# SAFETY-128 - a reading that does not answer the last command is not current
**Status: FIXED on release/1.0 (after 0.20.0).** Code: `app/lateness.py`,
`control.compute(hold=, hold_w=)`, `peakguard.cap_floor()`,
`Controller._readings_late()`, `Controller.read_inputs()` (feeds the fits).
Tests: `test_safety128.py` (`tools/safety128_rig.py`, TEST-23's plant).
**Cause** (SAFETY-127 report). Home Assistant can deliver readings late but
still changing. Every gate judges arrival (SAFETY-01) or a value that stops
changing (SAFETY-18, SAFETY-37), so a late reading passes them all. The loop
then corrects, each cycle, an error its last command has already fixed: a
loop with a dead time far longer than its cycle, which swings and grows. The
peak guard projects the quarter from the same late figures and pushes to the
inverter limit in its last seconds (OPT-34 rig F-2).
**Rule.**
1. *Find late readings* (`Answer.watch()`, every 2 s, from the 1 s reads).
- **Batteries** (`Delay`): fit one `d` so that each battery's reading minus
its own request at `t - d` (averaged over 2 s for the battery's lag and
the read) is flattest. The house does not move that reading, so a
repeating load cannot line up with it (review round 1, B1). Needs 5 new
readings in 60 s and the request and the reading each to move 300 W.
Late from 9.5 s, after 2 late fits in a row. A late fit must explain 75 %
and beat every fit up to 6.5 s by 2x; the shortest delay that fits about
as well (within 2x, or within 2 500 W^2) is taken instead, since a swing's
period fits again. A slow battery (3-10 s lag) answering at once gives no
late fit; at a 15-20 s lag some fits read late (see "What it costs").
No late battery fit counts for 60 s
after a battery gave nothing under its ask: an emptied battery lined its
old movement up as 85 s late.
- **Meter** (`MeterFit`, round 1's fit): `meter(t) + request(t - d)` is the
house alone at the right `d`. Quick, but confounded by the house. Needs
16 new values in 60 s, so only a meter of about 3.5 s or faster: at 5 s
it gave false delays. Late over 8 s. At a slower meter (a 5 s P1) the
same fit runs over 120 s and calls only a delay over 16 s late, on 2 fits
in a row, and never ends a verdict (SAFETY-129). Alone it reads 35-90 s on healthy
runs, a few times in a row; only the slow-start and battery-fit check
below keeps those from a verdict. 10 s late is not found: it cannot be
told from a 10 s slow battery, and it does not swing at 5 s.
- A meter fit says late only with evidence from the batteries' side too:
a request more than 100 W from the battery reading took 3 s or more to
move a reading towards it (`SLOW_START_S`; on time they start within
0-1 s in the recorded house at 1 and 2 s ticks), and no battery fit in
the last 60 s said on time (under 9.5 s). An ask during which a battery
gave nothing under its ask is no slow evidence. A repeating load fools
the meter fit but not these. No meter verdict in the first 150 s.
- On time again on a battery fit under 6.5 s, or a meter fit within 8 s
unless a battery fit said late (hysteresis). With no fit for 120 s the
verdict is dropped.
2. *Hold.* While late, a request more than 100 W from the battery reading is
pending until that reading comes within 100 W of it, or half way. Meanwhile
the loop may not lead the reading by more than 100 W that way, and the peak
guard's floor is capped at the request that stands. The loop is not held
while a battery gives nothing under its ask or refuses (SAFETY-52/94).
3. *Late verdict.* Pending for `LATE_S` (23 s) with no reading moving 100 W
towards it: control holds, then after `stale_input_s` goes to 0 W
("readings late"), as for a missing input.
4. *Seen.* While late an amber row says "Home Assistant readings show requests
about N seconds late, so control holds the batteries." (NL too). N is the
batteries' fitted delay: Home Assistant's lag plus the battery's own
answer. While only the meter has shown it the row gives no figure. One
WARNING (`READINGS_LATE`) per episode and one line when it ends.
**With readings on time** no verdict was reached in any reviewer scenario
(owner-shaped house, ovens 20/40 to 60/60 s, clouds, a 300 W/s battery, 6-8 s
dead times, HA jitter 0-4 s, an EV following the meter, capped batteries, HA
restarts, meter pauses; 1, 2 and 5 s meters) nor in 2 days of the recorded
house at 1, 2 and 5 s ticks, so the commands are the same as without the gate.
The fits run all the time; the pull request has the counts.
**What it costs.**
- Found 36-68 s after a lag starts at 1-2 s meters; at a 5 s meter 30 s late
is found within 100 s after it starts (88 s measured) (the loop first moves 100 W after 60 s,
SAFETY-129) with the export above -200 W, and 10 s late is not found. Until
then control is as before. In a quiet house the "readings late" row stays
about 2 minutes longer after the lag ends (126 s against 32 s on base); no
harm measured, and it clears as early as on base when the load changes.
- A battery that answers slowly is read as late readings and held: a dead
time of 10 s or more (8 s reads 7-8; 10 s reads 10 at 1-2 s meters, 9 at
5 s), or a 15-20 s lag (review round 2). The GoodWe measured settles in 6 s
(`freshness.PLANT_SETTLE_S`); the row then blames Home Assistant wrongly.
- The row can stay up to 180 s after the readings are on time on a steady
site. While only the meter has shown the delay it gives no figure.
- A battery that cannot follow while the readings are late (at a limit, not
reading 0 W) is held, then set to 0 W after 38 s.
- The fits cost a few ms every 2 s (x86, measured after 3 idle days); the
history they read is bounded (60 s of readings, 150 s of requests).
**Left out.** The setpoint -> Home Assistant round trip: the fitted delay gives
the figure from readings the add-on already has. The hold's step-and-pull-back
at extreme lag and the arbitrage charge's sizing on late readings
(`charge_room_w()`) are follow-up cards.