The owner reported the OUTPUT_CLAMP notification as a persistent annoyance on the live install. It re-asserted every 30 s, all day. ⚠️ THIS IS A REGIME CHANGE, NOT A CHANGE OF MIND ABOUT THE ALARM. 30 s was chosen when a loop-side engagement was rare - clamp.py's own note records "60 cycles of the §10.3 runaway produce 2 loop-side engagements". The live install produced 48 IN 25 MINUTES of ordinary operation, because `max_w` is 5000 W where the loop's tuning was derived at a 1500 W clamp (SAFETY-39). The integrator therefore reaches its bound constantly and the alarm narrated it every 30 s. An alarm that speaks that often about the normal case is how an operator learns to ignore the one that matters, which is the exact failure clamp.py's docstring is written against. ⚠️ 150 s IS THE REQUIREMENT'S OWN EDGE WITH ONE STEP OF MARGIN, not a comfort choice. test_clamp.py part 2 pins the cadence in WALL-CLOCK terms rather than against this constant: a loop pinned on the rail must speak at least MIN_PER_QUARTER = 5 times inside the 900 s quarter that bills the capacity tariff. That caps the constant at 900/5 = 180 s. Measured: 180 s -> 5 alarms per quarter (exactly the required 5, no margin) 150 s -> 6 alarms per quarter 300 s -> 3, and the floor check goes RED 180 s would sit on the boundary, so any later change to the firing logic would tip it red for a reason unrelated to that change. The FLOOR is the thing that must not move, and it does not. ⚠️ WHAT THIS DOES NOT DO. It changes how often the alarm repeats. It does NOT make the alarm correct: the message still calls the integrator bound a BUG SIGNAL and still pairs a request from one moment with a `self.target` read at another. That is SAFETY-40. And it does not stop the loop railing in the first place; that is SAFETY-39. This is a stop-gap and says so at the line. Nothing was suppressed: every engagement is still counted, the action-log row is unchanged, and the §10.3 runaway still raises the alarm - an earlier attempt at this that split the alarm so only `clamped` notified was REVERTED because test_clamp.py:398 proved it would have disabled runaway detection entirely (a runaway presents as `i_clamped`, and control.py:78-81 says `clamped` is unreachable on a default install). Full suite: 20 passed, 0 failed. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
GoodWe RS485 Controller — Home Assistant add-on repository
Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.
repository.yaml add-on repository metadata
goodwe_controller/ the add-on
config.yaml manifest + options schema (the per-site config form)
app/ the controller
control.py the control law — pure functions, no I/O
maintenance.py the monthly cycle state machine
hass.py Supervisor/Core API access
store.py persistent state in /data
mqtt.py optional status entities
web.py ingress UI
main.py orchestration, heartbeat, failsafe behaviour
test_control.py runnable checks — no framework needed
test_maintenance.py runnable checks — walks a full cycle in fake time
DOCS.md the add-on's documentation tab
MUTATION.md how to run a mutation so the result means something
tools/mutation_run.sh the mutation harness - purges bytecode, then grades
firmware/goodwe-master.yaml ESPHome config for the T-CAN485
estop/rs485_log.py optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf the guide techs carry (10pp, A4)
docs/build_guide.py its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md how to edit and rebuild the guide
Picking this up after a break? Read HANDOVER.md first — current state,
what is known broken, and what to do next.
Install
Settings → Add-ons → Add-on store → ⋮ → Repositories → add
https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install GoodWe RS485 Controller.
⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
goodwe_controller/ into the machine's /addons/ folder, then
ha store reload — it appears as a Local add-on.
⚠️ Bump version: in goodwe_controller/config.yaml for every change.
Supervisor keys the built image by that version, so without a bump it silently
reuses the old image and your fix appears not to work — on your bench and on
every client's machine.
Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.
Read this first
The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.
Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:
- ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
- Wind-down before firmware updates — 0 W written before the update starts.
- RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.
Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md
§10 signed.
Development
The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:
cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py
Both must pass before shipping any change. To prove a check bites - the way
almost every claim in this repository was established - mutate the module and
run tools/mutation_run.sh, which clears __pycache__ first. It is not
optional: a same-size edit reverted inside one second leaves CPython reusing the
old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md
has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre —
each assertion corresponds to a rule whose absence produced an observed failure
on real hardware, and the comments in control.py say which.
Compatibility
Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:
| tag | platform | verdict |
|---|---|---|
ESU EMU ESA BPS BPU EMJ IJL |
105 — ES/EM/BP, AA55-era meter bus | supported |
SPB SPN |
745 — SBP G2 (GW…-SBP-20) |
no |
ESN ESC |
745 — ES G2 (GW…-ES-20) |
no |
ETU EHU BTU … |
205/745/753 — ET/EH/BT hybrids | no |
SDT DST MSU NSU … |
PV-only inverters — no battery to control | no |
A "-20" or "G2" suffix means a different platform with a different meter
protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which
is also what Home Assistant's own integration uses to pick a protocol.
- GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
- The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.