DEV-02 made every per-device value per-instance - rating, SoC, watchdogs, heartbeat, store keys - so the code stopped assuming one inverter. The options schema did not. `build_roster()` returned a list of exactly one and said so in its own docstring, and there was no `inverters:` key for an operator to write, so the roster could only ever be a roster of one. THE SHAPE, AND WHY IT WAS MEASURED RATHER THAN CHOSEN config.yaml had no list-of-objects anywhere, and `static_profile` carries a whole tariff structure as a JSON string in a `str?` precisely because a nested schema was doubted. That is a question about somebody else's software, so it was answered by running it: `tools/supervisor_shape_probe.py` (committed) runs Supervisor 2026.08.0's OWN `AppOptions` validator and `SCHEMA_APP_CONFIG`, out of the release image, against this repository's config.yaml. 2026.08.0 is the version the live install reports. The full transcript and the argument are in DECISIONS/CFG-04-inverter-roster.md. It accepts the list, enforces per-entry types, refuses a missing `name` / `setpoint_entity` / `max_w` BY NAME, renders the option in the UI as a repeatable section, and drops the key with a warning under an older schema - so a downgrade is not the forward trap in reverse. ⚠️ AND THE `inverters: []` DEFAULT IS LOAD-BEARING, WHICH IS THE MEASUREMENT THAT MATTERED MOST. Supervisor answers `Missing option 'inverters' in root` for an options blob that has no such key - which every existing install's has, since the key did not exist when they were written. `App.options` is the shipped `options:` block deep-merged with the operator's stored one, so the empty default is the difference between an upgrade nobody notices and an add-on that cannot start with a schema pinned to the version that would fix it. That is docs/deploy-rollback.md §4's trap in the FORWARD direction, found before it was sprung. The merger was checked too: lists override rather than concatenate, so a non-empty default could not have grown a roster behind the operator's back. NOTHING IS INHERITED, WHICH IS DEV-02 RESTATED AS A CONFIG RULE `name`, `setpoint_entity` and `max_w` are required of every entry. An entry that omits `soc_entity` has no SoC sensor; it does not borrow the flat one. A three-line fallback would have rebuilt the sibling-grading defect DEV-02 spent a card removing, in YAML. Defaults still live in exactly one place (CFG-03): there is no per-entry default anywhere, because there is no optional per-entry number. A flat `setpoint_entity` left set beside a declared roster is refused rather than ignored - it names an actuator nothing will write. TWO PERMISSIVE READERS IN SHIPPED CODE, AND THREE MORE IN THE CHECKS validate.py rules 5 and 6 compared their thresholds against the FLAT `max_w`. At a roster of two 2000 W units with `max_w: 5000` left over from a single-inverter install, `sign_disagree_w: 3000` passed rule 5 while SAFETY-02's watchdog could fire on NEITHER unit - rule 5's own failure mode, reached through rule 5. They read `unit_caps()` now, which at one inverter is `[max_w]` exactly. main.py's `run_control()` re-ran the device-rating check behind `if self.o.get("setpoint_entity")` - the flat key, which a roster leaves blank - so on a two-inverter site no inverter's `max_w` was graded against the device it is written to, and the skip was silent. `validate_unit_ranges()` grades each unit against its own ESPHome and runs unconditionally. test_peakguard.py's `read_option()` and `_schema_bound()` and test_inverter.py's `read_schema_max()` matched a STRIPPED line and took the first hit, so the nested per-inverter `max_w:` began outranking the flat one - silently, and correctly, because the two bounds are the same int(100,5000) today. A reader that is right by coincidence is this project's named failure mode. All three are anchored at exactly two spaces now; the file's two halves disambiguate `peak_cap_w` instead of first-match, and an ambiguous key raises rather than picking one. test_tariff.py's copy of the idiom went with them. THE AUDIT IS A CHECK, NOT A PROMISE test_inverter.py part 11 finds every config.yaml-reading function in the suite - transitively, because two of the readers CFG-04 had to change never name the file - EXECUTES each against a synthetic two-inverter config.yaml whose per-inverter numbers differ from its flat ones, and fails if any answers with the per-inverter value. The table is not maintained by hand: the signature decides, so the eleventh reader is named on its first run. config.yaml declares `inverters:` BEFORE `max_w:` on purpose and part 11 asserts that ordering, so the trap stays baited. SAFETY-28's `actuator_writers()` needed no change - it was already a structural, case-folding census - but until now there was no configuration in which two writers on one actuator could be WRITTEN DOWN. There is now, and it is refused. VERIFIED BY BREAKING IT Ten mutations run through tools/mutation_run.sh and observed red, listed in test_inverter.py part 12 with the check that bites each. Two survived the first run and the CHECKS were changed, not the table: the inheritance check had blank flat keys, so "inherited" and "not inherited" were the same empty string; and the `run_control()` check asserted a SOURCE LINE was present, which re-indenting it does not remove. Both are recorded in MUTATION.md's "the check's data cannot reach the failure it names" section, which now carries two more habits: assert on behaviour rather than on source text, and give a check whose failure mode is a hang a deadline. 19/19 green in the goodwe-addon-ci image. The one-inverter path is byte- identical: the whole existing suite runs unmodified against it. Version bumped to 0.6.0 - the Supervisor keys the built image by `version:`, so a schema change without a bump is a schema nobody reads. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
GoodWe RS485 Controller — Home Assistant add-on repository
Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.
repository.yaml add-on repository metadata
goodwe_controller/ the add-on
config.yaml manifest + options schema (the per-site config form)
app/ the controller
control.py the control law — pure functions, no I/O
maintenance.py the monthly cycle state machine
hass.py Supervisor/Core API access
store.py persistent state in /data
mqtt.py optional status entities
web.py ingress UI
main.py orchestration, heartbeat, failsafe behaviour
test_control.py runnable checks — no framework needed
test_maintenance.py runnable checks — walks a full cycle in fake time
DOCS.md the add-on's documentation tab
MUTATION.md how to run a mutation so the result means something
tools/mutation_run.sh the mutation harness - purges bytecode, then grades
firmware/goodwe-master.yaml ESPHome config for the T-CAN485
estop/rs485_log.py optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf the guide techs carry (10pp, A4)
docs/build_guide.py its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md how to edit and rebuild the guide
Picking this up after a break? Read HANDOVER.md first — current state,
what is known broken, and what to do next.
Install
Settings → Add-ons → Add-on store → ⋮ → Repositories → add
https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install GoodWe RS485 Controller.
⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
goodwe_controller/ into the machine's /addons/ folder, then
ha store reload — it appears as a Local add-on.
⚠️ Bump version: in goodwe_controller/config.yaml for every change.
Supervisor keys the built image by that version, so without a bump it silently
reuses the old image and your fix appears not to work — on your bench and on
every client's machine.
Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.
Read this first
The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.
Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:
- ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
- Wind-down before firmware updates — 0 W written before the update starts.
- RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.
Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md
§10 signed.
Development
The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:
cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py
Both must pass before shipping any change. To prove a check bites - the way
almost every claim in this repository was established - mutate the module and
run tools/mutation_run.sh, which clears __pycache__ first. It is not
optional: a same-size edit reverted inside one second leaves CPython reusing the
old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md
has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre —
each assertion corresponds to a rule whose absence produced an observed failure
on real hardware, and the comments in control.py say which.
Compatibility
Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:
| tag | platform | verdict |
|---|---|---|
ESU EMU ESA BPS BPU EMJ IJL |
105 — ES/EM/BP, AA55-era meter bus | supported |
SPB SPN |
745 — SBP G2 (GW…-SBP-20) |
no |
ESN ESC |
745 — ES G2 (GW…-ES-20) |
no |
ETU EHU BTU … |
205/745/753 — ET/EH/BT hybrids | no |
SDT DST MSU NSU … |
PV-only inverters — no battery to control | no |
A "-20" or "G2" suffix means a different platform with a different meter
protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which
is also what Home Assistant's own integration uses to pick a protocol.
- GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
- The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.