stated the wrong mechanism ⚠️ REVIEW FINDING, BLOCKING, AND IT IS THE EVIDENCE THAT WAS WRONG RATHER THAN THE BEHAVIOUR. Part 8b's cut-out arm claimed an "identical power trace" to the wedged arm and that "what separates them is `account()`". EVERY PART OF THAT WAS FALSE, and the check survived deleting the gate it named. Measured: cut-out arm, account() live named 0/200, distinct B shares: [0] cut-out arm, account() FORCED None named 0/200, distinct B shares: [0] wedged arm, account() live named 200/200, shares 77/125/133/154 W At its own cut-out the pack's usable energy ABOVE that cut-out is zero, so `weights()` answers 0.0, `_fill()`'s preferred pass gives it nothing, the healthy sibling covers the load alone so the last-resort pass never runs, and its share is 0 W ON ALL 200 CYCLES. A unit with a 0 W share is not in `asked`, so `len(asked) < 2` returns {} BEFORE EITHER ARM IS EVALUATED and `account()` is never consulted. Nothing was identical, "100 % of the ask" was 0/0, and the arm never reached the comparison it was written to grade. WHAT REPLACES IT IS A BETTER FACT, NOT A WEAKER ONE: at its own cut-out OPT-09 STOPS ASKING THE PACK AT ALL, so SAFETY-43's relative arm is never reached. That is a SECOND, INDEPENDENT protection sitting UPSTREAM of `account()` - the allocator declines to ask before the detector has to decline to alarm. So the arm is kept and re-pointed, not deleted: * the 0 W share is now ASSERTED (`_sat_last[1][Bee] == 0`), not inferred from the silence - a control that cannot say WHY it is quiet cannot fail; * the arm runs a SECOND time with `account()` DELETED (`no_account=True`) and must still be silent, which is what proves which mechanism does the work; * the account gate's claim is re-pointed at test_delivery.py part 1, where it is graded on a REAL positive 125 W share. ⚠️ AND IT WAS INVISIBLE FOR ONE REASON WORTH KEEPING: that was the ONLY line in part 8b that did not print its shares. `inverter-b+0` would have been on screen from the first run. Every line in the part prints them now. The derated control's vacuity guard also now asserts ITS OWN unit is asked, rather than re-asserting a different run's 200/200 - which is exactly why the old guard could not see this. ALSO, from the same review: N1 app/delivery.py said 0.05 was "twelve times more sensitive" than 0.85. 0.85/0.05 = 17 and no reading of the pair gives 12. An unsupported number in shipped source; replaced with what was actually measured. N2 M14's recorded count was 4 named checks in test_delivery.py and it is 5 - part 1's pre-existing "a shortfall AT the threshold is not one" also goes red. It under-claimed, so it never inflated the evidence, but a recorded figure that does not reproduce is still one. N3 test_delivery.py part 1 printed the alarm sentence with a bare `delinquent(...)["b"]`, which raises KeyError under M12/M13 and ABORTED THE FILE AT PART 1, leaving parts 2-8 ungraded. The direction is safe (an abort is a red; MUTATION.md's defect fabricates only greens) but the recorded coverage read smaller than the truth. It is a `.get` now, and M12/M13's counts are re-run: 7 and 7 named checks, not 5 and 6. CFG-07: the assessment is unchanged (worse by one control cycle, 35.0 -> 40.0 s, deliberately not fixed here) and now says WHEN it has to close - BEFORE INVERTER B IS COMMISSIONED (~2026-09-12), because the band is unreachable at N=1 and commissioning B is when it first becomes reachable - and that CFG-07 HAS NO DECISION DOCUMENT IN THIS TREE, so whoever takes it writes one first. No behaviour change. `delinquent()`'s two arms, the fraction, `min_w` and the N=1 path are all untouched by this commit. 27/27 suites green. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
GoodWe RS485 Controller — Home Assistant add-on repository
Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.
repository.yaml add-on repository metadata
goodwe_controller/ the add-on
config.yaml manifest + options schema (the per-site config form)
app/ the controller
control.py the control law — pure functions, no I/O
maintenance.py the monthly cycle state machine
hass.py Supervisor/Core API access
store.py persistent state in /data
mqtt.py optional status entities
web.py ingress UI — routes only, status and configuration
config_page.py the configuration page's markup, style and script
configui.py its field model, built from the Supervisor's own
schema + translations — owns no key, label or rule
selfconfig.py reading and writing this add-on's own options,
with the validate-first / compare-and-swap gate
main.py orchestration, heartbeat, failsafe behaviour
test_control.py runnable checks — no framework needed
test_maintenance.py runnable checks — walks a full cycle in fake time
DOCS.md the add-on's documentation tab
MUTATION.md how to run a mutation so the result means something
tools/mutation_run.sh the mutation harness - purges bytecode, then grades
tools/supervisor_selfapi_probe.py what the Supervisor really permits and
returns, run against its own release image
firmware/goodwe-master.yaml ESPHome config for the T-CAN485
estop/rs485_log.py optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf the guide techs carry (10pp, A4)
docs/build_guide.py its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md how to edit and rebuild the guide
Picking this up after a break? Read HANDOVER.md first — current state,
what is known broken, and what to do next.
Install
Settings → Add-ons → Add-on store → ⋮ → Repositories → add
https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install GoodWe RS485 Controller.
⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
goodwe_controller/ into the machine's /addons/ folder, then
ha store reload — it appears as a Local add-on.
⚠️ Bump version: in goodwe_controller/config.yaml for every change.
Supervisor keys the built image by that version, so without a bump it silently
reuses the old image and your fix appears not to work — on your bench and on
every client's machine.
Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.
Read this first
The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.
Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:
- ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
- Wind-down before firmware updates — 0 W written before the update starts.
- RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.
Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md
§10 signed.
Development
The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:
cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py
Both must pass before shipping any change. To prove a check bites - the way
almost every claim in this repository was established - mutate the module and
run tools/mutation_run.sh, which clears __pycache__ first. It is not
optional: a same-size edit reverted inside one second leaves CPython reusing the
old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md
has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre —
each assertion corresponds to a rule whose absence produced an observed failure
on real hardware, and the comments in control.py say which.
Compatibility
Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:
| tag | platform | verdict |
|---|---|---|
ESU EMU ESA BPS BPU EMJ IJL |
105 — ES/EM/BP, AA55-era meter bus | supported |
SPB SPN |
745 — SBP G2 (GW…-SBP-20) |
no |
ESN ESC |
745 — ES G2 (GW…-ES-20) |
no |
ETU EHU BTU … |
205/745/753 — ET/EH/BT hybrids | no |
SDT DST MSU NSU … |
PV-only inverters — no battery to control | no |
A "-20" or "G2" suffix means a different platform with a different meter
protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which
is also what Home Assistant's own integration uses to pick a protocol.
- GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
- The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.