py orchestration, heartbeat, failsafe behaviour
test_control.py runnable checks — no framework needed
test_maintenance.py runnable checks — walks a full cycle in fake time
DOCS.md the add-on's documentation tab
MUTATION.md how to run a mutation so the result means something
tools/mutation_run.sh the mutation harness - purges bytecode, then grades
tools/supervisor_selfapi_probe.py what the Supervisor really permits and
returns, run against its own release image
firmware/goodwe-master.yaml ESPHome config for the T-CAN485
estop/rs485_log.py optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf the guide techs carry (10pp, A4)
docs/build_guide.py its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md how to edit and rebuild the guide
Picking this up after a break? Read HANDOVER.md first — current state,
what is known broken, and what to do next.
Install
Settings → Add-ons → Add-on store → ⋮ → Repositories → add
https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install GoodWe RS485 Controller.
⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
goodwe_controller/ into the machine's /addons/ folder, then
ha store reload — it appears as a Local add-on.
⚠️ Bump version: in goodwe_controller/config.yaml for every change.
Supervisor keys the built image by that version, so without a bump it silently
reuses the old image and your fix appears not to work — on your bench and on
every client's machine.
Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.
Read this first
The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.
Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:
- ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
- Wind-down before firmware updates — 0 W written before the update starts.
- RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.
Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md
§10 signed.
Development
The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:
cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py
Both must pass before shipping any change. To prove a check bites - the way
almost every claim in this repository was established - mutate the module and
run tools/mutation_run.sh, which clears __pycache__ first. It is not
optional: a same-size edit reverted inside one second leaves CPython reusing the
old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md
has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre —
each assertion corresponds to a rule whose absence produced an observed failure
on real hardware, and the comments in control.py say which.
Compatibility
Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:
| tag | platform | verdict |
|---|---|---|
ESU EMU ESA BPS BPU EMJ IJL |
105 — ES/EM/BP, AA55-era meter bus | supported |
SPB SPN |
745 — SBP G2 (GW…-SBP-20) |
no |
ESN ESC |
745 — ES G2 (GW…-ES-20) |
no |
ETU EHU BTU … |
205/745/753 — ET/EH/BT hybrids | no |
SDT DST MSU NSU … |
PV-only inverters — no battery to control | no |
A "-20" or "G2" suffix means a different platform with a different meter
protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which
is also what Home Assistant's own integration uses to pick a protocol.
- GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
- The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.