OPT-09: the weights DO move on a wedged unit, and that narrows SAFETY-42
B1, the blocking review finding. §5 of the decision said:

    "A wedged unit reads a healthy SoC, so no envelope closes and no weight
     moves - OPT-09 cannot see it at all."

The first clause is true and is about the ENVELOPE. The second clause is
FALSE, and it was load-bearing for the claim that OPT-09 and SAFETY-42 meet
without overlapping. A weight is a function of a pack's ENERGY HEADROOM, not
of what the pack delivers, so a wedged unit's weight moves whenever its
headroom differs from its sibling's - the ordinary case this card exists to
exploit. And delivery.delinquent() (app/delivery.py:484, threshold at :531)
names a unit only while its short_by() gap exceeds min_w = Tuning.saturation_w
= 500 W in ABSOLUTE WATTS. Shrinking the share shrinks the gap below the
threshold, and the alarm stops firing on a unit still delivering nothing.

So the seam, stated accurately: OPT-09 stops the ask AND narrows SAFETY-42's
detection window for a low-headroom unit. That is a DETECTION REGRESSION at
N=2. It is disclosed here, not fixed: making delinquent() relative to the ask
rather than absolute is SAFETY-42's code and a design change, filed as its own
card.

1. THE CORRECTION, in the three places that carried the claim

   * DECISIONS/OPT-09-soc-aware-weights.md §5 - rewritten. States the seam
     accurately, quotes the sentence it is replacing, carries the measured
     rows and the window arithmetic, and names the residual in the same voice
     as SAFETY-13's "2 of 272" and SAFETY-42's "the discriminator does not
     exist". Also drops "they meet and do not overlap" from the opening.
   * app/packshare.py - a new section in the module docstring, immediately
     after "weights are a comfort choice for stability and not for delivery",
     which is where the over-read starts.
   * CHANGELOG.md - a new paragraph in the SAFETY-42 entry, ending on the
     operator-facing sentence: a wedged inverter with less energy headroom
     than its sibling can now go unreported at ordinary house loads.

   test_packshare.py part 8's closing check and its "what this file cannot
   see" list repeated the same false clause; both now say the ENVELOPE cannot
   reach a wedged unit and point at part 8b for what the WEIGHTS do to it.

2. THE GRADED CHECK - test_packshare.py part 8b, 6 named checks

   The reviewer's probe, reproduced: real compute(), real plan(), real
   packshare.weights(), real delivery.account(), real delivery.delinquent();
   the only model is the plant (A obeys within one cycle inside its rating,
   B accepts its share and delivers 0 W). Unit B is WEDGED at 15 % against
   its own 10 % floor, so envelope() does not close and account() explains
   nothing - a SAFETY-42 true positive by that card's own definition, which
   a PRECONDITION check asserts before anything is concluded from it.

       load 1500 W, B wedged at 15 %, equal weights  named on 199/200 cycles,
         site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
       load 1500 W, B wedged at 15 %, OPT-09 weights named on   0/200 cycles,
         site target +1630 W, shares a+1505, b+125,  grid -5 W, named=(nobody)
       load 6000 W, B wedged at 15 %, equal weights  named on 199/200 cycles
       load 6000 W, B wedged at 15 %, OPT-09 weights named on 195/200 cycles

       suppression window: equal weights, site target < 1000 W; OPT-09
       weights, site target < 6500 W of a 9600 W site

   THE CHECKS ASSERT THE CURRENT, UNFLATTERING BEHAVIOUR ON PURPOSE - that
   the weighted arm names NOBODY where the equal arm names the wedged unit.
   A check asserting the alarm still fires would fail, and papering over it
   would be worse than the original defect. The 6000 W row is there so the
   part is not pinning "the weighted arm never names anybody": past the
   healthy pack's own rating, _fill()'s last-resort pass hands the wedged
   unit 3000 W and both arms name it. The window is real and it has an edge.

   MUTATION - packshare.weights() keeps its shape and forces every weight to
   1.0 (M11 in part 11's table, which now has 11 rows). RUN on a purged tree
   with python3 -B, not reasoned about:

       load 1500 W, B wedged at 15 %, equal weights  named on 199/200 cycles,
         site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
       load 1500 W, B wedged at 15 %, OPT-09 weights named on 199/200 cycles,
         site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
       load 6000 W, B wedged at 15 %, OPT-09 weights named on 199/200 cycles,
         site target +4000 W, shares a+2000, b+2000, grid +4000 W, named=[b]
       suppression window: equal weights < 1000 W; OPT-09 weights < 1000 W

     FAIL  AND WITH OPT-09's WEIGHTS IT IS NAMED ON NONE OF THE 200 [...]
     FAIL  ...and the arithmetic behind it, stated as a window [...]
     FAIL  AND IT IS NOT THAT THE WEIGHTED ARM NEVER NAMES ANYBODY [...]

   test_packshare.py exits 1. Restored: exits 0.

3. THREE PROC-01 PROSE DEFECTS

   * DECISIONS/OPT-09-soc-aware-weights.md:3 said "Base: release/1.0 @
     464d398". The branch was rebased; git merge-base HEAD 3368231 is
     3368231. Corrected, and it says why the old number was there.
   * Same file:13 cited main.py:2272 for "resolution = resolve(...)".
     git show 3368231:goodwe_controller/app/main.py | grep -n says 2422.
     Corrected. The sibling citation arbiter.py:535 is right and is left.
   * DOCS.md:174 said "Since 0.7.x the split is driven by two separate
     things", which tells an operator the fix already shipped. config.yaml
     is 0.8.0 and the live install is 0.7.0, where the split is 50/50 - this
     card's own premise. Now "from 0.8.0 onwards", with an explicit warning
     that 0.7.0 and earlier are a fixed 50/50.

NOT TOUCHED, deliberately: delinquent()'s absolute threshold (SAFETY-42's
code, its own card), and app/main.py:2699's double-logged scope refusal (N4,
filed separately).

INVERTER B DOES NOT EXIST (expected ~2026-09-12). Every two-unit figure above
is TWO COPIES OF A through a plant modelled in test_packshare.py; B's 4600 W /
20.48 kWh / 10 % floor are from the datasheet and the serial. Nothing here was
measured on hardware, and the added disclaimers say so in each place.

Verified with the real harness per .gitea/workflows/checks.yml
(goodwe-addon-checks:1): COLLECTED 24 files, ALLGREEN. Harness positive
control run first - test_validate.py deliberately broken, harness reported
"FAILED: test_validate.py" and exited 1; restored.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-06 22:55:20 +02:00

17 KiB

OPT-09 - the weights parameter, and what it is honestly for

Status: implemented. Branch: OPT-09. Base: release/1.0 @ 3368231 (git merge-base HEAD 3368231; the branch was rebased and this line used to name the pre-rebase base, 464d398).

0. What was actually wrong

allocator.plan() has taken a weights argument since ALLOC-01, _fill() consumes it in two passes, and nothing had ever passed one. Confirmed on the base commit:

arbiter.py:535   def resolve(claims, *, units=None, weights=None, live=None, ...)
main.py:2422     resolve(claims, units=self.units, live=self.live_units(), ...)

So weights was None on every tick of every install, plan() turned that into 1.0 per unit, and the site target was split 50/50 regardless of what either pack could do. The card was filed as "per-pack arbitrage sizing"; the architect pass found the sharper content, and it is the sharper content that this branch is mostly about.

1. Two instruments, and they are not interchangeable

allocator.py states the rule this card is built on, and it is mechanical rather than advisory:

WEIGHTS EXPRESS PREFERENCE. ENVELOPES EXPRESS PERMISSION. A weight of 0 is "please do not use this unit", and it is honoured while any other unit has headroom - but it is NOT a constraint.

_fill() runs a deliberate last-resort pass over the zero-weight units when the preferred ones saturate, so that a preference can never manufacture a standing error at the meter. A pack at its own cut-out that is only weighted to zero is therefore still commanded to discharge the moment its sibling fills up. So this branch ships both:

question mechanism
packshare.envelope() MAY this pack be asked, at all, in this direction? a pack UNIT claim at P_SAFETY, hi = 0 at the cut-out, lo = 0 at 100 %
packshare.weights() GIVEN that both may, which should carry more? energy headroom in kWh, handed to resolve()

2. ⚠️ What the weights CANNOT do

ARCH-01's convex-combination argument - the gain at the meter is sum(a_i * g_i), so it lies in [min g_i, max g_i] for any split - guarantees that a bad split cannot destabilise the site. It says nothing about whether the site can regulate. A unit at its energy limit has g_i = 0; the combination is still inside the interval and the load it was asked to carry simply does not move.

Measured, test_packshare.py part 8, two units rated 2000 W each, B sitting on its own floor and therefore answering 0 W to any discharge command. The plant is modelled in that file (lag_s = 0, obeys within one cycle, bounded by its rating) and the loop is the real compute():

load arm site target shares grid unmet
1500 W shipped +3000 W A +1500, B +1500 0 W 0 W
1500 W weights +1500 W A +1500, B +0 0 W 0 W
1500 W envelope +1500 W A +1500, B +0 0 W 0 W
3000 W shipped +4000 W A +2000, B +2000 +1000 W 0 W
3000 W weights +4000 W A +2000, B +2000 +1000 W 0 W
3000 W envelope +4000 W A +2000, B +0 +1000 W +2000 W

Three things are worth reading off that table, and the second and third are the uncomfortable ones:

  1. At a load the healthy pack can cover, the weights alone deliver the whole improvement. The shipped arm reaches the same meter reading only by winding the site target to twice the load and standing a +1500 W command on a battery that answers nothing, permanently saturation-frozen. That is not a working site, it is a site with no headroom left for the next load step.
  2. At a load it cannot cover, the weights stop working entirely. The weighted arm and the shipped arm command the identical +2000 W into the empty pack, because _fill()'s last-resort pass hands the remainder to the zero-weighted unit. Same shares, same watts, same error.
  3. And the envelope does not rescue the delivery either - it names the shortfall. Same 2000 W delivered, same 1000 W standing at the meter. What changes is that the empty pack is commanded 0 W instead of 2000 W, and 2000 W of site target is reported as unplaceable instead of appearing to have been placed.

Weights are a comfort choice for STABILITY and NOT for DELIVERY. Nothing in this add-on shifts a unit's load to its sibling once the sibling is at its rating, and weighting a failing unit down is not a remedy for it.

2b. ⚠️ The card's own premise is only half true

The card opens with "a unit that stops delivering its share (empty, full, curtailed, wedged) parks the site with a standing grid error and no alarm." After this branch: the ask stops, and while the sibling has headroom the site regulates to zero error instead of winding to twice the load. The standing grid error does not stop once the sibling is at its rating - §2's table measures 1000 W standing in all three arms - and there is still no alarm for it, only a report. SAFETY-42 will not alarm on a pack at its own floor; that is one of its acceptance criteria and its evidence is that the benign and the wedged case are indistinguishable in the power domain.

So the two cards together mean: an empty pack limiting the site is now REPORTED (unmet_w, an action-log line) and still, deliberately, NOT ALARMED. Whether it should be alarmed is a decision - and the alarm it would need is about a site's stored ENERGY, not about an inverter's delivery, so it is not this card's and not SAFETY-42's. Recorded rather than quietly closed against a premise this card only half meets.

3. Which floor, and which ceiling - the two places this could have become policy

The floor is bms_soc_floor alone, never peakguard.pack_floor_pct(). That function's conjunction with peak_soc_floor is right for the peak guard and wrong here: SAFETY-25 decided (2026-09-02, Option A) that peak_soc_floor bounds the peak guard only, ordinary self-consumption discharges straight past it, and closing an envelope at it would turn an operator preference into a hard stop on the grid-following loop - the memo's deferred Option B, built by accident. delivery.py's account() made the same choice one step out, for the same reason. Graded: a pack at 15 % with a 10 % cut-out is not closed, though a 20 % EMS floor would have closed it.

The ceiling is 100 %, and the coarseness is the honest answer. There is no per-pack charge ceiling anywhere in this add-on - delivery.py says so at length and calls it a card, and it is why SAFETY-42 is armed on discharge shares only. The only other number available is arbitrage_soc_ceiling, which is one site-wide trade policy; filing it as a P_SAFETY envelope on the loop would be the mistake above in the charge direction. So the envelope closes only where the ask is physically impossible, and everything between is left to the weights - which is the right instrument for a graded preference and is honest about being only a preference.

4. N=1, and the tripwire this had to argue past

actuator_for() routes every source to the site at one inverter, so a pack interval filed there would bound the SITE TARGET rather than a share. main.py therefore does not file it at all below a roster of two - the same guard, for the same reason, that SAFETY-30's sign_site carries. AC 4 ("at N=1 allocation is byte-identical") is that if.

test_peakguard.py part 10f pins the claim-source set against main.py's own AST precisely so that a state-of-charge-conditioned claim cannot arrive quietly. pack is state-of-charge-conditioned, so the argument is written at that set rather than the count edited: the number is not an option, the claim is unit-scoped so it cannot bound the site target, it is not filed at N=1, and part 10f's own note names this as the revisit trigger - "under ALLOC-01 the reserve becomes a PER-INVERTER INTERVAL AT THE ALLOCATOR rather than a ninth claim here". Stage 1 is how an interval reaches the allocator and stage 1's input is claims, so a unit-scoped claim is the shape that sentence asks for.

What N=1 still does not get, said plainly: nothing stops the loop discharging into the BMS cut-out at one inverter. That is unchanged, it is SAFETY-25's deferred option, and the BMS is what stops it.

5. SAFETY-42 - the same hazard from the opposite side

The seam is the state of charge - and they overlap in one direction, which is what the rest of this section is about:

  • OPT-09 stops the site ASKING a pack whose own SoC says it cannot deliver.
  • SAFETY-42 alarms when a pack that said it could does not.

A wedged unit reads a healthy SoC, so no envelope closes - that half is absolute, and it is why this card cannot stop the ask on a wedged box. A pack at its floor is account()'s explained case, so SAFETY-42 stays silent - and after this card that ask does not arrive in the first place, which removes the benign arm from the detector's input rather than teaching it a new discriminator.

⚠️ BUT THE WEIGHT DOES MOVE, AND IT NARROWS SAFETY-42's DETECTION WINDOW. THIS IS A DETECTION REGRESSION AT N=2 AND IT IS NOT FIXED HERE. An earlier draft of this section said "no envelope closes and no weight moves - OPT-09 cannot see it at all". The second clause was false, and it was load-bearing for the claim that the two cards do not overlap. A weight is a function of the pack's ENERGY HEADROOM, not of what the pack delivers, so a wedged unit's weight moves whenever its headroom differs from its sibling's - which is the ordinary case this card exists to exploit. And delivery.delinquent() (app/delivery.py:484) names a unit only while its short_by() gap exceeds min_w = Tuning.saturation_w - the comparison is app/delivery.py:531, and it is 500 W in absolute watts. Shrinking a unit's share shrinks its gap. Shrink the share far enough and the gap drops below 500 W while the unit is still delivering nothing, and the alarm stops firing.

Measured on the closed loop - real compute(), real plan(), real delinquent(), modelled plant, B wedged at 15 % against its own 10 % floor so nothing closes and account() explains nothing, i.e. a SAFETY-42 true positive by that card's own definition:

load 1500 W  equal weights (shipped)  named on 199/200 cycles
             shares {a:1500, b:1500}  grid  +0 W  named=['inverter-b']
load 1500 W  OPT-09 weights           named on   0/200 cycles
             shares {a:1505, b: 125}  grid  -5 W  named=(nobody)

⚠️ That plant is modelled in test_packshare.py, and inverter B does not exist (expected ~2026-09-12): it is two copies of A driven with different numbers, and B's 4600 W / 20.48 kWh / 10 % floor are from the datasheet and the serial. The claim is about the arithmetic of the split and the threshold, which needs no hardware, and not about a GW5000S-BP.

At a load the healthy pack can cover - the regime where nothing else tells the operator anything, unmet_w is 0, the meter is satisfied and no action-log line fires - a wedged inverter goes from named on essentially every cycle to never named. The suppression window widens from site target < 2 * min_w = 1000 W to site target < min_w * (w_A + w_B) / w_B, which on that fixture is 6500 W of a 9600 W site; above it - once the healthy pack is at its own rating and _fill()'s last-resort pass hands the wedged unit a big share again - the alarm returns. test_packshare.py part 8b grades all of it and pins the current, unflattering behaviour, so that the day it changes a named check moves.

So the seam, stated accurately: OPT-09 stops the ask AND narrows SAFETY-42's detection window for a low-headroom unit. The two cards do not merely meet from opposite sides; this one takes something away from the other one. Closing the gap means making delinquent() relative to the ask rather than absolute, which is SAFETY-42's code and a design change - it is filed as its own card, deliberately not done here, and this paragraph is its input. Until then this is a disclosed residual, in the same voice as SAFETY-13's "2 of 272" and SAFETY-42's own "the discriminator does not exist": at two inverters, a wedged unit with materially less energy headroom than its sibling can go unreported at ordinary house loads.

⚠️ And OPT-09 supplies the mechanism SAFETY-42 said was missing, without connecting it. That module's rejection of re-allocation rests on "the only re-allocation this add-on can express is ALL OR NOTHING [...] a partial re-allocation is what would make acting safe, and the allocator has no way to express it today". Passing weights is that expression. Wiring delinquency into them is deliberately not done here: it would be acting on the alarm, which SAFETY-42 refused with rig evidence (a unit derated to 50 % is 400 W worse dropped than kept, and no instrument this add-on has can tell it from a wedged one), and - see §2 - a weight cannot stop a unit being commanded anyway. That is a card, and this paragraph is its input.

6. Per-pack arbitrage sizing, and the half that is deliberately not moved

arbitrage.decide() was handed site_max_w on both sides, so a two-pack site would buy at the sum of the ratings whatever either pack's state of charge was. It is now sized to the packs whose own SoC permits that direction (Controller.trade_power_w()), using arbitrage's own bounds rather than the BMS cut-out - sizing a trade is the trade's business; permitting a command is the pack's.

Two honest limits:

  • The sell side is a no-op on every roster today. decide() is handed pack_floor_soc - the emptiest pack - so a sell is refused outright whenever any pack is at or under the floor, i.e. in exactly the states where the sum could be smaller than the site rating. The arithmetic is graded directly (test_packshare.py part 9); it becomes reachable the day that gate is per-pack.
  • Moving that gate is not this card's. Sizing a sell off the fullest pack would let the trade proceed while the emptiest pack was below arbitrage_soc_floor, and the only per-pack instrument that could keep it out of that pack is the weights - which are a preference, and _fill() will hand it watts anyway. Doing it safely needs an envelope that depends on WHICH CLAIM WON the tick, which the arbiter's partition does not express. §2 is why that is a real objection and not a hedge.

arbitrage.decide() also now refuses a 0 W sizing by name (IDLE_NO_SIZE), because a Claim.set(..., 0.0) at P_ARBITRAGE is a park order that outranks the loop - the failure the note on claim() is already written against. The sizing can never be zero on a tick that trades today; that is a coincidence of the existing gate, and this makes it structural instead.

7. The fixture, which is the hard part

Two packs that differ in only ONE of SoC and capacity cannot separate a SoC-aware weighting from a capacity-aware one; two identical packs cannot separate ANY weighting from any other. test_packshare.py part 1 grades the fixture itself before anything is asserted with it - four candidate schemes (equal, power rating, SoC only, energy), four distinct splits of the same 1000 W:

equal     A +500, B +500
power     A +521, B +479
soc only  A +125, B +875
energy    A  +97, B +903

and the counterfactuals: on two identical packs all four collapse to one answer; at the same SoC, soc only collapses onto equal; at the same capacity, energy collapses onto soc only.

8. Provenance of every number

  • A: 5000 W, 15.36 kWh, 10 % floor - measured (GW5000S-BP, register 0x0560).
  • B: 4600 W, 20.48 kWh, 10 % floor - FROM DATASHEET AND SERIAL (goodwe/NOTES.md §1.1b, GW5048D-ES 55048ESU22AW0992). ⚠️ Inverter B does not exist (expected ~2026-09-12).
  • Every two-unit run in test_packshare.py is arithmetic over intervals and weights, or a plant modelled in that file. sim/plantsim.py:216's INVERTER_B is inverter A copied with measured=False, so any two-inverter simulation result anywhere in this project is two copies of A.
  • No rig was taken, no hardware was touched, and nothing here is evidence about a second GoodWe inverter.

9. Config

capacity_kwh joins the inverters roster as an optional per-entry key (float(0.1,200)?) - the opposite choice to SAFETY-32's required bms_soc_floor, and for that card's own reason: a missing cut-out would have to be defaulted, and one default for two batteries protects the shallower pack with the deeper pack's number, whereas a missing capacity has an honest answer - no opinion about the split, every unit weighs 1.0, which is exactly what shipped.

It is all or nothing across the roster and rule 9 refuses a partial one: a pack measured in kWh beside a sibling weighing a dimensionless 1.0 is not a comparison, weights() answers "no opinion" for the whole roster in that case, and a key that silently changes nothing is worse than one that refuses to load.

There is deliberately no flat capacity_kwh: at one inverter there is no split to weight, so it would be an option an operator can set and nothing reads.