goodwe-addon/goodwe_controller/DECISIONS/OPT-09-soc-aware-weights.md
T
glenn schrooyenandClaude Opus 5 8d83ef0dfb
checks / unit (pull_request) Successful in 6m11s
OPT-09: the weights DO move on a wedged unit, and that narrows SAFETY-42
B1, the blocking review finding. §5 of the decision said:

    "A wedged unit reads a healthy SoC, so no envelope closes and no weight
     moves - OPT-09 cannot see it at all."

The first clause is true and is about the ENVELOPE. The second clause is
FALSE, and it was load-bearing for the claim that OPT-09 and SAFETY-42 meet
without overlapping. A weight is a function of a pack's ENERGY HEADROOM, not
of what the pack delivers, so a wedged unit's weight moves whenever its
headroom differs from its sibling's - the ordinary case this card exists to
exploit. And delivery.delinquent() (app/delivery.py:484, threshold at :531)
names a unit only while its short_by() gap exceeds min_w = Tuning.saturation_w
= 500 W in ABSOLUTE WATTS. Shrinking the share shrinks the gap below the
threshold, and the alarm stops firing on a unit still delivering nothing.

So the seam, stated accurately: OPT-09 stops the ask AND narrows SAFETY-42's
detection window for a low-headroom unit. That is a DETECTION REGRESSION at
N=2. It is disclosed here, not fixed: making delinquent() relative to the ask
rather than absolute is SAFETY-42's code and a design change, filed as its own
card.

1. THE CORRECTION, in the three places that carried the claim

   * DECISIONS/OPT-09-soc-aware-weights.md §5 - rewritten. States the seam
     accurately, quotes the sentence it is replacing, carries the measured
     rows and the window arithmetic, and names the residual in the same voice
     as SAFETY-13's "2 of 272" and SAFETY-42's "the discriminator does not
     exist". Also drops "they meet and do not overlap" from the opening.
   * app/packshare.py - a new section in the module docstring, immediately
     after "weights are a comfort choice for stability and not for delivery",
     which is where the over-read starts.
   * CHANGELOG.md - a new paragraph in the SAFETY-42 entry, ending on the
     operator-facing sentence: a wedged inverter with less energy headroom
     than its sibling can now go unreported at ordinary house loads.

   test_packshare.py part 8's closing check and its "what this file cannot
   see" list repeated the same false clause; both now say the ENVELOPE cannot
   reach a wedged unit and point at part 8b for what the WEIGHTS do to it.

2. THE GRADED CHECK - test_packshare.py part 8b, 6 named checks

   The reviewer's probe, reproduced: real compute(), real plan(), real
   packshare.weights(), real delivery.account(), real delivery.delinquent();
   the only model is the plant (A obeys within one cycle inside its rating,
   B accepts its share and delivers 0 W). Unit B is WEDGED at 15 % against
   its own 10 % floor, so envelope() does not close and account() explains
   nothing - a SAFETY-42 true positive by that card's own definition, which
   a PRECONDITION check asserts before anything is concluded from it.

       load 1500 W, B wedged at 15 %, equal weights  named on 199/200 cycles,
         site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
       load 1500 W, B wedged at 15 %, OPT-09 weights named on   0/200 cycles,
         site target +1630 W, shares a+1505, b+125,  grid -5 W, named=(nobody)
       load 6000 W, B wedged at 15 %, equal weights  named on 199/200 cycles
       load 6000 W, B wedged at 15 %, OPT-09 weights named on 195/200 cycles

       suppression window: equal weights, site target < 1000 W; OPT-09
       weights, site target < 6500 W of a 9600 W site

   THE CHECKS ASSERT THE CURRENT, UNFLATTERING BEHAVIOUR ON PURPOSE - that
   the weighted arm names NOBODY where the equal arm names the wedged unit.
   A check asserting the alarm still fires would fail, and papering over it
   would be worse than the original defect. The 6000 W row is there so the
   part is not pinning "the weighted arm never names anybody": past the
   healthy pack's own rating, _fill()'s last-resort pass hands the wedged
   unit 3000 W and both arms name it. The window is real and it has an edge.

   MUTATION - packshare.weights() keeps its shape and forces every weight to
   1.0 (M11 in part 11's table, which now has 11 rows). RUN on a purged tree
   with python3 -B, not reasoned about:

       load 1500 W, B wedged at 15 %, equal weights  named on 199/200 cycles,
         site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
       load 1500 W, B wedged at 15 %, OPT-09 weights named on 199/200 cycles,
         site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
       load 6000 W, B wedged at 15 %, OPT-09 weights named on 199/200 cycles,
         site target +4000 W, shares a+2000, b+2000, grid +4000 W, named=[b]
       suppression window: equal weights < 1000 W; OPT-09 weights < 1000 W

     FAIL  AND WITH OPT-09's WEIGHTS IT IS NAMED ON NONE OF THE 200 [...]
     FAIL  ...and the arithmetic behind it, stated as a window [...]
     FAIL  AND IT IS NOT THAT THE WEIGHTED ARM NEVER NAMES ANYBODY [...]

   test_packshare.py exits 1. Restored: exits 0.

3. THREE PROC-01 PROSE DEFECTS

   * DECISIONS/OPT-09-soc-aware-weights.md:3 said "Base: release/1.0 @
     464d398". The branch was rebased; git merge-base HEAD 3368231 is
     3368231. Corrected, and it says why the old number was there.
   * Same file:13 cited main.py:2272 for "resolution = resolve(...)".
     git show 3368231:goodwe_controller/app/main.py | grep -n says 2422.
     Corrected. The sibling citation arbiter.py:535 is right and is left.
   * DOCS.md:174 said "Since 0.7.x the split is driven by two separate
     things", which tells an operator the fix already shipped. config.yaml
     is 0.8.0 and the live install is 0.7.0, where the split is 50/50 - this
     card's own premise. Now "from 0.8.0 onwards", with an explicit warning
     that 0.7.0 and earlier are a fixed 50/50.

NOT TOUCHED, deliberately: delinquent()'s absolute threshold (SAFETY-42's
code, its own card), and app/main.py:2699's double-logged scope refusal (N4,
filed separately).

INVERTER B DOES NOT EXIST (expected ~2026-09-12). Every two-unit figure above
is TWO COPIES OF A through a plant modelled in test_packshare.py; B's 4600 W /
20.48 kWh / 10 % floor are from the datasheet and the serial. Nothing here was
measured on hardware, and the added disclaimers say so in each place.

Verified with the real harness per .gitea/workflows/checks.yml
(goodwe-addon-checks:1): COLLECTED 24 files, ALLGREEN. Harness positive
control run first - test_validate.py deliberately broken, harness reported
"FAILED: test_validate.py" and exited 1; restored.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-06 22:55:20 +02:00

303 lines
17 KiB
Markdown

# OPT-09 - the weights parameter, and what it is honestly for
**Status:** implemented. **Branch:** `OPT-09`. **Base:** `release/1.0` @ `3368231`
(`git merge-base HEAD 3368231`; the branch was rebased and this line used to name
the pre-rebase base, `464d398`).
## 0. What was actually wrong
`allocator.plan()` has taken a `weights` argument since ALLOC-01, `_fill()`
consumes it in two passes, and **nothing had ever passed one**. Confirmed on the
base commit:
arbiter.py:535 def resolve(claims, *, units=None, weights=None, live=None, ...)
main.py:2422 resolve(claims, units=self.units, live=self.live_units(), ...)
So `weights` was None on every tick of every install, `plan()` turned that into
1.0 per unit, and the site target was split **50/50 regardless of what either
pack could do**. The card was filed as "per-pack arbitrage sizing"; the architect
pass found the sharper content, and it is the sharper content that this branch is
mostly about.
## 1. Two instruments, and they are not interchangeable
`allocator.py` states the rule this card is built on, and it is mechanical rather
than advisory:
> WEIGHTS EXPRESS PREFERENCE. ENVELOPES EXPRESS PERMISSION. A weight of 0 is
> "please do not use this unit", and it is honoured while any other unit has
> headroom - but it is NOT a constraint.
`_fill()` runs a deliberate **last-resort pass** over the zero-weight units when
the preferred ones saturate, so that a preference can never manufacture a
standing error at the meter. A pack at its own cut-out that is only *weighted*
to zero is therefore still commanded to discharge the moment its sibling fills
up. So this branch ships both:
| | question | mechanism |
|---|---|---|
| `packshare.envelope()` | MAY this pack be asked, at all, in this direction? | a `pack` UNIT claim at `P_SAFETY`, `hi = 0` at the cut-out, `lo = 0` at 100 % |
| `packshare.weights()` | GIVEN that both may, which should carry more? | energy headroom in kWh, handed to `resolve()` |
## 2. ⚠️ What the weights CANNOT do
ARCH-01's convex-combination argument - the gain at the meter is
`sum(a_i * g_i)`, so it lies in `[min g_i, max g_i]` for **any** split -
guarantees that a bad split cannot **destabilise** the site. It says nothing
about whether the site can **regulate**. A unit at its energy limit has
`g_i = 0`; the combination is still inside the interval and the load it was
asked to carry simply does not move.
Measured, `test_packshare.py` part 8, two units rated 2000 W each, B sitting on
its own floor and therefore answering 0 W to any discharge command. The plant is
modelled in that file (`lag_s = 0`, obeys within one cycle, bounded by its
rating) and the loop is the real `compute()`:
| load | arm | site target | shares | grid | unmet |
|---|---|---|---|---|---|
| 1500 W | shipped | +3000 W | A +1500, B +1500 | 0 W | 0 W |
| 1500 W | weights | +1500 W | A +1500, B +0 | 0 W | 0 W |
| 1500 W | envelope | +1500 W | A +1500, B +0 | 0 W | 0 W |
| 3000 W | shipped | +4000 W | A +2000, B +2000 | +1000 W | 0 W |
| 3000 W | weights | +4000 W | A +2000, B +2000 | +1000 W | 0 W |
| 3000 W | envelope | +4000 W | A +2000, B **+0** | +1000 W | **+2000 W** |
Three things are worth reading off that table, and the second and third are the
uncomfortable ones:
1. At a load the healthy pack can cover, the weights alone deliver the whole
improvement. The shipped arm reaches the same meter reading only by winding
the site target to **twice the load** and standing a +1500 W command on a
battery that answers nothing, permanently saturation-frozen. That is not a
working site, it is a site with no headroom left for the next load step.
2. At a load it cannot cover, **the weights stop working entirely**. The
weighted arm and the shipped arm command the identical +2000 W into the empty
pack, because `_fill()`'s last-resort pass hands the remainder to the
zero-weighted unit. Same shares, same watts, same error.
3. **And the envelope does not rescue the delivery either - it names the
shortfall.** Same 2000 W delivered, same 1000 W standing at the meter. What
changes is that the empty pack is commanded 0 W instead of 2000 W, and 2000 W
of site target is *reported* as unplaceable instead of appearing to have been
placed.
> **Weights are a comfort choice for STABILITY and NOT for DELIVERY.** Nothing in
> this add-on shifts a unit's load to its sibling once the sibling is at its
> rating, and weighting a failing unit down is not a remedy for it.
## 2b. ⚠️ The card's own premise is only half true
The card opens with *"a unit that stops delivering its share (empty, full,
curtailed, wedged) parks the site with a standing grid error and no alarm."*
After this branch: the **ask** stops, and while the sibling has headroom the site
regulates to zero error instead of winding to twice the load. The **standing grid
error does not stop** once the sibling is at its rating - §2's table measures
1000 W standing in all three arms - and there is **still no alarm** for it, only
a report. SAFETY-42 will not alarm on a pack at its own floor; that is one of its
acceptance criteria and its evidence is that the benign and the wedged case are
indistinguishable in the power domain.
So the two cards together mean: an empty pack limiting the site is now REPORTED
(`unmet_w`, an action-log line) and still, deliberately, NOT ALARMED. Whether it
should be alarmed is a decision - and the alarm it would need is about a site's
stored ENERGY, not about an inverter's delivery, so it is not this card's and not
SAFETY-42's. Recorded rather than quietly closed against a premise this card only
half meets.
## 3. Which floor, and which ceiling - the two places this could have become policy
**The floor is `bms_soc_floor` alone, never `peakguard.pack_floor_pct()`.** That
function's conjunction with `peak_soc_floor` is right for the peak guard and
wrong here: SAFETY-25 decided (2026-09-02, Option A) that `peak_soc_floor` bounds
the peak guard **only**, ordinary self-consumption discharges straight past it,
and closing an envelope at it would turn an operator preference into a hard stop
on the grid-following loop - the memo's **deferred Option B**, built by accident.
`delivery.py`'s `account()` made the same choice one step out, for the same
reason. Graded: a pack at 15 % with a 10 % cut-out is not closed, though a 20 %
EMS floor would have closed it.
**The ceiling is 100 %, and the coarseness is the honest answer.** There is no
per-pack charge ceiling anywhere in this add-on - `delivery.py` says so at length
and calls it a card, and it is why SAFETY-42 is armed on discharge shares only.
The only other number available is `arbitrage_soc_ceiling`, which is one
site-wide **trade policy**; filing it as a `P_SAFETY` envelope on the loop would
be the mistake above in the charge direction. So the envelope closes only where
the ask is physically impossible, and everything between is left to the weights -
which is the right instrument for a graded preference and is honest about being
only a preference.
## 4. N=1, and the tripwire this had to argue past
`actuator_for()` routes **every** source to the site at one inverter, so a `pack`
interval filed there would bound the SITE TARGET rather than a share. `main.py`
therefore does not file it at all below a roster of two - the same guard, for the
same reason, that SAFETY-30's `sign_site` carries. AC 4 ("at N=1 allocation is
byte-identical") is that `if`.
`test_peakguard.py` part 10f pins the claim-source set against `main.py`'s own
AST precisely so that a state-of-charge-conditioned claim cannot arrive quietly.
`pack` is state-of-charge-conditioned, so the argument is written at that set
rather than the count edited: the number is not an option, the claim is
unit-scoped so it cannot bound the site target, it is not filed at N=1, and part
10f's own note names this as the revisit trigger - *"under ALLOC-01 the reserve
becomes a PER-INVERTER INTERVAL AT THE ALLOCATOR rather than a ninth claim
here"*. Stage 1 is how an interval reaches the allocator and stage 1's input is
claims, so a unit-scoped claim is the shape that sentence asks for.
**What N=1 still does not get, said plainly:** nothing stops the loop discharging
into the BMS cut-out at one inverter. That is unchanged, it is SAFETY-25's
deferred option, and the BMS is what stops it.
## 5. SAFETY-42 - the same hazard from the opposite side
The seam is **the state of charge** - and they overlap in one direction, which
is what the rest of this section is about:
* **OPT-09 stops the site ASKING** a pack whose own SoC says it cannot deliver.
* **SAFETY-42 alarms** when a pack that said it could does not.
A wedged unit reads a healthy SoC, so **no envelope closes** - that half is
absolute, and it is why this card cannot stop the ask on a wedged box. A pack at
its floor is `account()`'s explained case, so SAFETY-42 stays silent - and after
this card that ask does not arrive in the first place, which removes the benign
arm from the detector's input rather than teaching it a new discriminator.
⚠️ **BUT THE WEIGHT DOES MOVE, AND IT NARROWS SAFETY-42's DETECTION WINDOW. THIS
IS A DETECTION REGRESSION AT N=2 AND IT IS NOT FIXED HERE.** An earlier draft of
this section said "no envelope closes and no weight moves - OPT-09 cannot see it
at all". The second clause was **false**, and it was load-bearing for the claim
that the two cards do not overlap. A weight is a function of the pack's ENERGY
HEADROOM, not of what the pack delivers, so a wedged unit's weight moves whenever
its headroom differs from its sibling's - which is the ordinary case this card
exists to exploit. And `delivery.delinquent()` (`app/delivery.py:484`)
names a unit only while its `short_by()` gap exceeds `min_w =
Tuning.saturation_w` - the comparison is `app/delivery.py:531`, and it is
**500 W in absolute watts**. Shrinking a unit's share shrinks its gap. Shrink the
share far enough and the gap drops below 500 W while the unit is still delivering
nothing, and the alarm stops firing.
Measured on the closed loop - real `compute()`, real `plan()`, real
`delinquent()`, modelled plant, B wedged at 15 % against its own 10 % floor so
nothing closes and `account()` explains nothing, i.e. a SAFETY-42 **true
positive** by that card's own definition:
load 1500 W equal weights (shipped) named on 199/200 cycles
shares {a:1500, b:1500} grid +0 W named=['inverter-b']
load 1500 W OPT-09 weights named on 0/200 cycles
shares {a:1505, b: 125} grid -5 W named=(nobody)
⚠️ That plant is modelled in `test_packshare.py`, and **inverter B does not
exist** (expected ~2026-09-12): it is two copies of A driven with different
numbers, and B's 4600 W / 20.48 kWh / 10 % floor are from the datasheet and the
serial. The claim is about the arithmetic of the split and the threshold, which
needs no hardware, and not about a GW5000S-BP.
At a load the healthy pack can cover - the regime where nothing else tells the
operator anything, `unmet_w` is 0, the meter is satisfied and no action-log line
fires - a wedged inverter goes from named on essentially every cycle to **never
named**. The suppression window widens from `site target < 2 * min_w` = 1000 W to
`site target < min_w * (w_A + w_B) / w_B`, which on that fixture is **6500 W** of
a 9600 W site; above it - once the healthy pack is at its own rating and
`_fill()`'s last-resort pass hands the wedged unit a big share again - the alarm
returns. `test_packshare.py` part 8b grades all of it and **pins the current,
unflattering behaviour**, so that the day it changes a named check moves.
So the seam, stated accurately: **OPT-09 stops the ask AND narrows SAFETY-42's
detection window for a low-headroom unit.** The two cards do not merely meet from
opposite sides; this one takes something away from the other one. Closing the gap
means making `delinquent()` relative to the ask rather than absolute, which is
SAFETY-42's code and a design change - it is filed as its own card, deliberately
not done here, and this paragraph is its input. Until then this is a **disclosed
residual**, in the same voice as SAFETY-13's "2 of 272" and SAFETY-42's own "the
discriminator does not exist": at two inverters, a wedged unit with materially
less energy headroom than its sibling can go unreported at ordinary house loads.
⚠️ **And OPT-09 supplies the mechanism SAFETY-42 said was missing, without
connecting it.** That module's rejection of re-allocation rests on *"the only
re-allocation this add-on can express is ALL OR NOTHING [...] a partial
re-allocation is what would make acting safe, and the allocator has no way to
express it today"*. Passing weights **is** that expression. Wiring delinquency
into them is deliberately **not** done here: it would be acting on the alarm,
which SAFETY-42 refused with rig evidence (a unit derated to 50 % is 400 W worse
dropped than kept, and no instrument this add-on has can tell it from a wedged
one), and - see §2 - a weight cannot stop a unit being commanded anyway. That is
a card, and this paragraph is its input.
## 6. Per-pack arbitrage sizing, and the half that is deliberately not moved
`arbitrage.decide()` was handed `site_max_w` on **both** sides, so a two-pack
site would buy at the sum of the ratings whatever either pack's state of charge
was. It is now sized to the packs whose own SoC permits that direction
(`Controller.trade_power_w()`), using **arbitrage's own** bounds rather than the
BMS cut-out - sizing a trade is the trade's business; permitting a command is the
pack's.
Two honest limits:
* **The sell side is a no-op on every roster today.** `decide()` is handed
`pack_floor_soc` - the emptiest pack - so a sell is refused outright whenever
*any* pack is at or under the floor, i.e. in exactly the states where the sum
could be smaller than the site rating. The arithmetic is graded directly
(`test_packshare.py` part 9); it becomes reachable the day that gate is
per-pack.
* **Moving that gate is not this card's.** Sizing a sell off the *fullest* pack
would let the trade proceed while the emptiest pack was below
`arbitrage_soc_floor`, and the only per-pack instrument that could keep it out
of that pack is the weights - which are a preference, and `_fill()` will hand
it watts anyway. Doing it safely needs an envelope that depends on WHICH CLAIM
WON the tick, which the arbiter's partition does not express. §2 is why that is
a real objection and not a hedge.
`arbitrage.decide()` also now refuses a **0 W sizing** by name (`IDLE_NO_SIZE`),
because a `Claim.set(..., 0.0)` at `P_ARBITRAGE` is a park order that outranks
the loop - the failure the note on `claim()` is already written against. The
sizing can never be zero on a tick that trades today; that is a coincidence of
the existing gate, and this makes it structural instead.
## 7. The fixture, which is the hard part
Two packs that differ in only ONE of SoC and capacity cannot separate a
SoC-aware weighting from a capacity-aware one; two identical packs cannot
separate ANY weighting from any other. `test_packshare.py` part 1 grades the
fixture itself before anything is asserted with it - four candidate schemes
(equal, power rating, SoC only, energy), four distinct splits of the same
1000 W:
equal A +500, B +500
power A +521, B +479
soc only A +125, B +875
energy A +97, B +903
and the counterfactuals: on two identical packs all four collapse to one answer;
at the same SoC, `soc only` collapses onto `equal`; at the same capacity,
`energy` collapses onto `soc only`.
## 8. Provenance of every number
* A: **5000 W, 15.36 kWh, 10 % floor** - measured (GW5000S-BP, register 0x0560).
* B: **4600 W, 20.48 kWh, 10 % floor** - **FROM DATASHEET AND SERIAL**
(`goodwe/NOTES.md` §1.1b, GW5048D-ES `55048ESU22AW0992`). ⚠️ **Inverter B does
not exist** (expected ~2026-09-12).
* Every two-unit run in `test_packshare.py` is arithmetic over intervals and
weights, or a plant modelled in that file. `sim/plantsim.py:216`'s `INVERTER_B`
is **inverter A copied** with `measured=False`, so any two-inverter simulation
result anywhere in this project is **two copies of A**.
* No rig was taken, no hardware was touched, and nothing here is evidence about
a second GoodWe inverter.
## 9. Config
`capacity_kwh` joins the `inverters` roster as an **optional** per-entry key
(`float(0.1,200)?`) - the opposite choice to SAFETY-32's required
`bms_soc_floor`, and for that card's own reason: a missing cut-out would have to
be *defaulted*, and one default for two batteries protects the shallower pack
with the deeper pack's number, whereas a missing capacity has an honest answer -
no opinion about the split, every unit weighs 1.0, which is exactly what shipped.
It is **all or nothing across the roster** and rule 9 refuses a partial one: a
pack measured in kWh beside a sibling weighing a dimensionless 1.0 is not a
comparison, `weights()` answers "no opinion" for the whole roster in that case,
and a key that silently changes nothing is worse than one that refuses to load.
There is deliberately **no flat `capacity_kwh`**: at one inverter there is no
split to weight, so it would be an option an operator can set and nothing reads.