glenn schrooyenandClaude Opus 5 06661c5e17
checks / unit (pull_request) Successful in 6m6s
PKG-07: bump 0.7.0 -> 0.8.0, because 0.7.0's own default is now a refused config
Six merges landed behind an unbumped 0.7.0 - CI-06, SAFETY-38, SAFETY-39,
SAFETY-37, SAFETY-13, SAFETY-42. PKG-06 recorded this exact failure YESTERDAY
(bbc903b, 2026-09-05 19:23): the Supervisor keys the built image by `version:`,
so `ha apps update` against an unchanged version is a silent no-op and the box
keeps running the old tree. Catching it by hand a second time is the argument
for the automated check PKG-06's follow-up still owes.

MINOR rather than patch, and the reason is sharper than a semantic change:
SAFETY-39's validator rule 10 refuses an explicit `slew_w` above
SLEW_RAIL_FRAC x the site rail - 555.6 W on a 5000 W rail - and 0.7.0's own
SHIPPED DEFAULT was `slew_w: 1000` under schema `int(50,5000)`. An install that
never touched the key is refused on 0.8.0. Refusal is SystemExit(78); the
add-on does not start.

⚠️ AN EARLIER DRAFT OF THIS COMMIT JUSTIFIED THE BUMP BY CLAIMING `slew_w: 0`
USED TO MEAN "no limit" AND NOW MEANS "follow the rail". THAT WAS FALSE AND IS
REMOVED. The schema was `int(50,5000)` from the repo's first commit through
0.7.0, so 0 was never a legal value and never meant anything; and the old
`control.py` had no zero case - at slew_w=0 it pinned the command to its
previous value, freezing it, which is the opposite of "no limit". The widening
to `int(0,5000)` is a NEW capability, not a changed meaning. The bump is right;
the story told for it was invented - PROC-01's defect appearing in the very
commit that complains about process.

⚠️ AND THEN A SECOND ONE, IN THE SAME COMMIT: the text said PKG-06 was "three
days ago" when the two commits are about a day apart (2026-09-05 19:23 ->
2026-09-06 20:03). Caught in round 2 and corrected. Two invented facts in one
documentation-only change is the measurement PROC-01 wants, not an anecdote:
both were plausible, neither was load-bearing, and both would have shipped.

⚠️ THE PRE-DEPLOY CHECK THIS IMPLIES IS NOT DONE AND CANNOT BE DONE FROM HERE.
Whether the LIVE options survive rule 10 depends on the live `slew_w`, and the
options blob is only reachable through the Supervisor API, which needs a token
this session does not have; the HA REST API does not expose it and no entity
carries it. On record `slew_w` was set to 400 during the SAFETY-39 interim fix,
and 400 is below 555.6 - but that is a written record, not a reading, and the
value has been hand-edited since. Read the options and check them BEFORE
`ha apps update`. Exit 78 also takes the ingress panel down, because the add-on
serving it is not running.

The contents table now carries each merge subject's WHOLE claim. Two rows had
been trimmed to their flattering halves - SAFETY-39's "`gain` is the constant
that is still wrong" and SAFETY-42's "the discriminator the card asked for does
not exist" - and both are restored.

Separately, `## Unreleased` was a lie twice over: two headings by that name, one
spanning ~3000 lines across three releases, one from the 0.4.x era, and every
word under both is shipped and running. Retitled, not re-sorted; the split is
PKG-08.

Reviewed twice. Round 1 REJECTED for an empty PR - built in a clone a concurrent
agent was using, and "pushed" reported from the command's echo rather than from
the remote ref - and for the fabricated slew_w story. Round 2 APPROVED with the
date as a non-blocking finding, fixed here.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-06 20:16:39 +02:00

856 lines
45 KiB
YAML

name: GoodWe RS485 Controller
version: "0.8.0"
slug: goodwe_controller
description: >-
Drives a GoodWe ES/BP battery inverter over RS485 by emulating its smart
meter, holding net grid exchange at zero and running a monthly battery
maintenance cycle.
url: https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
arch:
- aarch64
- amd64
- armv7
init: false
startup: application
boot: auto
# Needed to read the meter and to write the ESPHome setpoint number.
homeassistant_api: true
hassio_api: true
# Own diagnostics/operations UI inside HA. This is what a field tech and a
# remote supporter both look at, so it is not optional.
ingress: true
ingress_port: 8099
panel_icon: mdi:battery-sync
panel_title: GoodWe
# Optional: publish status entities by MQTT discovery. `want` rather than
# `need` - the add-on runs fine with no broker, it just publishes nothing.
services:
- mqtt:want
options:
# ==========================================================================
# HARDWARE - the inverter, its actuator and its own sensors
# ==========================================================================
setpoint_entity: ""
soc_entity: ""
batt_entity: ""
batt_invert: false
# ⚠️ EMPTY IS NOT "UNCONFIGURED", IT IS THE SINGLE-INVERTER CONFIGURATION, and
# it is what every install that upgrades into this version lands on. An empty
# list means THE SIX FLAT KEYS - `setpoint_entity`, `soc_entity`,
# `batt_entity`, `batt_invert`, `max_w` and `bms_soc_floor` - DESCRIBE THE
# ONE INVERTER: same entities, same rating, same behaviour, no operator
# action, which is the only migration story this key was allowed to have.
# `build_roster()` reads this and nothing else decides the shape.
#
# Declared, it REPLACES those six keys rather than extending them. Each entry
# names its own actuator, its own rating and its own sensors:
#
# inverters:
# - name: inverter-a
# setpoint_entity: number.goodwe_a_setpoint_w
# soc_entity: sensor.goodwe_a_soc
# batt_entity: sensor.goodwe_a_battery_power
# max_w: 5000
# bms_soc_floor: 10
# - name: inverter-b
# setpoint_entity: number.goodwe_b_setpoint_w
# soc_entity: sensor.goodwe_b_soc
# batt_entity: sensor.goodwe_b_battery_power
# max_w: 4600
# bms_soc_floor: 10
#
# ⚠️ THE 4600 IS INVERTER B'S DATASHEET FIGURE, NOT A MEASUREMENT AND NOT A
# PLACEHOLDER. SPIKE-04a (2026-09-04) identified B as a GoodWe GW5048D-ES,
# serial `55048ESU22AW0992`, whose datasheet gives Max. Charging / Discharging
# Power as 4600 W; nothing will be connected to its MPPTs, so the battery path
# is the ceiling and the 5000 VA AC nameplate is not. The 3000 W this example
# used to carry was a guess made before the unit was known. ⚠️ It is STILL not
# measured: the datasheet prints 4600 W under BATTERY INPUT DATA, so it may be
# DC, and `max_w` is graded against 0x0518 - the inverter's own AC power. If it
# is DC the AC ceiling is nearer 4324 W. SAFETY-20's `min(max_w, dev_max)` is
# what settles that once the device range is read; see goodwe/NOTES.md §1.1b,
# which records both readings and picks neither.
#
# ⚠️ AND THE `bms_soc_floor: 10` BESIDE IT IS FROM THE SAME PLACE - THE
# DATASHEET AND THE SERIAL, NOT A PACK ANYONE HAS READ. No second inverter
# exists on this site (SPIKE-04, ≈ 2026-09-12 for B); the cut-out must be read
# off the pack that is actually installed (register 0x0560 on the reference
# unit) before that pack is commanded. It reads 10 here because pack A reads
# 10, which makes this example DEGENERATE ON THE FLOOR AXIS: a site whose two
# packs floor at the SAME percent cannot separate `min`, `max`, first or last
# over the roster, and every SAFETY-32 fixture that DIFFERS the floors differs
# it for exactly that reason. Do not "simplify" those fixtures to match this
# example.
#
# ⚠️ NOTHING IS INHERITED FROM THE FLAT KEYS BY AN ENTRY THAT OMITS IT, and
# that is the whole of DEV-02 restated as a config rule. `soc`, `batt` and the
# rating became per-instance precisely so that no inverter is ever graded
# against a sibling's numbers; an entry silently inheriting `soc_entity` would
# rebuild that defect in YAML. `name`, `setpoint_entity`, `max_w` and
# `bms_soc_floor` are therefore REQUIRED of every entry (the schema below enforces it, and
# validate.py rule 9 enforces it again for the callers the Supervisor never
# sees). An omitted `soc_entity`/`batt_entity` means THIS UNIT HAS NO SUCH
# SENSOR - `inputs_ok` already stops the site for that - and never means
# "use the other one's".
#
# ⚠️ SAFETY-32: `bms_soc_floor` IS PER ENTRY AND IS REQUIRED, NOT DEFAULTED.
# It is the percent THAT pack's own BMS cuts out at, and two batteries of
# different models do not share one. A default would be this add-on inventing
# a cut-out for a battery it has not been told about, which is the same defect
# as inheriting one: the shallower pack gets protected by a floor that belongs
# to the deeper pack, and validate.py rule 8 - which refuses a peak_soc_floor
# the BMS would win against - would be grading the wrong number. Rule 8 grades
# EVERY entry and names the one it refuses. The flat key below is unchanged and
# is the single-inverter shape's own cut-out.
#
# ⚠️ AND THE FLAT `setpoint_entity` MUST THEN BE BLANK. Leaving it set while a
# roster is declared is two config sites aimed at actuators, one of which
# nothing writes; if it names an entity an entry also names, SAFETY-28's
# writer census refuses it as two writers on one actuator, and if it names a
# different one the add-on would run a site quietly smaller than the config
# reads. Rule 9 refuses both rather than picking one.
#
# ⚠️ THE SHAPE WAS MEASURED, NOT ASSUMED. A list of objects is not used
# anywhere else in this file, and whether Supervisor's options validator
# accepts one was an open question - `static_profile` carries its structure as
# a JSON string in a `str?` for exactly that doubt. It was settled by running
# Supervisor 2026.08.0's OWN `AppOptions` validator (the version this site
# runs) against both candidates: tools/supervisor_shape_probe.py is the
# script, DECISIONS/CFG-04-inverter-roster.md is what it printed and why the
# list won. The default `[]` is load-bearing in that record: WITHOUT it the
# validator answers `Missing option 'inverters' in root` for every existing
# options blob, and the upgrade leaves an add-on that cannot start.
inverters: []
estop_fitted: false
# ==========================================================================
# METER - where the grid reading comes from
# ==========================================================================
# `off` keeps the original single `meter_entity` path, so an existing
# install is untouched until it opts in. ha_dsmr subscribes to the DSMR
# integration's entities over the HA WebSocket; mqtt_p1 reads the topic below;
# ha_signed reads ONE signed HA entity (+ import / - export), which is what a
# HomeWizard P1 publishes and what ha_dsmr cannot consume.
# homewizard_local skips Home Assistant entirely and polls the meter's own
# local API. ⚠️ It is the ONLY mode whose sensor.p1_sample_age_s measures when
# the meter REPORTED rather than when the value last CHANGED - HA emits
# nothing at all for a repeated reading - so it is the only mode a firmware
# watchdog may threshold. See DOCS.md.
meter_source: "off"
meter_entity: sensor.p1_meter_active_power
meter_invert: false
meter_phases: 1
# homewizard_local only. The meter's own address, `host` or `host:port`.
p1_host: ""
# homewizard_local only. Seconds between polls. Must be well under
# meter_max_age_s - the age is never fresher than this interval - and there is
# nothing to gain below the meter's own ~5.0 s update rate (NOTES.md:640).
meter_poll_s: 5
meter_max_age_s: 30
meter_mqtt_topic: ""
# The two UNSIGNED Belgian registers. The EMS derives net power from them
# (import - export); do NOT point these at a signed template sensor.
p1_import_entity: ""
p1_export_entity: ""
# ha_signed only. ONE signed net-power sensor: positive = import from the
# grid, negative = export to it. Do NOT split it into two template sensors -
# the split is done in the add-on (p1.split_signed) precisely so the sign
# convention is tested rather than living in unreviewed YAML.
p1_net_entity: ""
# Optional, in L1..L3 order. Required for the capacity-tariff peak on a
# three-phase connection; the list length must equal meter_phases.
p1_phase_import_entities: []
p1_phase_export_entities: []
# Optional, in L1..L3 order, each one signed the same way. Same role as
# p1_phase_import_entities: the capacity-tariff peak on a three-phase
# connection. The list length must equal meter_phases.
p1_phase_net_entities: []
# ==========================================================================
# RATINGS AND LIMITS - what this site is allowed to do
# ==========================================================================
max_w: 2000
# The pack's OWN cut-out percent - what the BMS enforces whatever
# `peak_soc_floor` is set to. Register 0x0560 reads 10 on the reference
# GW5000S-BP, consistent with DoD 90. It is here so validate.py can REFUSE a
# peak_soc_floor at or below it: such a floor can never bind, the BMS wins,
# and the status page would report an energy backstop that does not exist.
#
# ⚠️ SAFETY-32 - THIS KEY DESCRIBES ONE PACK, so it is the SINGLE-INVERTER
# shape's number and nothing more. Declare an `inverters:` roster and each
# entry states its own `bms_soc_floor`; this one is not read at all and is
# not inherited by any entry. Rule 8 then grades every unit separately, which
# is the whole of that card: one cut-out for two packs of different models
# protects the shallower pack with the deeper pack's number.
bms_soc_floor: 10
peak_cap_w: 3500
peak_forecast_entity: ""
# The peak guard can COMMAND a discharge to hold a billed quarter under
# peak_cap_w. Until this card it was bounded from below by nothing but the
# pack's own BMS cut-out - a real floor, but the PACK's protection rather than
# the OPERATOR's. On the 2026-08-20 replay the guard asks for 878 Wh in a day.
#
# peak_soc_floor is the percent below which that discharge is not sized. When
# it binds the guard reports FLOOR-LIMITED, keeps charging blocked (a 0 W
# floor), and the add-on raises ONE notification saying the quarter will be
# exceeded - failing to shave is never silent, because the euro figure is the
# whole point of the guard.
#
# ⚠️ THIS IS NOT maintenance_soc_floor AND MUST NOT BE MERGED WITH IT.
# maintenance_soc_floor is the DRAIN TARGET of the monthly recalibration: the
# depth the cycle deliberately goes to, once a month, on purpose. This is the
# depth a money-saving discharge may never reach on any day. The right values
# differ, and sharing one key would couple two features that want to move
# independently.
#
# ⚠️ 20 IS DERIVED, NOT PICKED. The reference pack is 13.8 kWh usable and the
# worst modelled guard day is 878 Wh, i.e. 6.4 % - so 10 points above the
# pack's own cut-out leaves the guard ~1.6 of its worst observed days of room
# and still never reaches the BMS.
#
# ⚠️⚠️ SAFETY-25 - WHAT THIS DOES NOT BOUND, AND IT IS THE HALF THE NAME HIDES.
# peak_soc_floor BOUNDS THE PEAK GUARD ONLY. IT IS NOT A PACK-WIDE RESERVE.
# Ordinary self-consumption - the grid-following loop that holds the meter at
# zero - has no SoC floor of any kind, so on a sustained-load evening it will
# discharge STRAIGHT PAST this number and go on until the pack's own BMS
# cut-out (bms_soc_floor) stops it. Replayed on the committed 2026-08-20
# capture, 19:00-22:00 UTC: a 13.8 kWh pack starting at 21 % ends the evening
# at 10.0 %, and 343 of 587 control cycles deliver discharge with the pack
# already below this floor. Setting this key higher does not change that by
# one tenth of a percent - the same replay at every value the schema accepts
# (5..60) ends at the same 10.0 %.
#
# The reason is structural, not an oversight: the peak guard files a `lo`
# limit (a LOWER bound on the setpoint), which is what makes it provably
# unable to cap a discharge or contradict the arbiter - and therefore also
# unable to stop one the loop itself wants. See peakguard.py's module note and
# DECISIONS/SAFETY-25-loop-soc-floor.md, which records the options for a
# loop-side reserve and is waiting on the product owner. Until that is
# answered, the BMS is the only floor under self-consumption.
peak_soc_floor: 20
# ==========================================================================
# TARIFF - what energy costs, and whether to trade on it
# ==========================================================================
# `off` is the shipped default and means the §11.4 no-price-data row applies:
# static profile, plan provisional, NO ARBITRAGE. Nothing in 0.5.x consumes
# the series yet - OPT-04 is the consumer - so turning this on today fetches,
# validates and publishes prices and changes no energy decision.
#
# ⚠️ THESE DEFAULTS ARE MIRRORED ONCE, IN app/price.py's
# PRICE_OPTION_DEFAULTS, and test_price.py reads THIS FILE and asserts the two
# agree key for key. Do not add a third copy in main.py - CFG-03 is open
# because that has already happened three times.
#
# markup/taxes are the §14 `tariffs.energy_price.*` figures and are added by
# the FRAMEWORK, only for the components the chosen plugin declares its feed
# does not already contain. engie_dynamic, totalenergies_dynamic, eneco_eddy
# and manual_csv publish a figure that already carries the markup, so setting
# it under those is ignored - and logged as ignored, never applied twice.
price_provider: "off"
price_markup_eur_kwh: 0.03
price_taxes_eur_kwh: 0.06
# §9.3: injection is priced SEPARATELY, and in Belgium it is often near zero -
# which by itself strongly favours self-consumption over export. A scalar, not
# a second series: no shipped supplier publishes a dynamic injection curve.
export_price_eur_kwh: 0.04
# §14's `tariffs.static_profile`, and "" is its `null`. §9.2: "a large share
# of the installed base is on [a static profile]" - this is what makes those
# sites first-class rather than "price_provider: off, good luck".
#
# A JSON object, on one line, whose periods must tile every day type exactly
# once - no gap and no overlap. A gap is REFUSED at startup rather than
# defaulted, because an invented price is one an optimiser would trade on.
# A fully-fixed tariff is ONE period covering 00:00-24:00, all days; the
# add-on derives "fixed" from there being one distinct price, so there is no
# box to tick and none to tick wrongly.
#
# {"periods": [
# {"name":"day", "from":"07:00","to":"22:00","days":"mon-fri","eur_per_kwh":0.34},
# {"name":"night","from":"22:00","to":"07:00","days":"mon-fri","eur_per_kwh":0.26},
# {"name":"night","from":"00:00","to":"24:00","days":"sat,sun", "eur_per_kwh":0.26}]}
#
# ⚠️ A window written "22:00-07:00 mon-fri" does NOT cover Saturday morning -
# a period applies on the day the CLOCK reads, so the weekend row above is
# required, not decorative. See DOCS.md.
#
# eur_per_kwh is ALL-IN (energy + markup + taxes, §9.3), the same basis the
# dynamic providers are assembled onto. price_markup_eur_kwh and
# price_taxes_eur_kwh are NOT added to it.
#
# ⚠️ RECOMMENDED EVEN ON A DYNAMIC SITE. §11.4's degradation row is "no price
# data -> fall back to the static profile"; with this empty there is nothing
# to fall back to and a dead feed leaves the site with no tariff at all.
# validate.py warns about exactly that.
static_profile: ""
price_csv_path: "/share/goodwe_prices.csv"
price_feed_url: ""
price_horizon_h: 48
price_timeout_s: 10
# ⚠️ THE OLD PRICE PATH, AND IT IS NOT DEAD YET. These two entities are the
# add-on delegating the whole price question to Home Assistant: main.py reads
# both and derives ONE BOOLEAN, `cheap = now <= avg`, which is consumed by
# nothing except the maintenance cycle's cheap-window charge floor. That is
# all they have ever done. They are kept, because retiring them would take
# the maintenance cycle's only price signal away on a live install before
# anything replaces it - TARIFF-03 (static profile) and OPT-04 (arbitrage)
# are the cards that replace it, and neither has landed.
#
# ⚠️ They may NOT be combined with `price_provider`. Two price sources on
# one site, one of which silently wins, is exactly the "double up" the PM
# named; validate.py rule 7 refuses that configuration at startup rather than
# letting an operator believe the provider they configured is driving
# something. See app/validate.py.
price_now_entity: ""
price_avg_entity: ""
# Charge in the cheapest published hour, discharge in the dearest, and ONLY
# when the spread covers what the round trip costs. Off in the shipped
# configuration: this is the first strategy in the add-on that moves energy
# against the meter on purpose, so it is armed deliberately or not at all.
#
# ⚠️ IT NEEDS A PRICE SOURCE AND A P1 METER, and validate.py refuses the
# combinations that cannot work rather than letting them look armed. With
# `price_provider: off` and no `static_profile` there is no series to trade
# on; with `meter_source: off` the capacity-tariff peak guard never runs, and
# §9.1 puts peak shaving above arbitrage - a charge nothing measures is the
# exact failure that guard exists to prevent.
#
# ⚠️ AT THE SHIPPED THRESHOLD A STATIC DAY/NIGHT SITE DOES NOT TRADE. The
# realistic Belgian day/night spread is about 0.08 EUR/kWh and the threshold
# below is 0.10, so the verdict is "the firm spread does not cover this
# cycle's cost" and nothing happens - correctly. That is a product decision
# (this number, and app/price.py's widening factors) and it is open with the
# owner; the code is correct at any value and no number was picked to make a
# trade appear.
arbitrage_enabled: false
# §10.1's `cycle_cost_threshold_eur`: what one full round trip costs per kWh
# - the wear on the pack plus the conversion losses. A spread below this is
# a cycle that loses money and pack life, so it is not taken.
cycle_cost_threshold_eur: 0.10
# The reserve arbitrage may not spend, and the headroom it may not overfill.
# Deliberately NOT the maintenance_soc_* keys: those describe a monthly
# balancing cycle, and pointing a trading strategy at them would couple two
# unrelated policies through one number.
arbitrage_soc_floor: 20
arbitrage_soc_ceiling: 95
# ==========================================================================
# MAINTENANCE - the monthly battery recalibration cycle
# ==========================================================================
# ⚠️ CFG-03. THESE EIGHT LINES ARE THE SOURCE OF TRUTH FOR THE MAINTENANCE
# DEFAULTS. The Supervisor reads this file and the operator edits this file,
# so nothing else in the add-on gets an opinion about what a missing
# `maintenance_*` key means. There is exactly ONE in-code copy -
# `app/maintenance.py`'s `MAINT_OPTION_DEFAULTS` - because the Dockerfile does
# not put this file in the image and the running add-on therefore cannot read
# it; test_maintenance.py pins that copy by READING these lines, so a drift
# goes red in CI rather than shipping. main.py and validate.py both read the
# mirror and type no number of their own.
#
# Before this card the same defaults were written down three times and had
# already disagreed: this block said 2000 while main.py and MaintConfig said
# 2500, so an options dict with the key ABSENT passed validation at 2000 and
# then ran at 2500 against a 2000 W ceiling - a silent 0 W arbiter
# contradiction. Changing one of these numbers now moves every consumer.
maintenance_enabled: false
maintenance_interval_days: 28
maintenance_start_hour: 10
# ⚠️ BOTH MUST STAY AT OR BELOW max_w, and that is why they are 2000 rather
# than the 2500 they shipped as. The cheap-window charge shaping asks the
# arbiter for `hi = -maintenance_charge_w` against the supervised `lo =
# -max_w`: above the ceiling that is `lo > hi`, a contradiction resolved to
# 0 W, so maintenance would SILENTLY NEVER CHARGE in a cheap window on a
# default install. validate.py refuses that config (rule 6), so these
# defaults had to become self-consistent with the max_w above rather than
# ship a configuration the validator rejects.
#
# The discharge side is clamped rather than contradicted - it drains at max_w
# and the arbiter says so - so it is only warned about; it is 2000 here for
# symmetry and to keep the shipped config warning-free.
#
# Raising max_w (the live reference install runs 5000) is what unlocks a
# faster maintenance cycle. Raise max_w FIRST, then these.
maintenance_discharge_w: 2000
maintenance_charge_w: 2000
maintenance_soc_floor: 11
maintenance_soc_target: 99
maintenance_hold_min: 120
# ==========================================================================
# SAFETY - DERIVED CONSTANTS. Every number below was measured. Do not change
# one without re-deriving it
# ==========================================================================
# Trips when the emitted setpoint and the P1 net figure point OPPOSITE ways,
# both over sign_disagree_w, continuously for sign_disagree_s. Action: 0 W and
# a failsafe that latches until an operator starts control again.
#
# Both defaults are measured, not chosen. On the captured healthy day
# (2026-08-23) the longest legitimate opposed run - a load step the loop has
# not caught up with - is 30 s, and sign agreement over the gated samples is
# 93.4 %. On the captured fault day (2026-08-20) the clusters run 0.0-10.5 %
# agreement with opposed runs up to 1752 s. 300 W / 180 s sits in the middle of
# a very wide gap: at 60 s the healthy day still trips nothing, at 300 s the
# fault day still trips 13 times. There is no reason to move either number
# without a capture that says so. They are options because the AC says
# thresholds are defaults rather than constants - not because they are knobs
# anyone is expected to turn.
#
# ⚠️ sign_disagree_w must stay BELOW max_w or the watchdog can never fire (the
# arbiter bounds the command to +-max_w). validate.py refuses that config.
sign_disagree_w: 300
sign_disagree_s: 180
# ⚠️ A DIFFERENT COMPARISON, NOT A SECOND COPY OF THE ONE ABOVE, AND IT IS
# ARMED ONLY WHEN THIS SITE HAS MORE THAN ONE INVERTER. The pair above grades
# the SITE's total command against P1 - one meter, one grid connection. This
# pair grades EACH inverter's own share against THAT inverter's own measured
# power (holding register 0x0518), and it catches the fault the meter cannot
# answer for once there are two units: a unit doing the opposite of what it
# was told, while its sibling covers for it and P1 reads exactly what a
# healthy site reads.
#
# At ONE inverter these two keys do nothing at all. §6.2's identity makes the
# site's total command that inverter's command, so the pair above is already
# asking this question of the same actuator, and arming a second detector
# would be two latches and two banners for one fault.
#
# Both defaults are measured on admin/goodwe's two-master rig, over 1890
# closed-loop runs in which nothing is faulty, swept across the whole range
# this file accepts for `gain` and `slew_w`. 250 W is `saturation_w / 2`, so
# the smallest divergence this can see is exactly the gap at which the control
# law itself already says the inverter is not following; 85 s is 8.5x the
# worst legitimate opposition those runs produce (10.0 s), 2.8x the firmware's
# own 30 s link veto, and under half the 180 s the site check takes. See
# app/watchdog.py's SIGN_OPTION_DEFAULTS and
# DECISIONS/SAFETY-30-per-unit-sign.md.
#
# ⚠️ unit_sign_disagree_w must stay BELOW max_w, for sign_disagree_w's reason:
# a share is bounded to +-max_w, so a threshold at or above it can never fire.
# validate.py refuses that config.
unit_sign_disagree_w: 250
unit_sign_disagree_s: 85
# ⚠️ THE SAME COMPARISON `sign_disagree_*` MAKES, AT THE ROSTER WHERE IT STOPS
# BEING A STATEMENT ABOUT ONE INVERTER. At two or more units the SUM of the
# standing commands is graded against P1, and the trip stops the whole site -
# what it catches is the site being asked for the wrong thing, which every
# per-inverter check is blind to because each unit is faithfully executing its
# share. At ONE inverter these two keys do nothing: `sign_disagree_*` above is
# already asking this of the same actuator.
#
# The threshold is the shipped 300 W, CARRIED, and the reason is that the
# argument behind it does not depend on the roster: near zero the sign is
# noise, the deadband is 15 W, and there is one P1 whatever is behind it.
#
# ⚠️ THE WINDOW IS NOT CARRIED, AND THAT IS A MEASUREMENT. The transient 180 s
# exists to reject is the loop crossing zero after a load reversal, and the
# command has to travel the whole SITE rail at `slew_w` per cycle - a rail
# that is the roster sum while `slew_w` is not. On 1890 two-inverter runs in
# which nothing is faulty, the worst continuous legitimate opposition at 300 W
# is 110 s at one inverter and 215 s at two: carrying 180 s across would have
# shipped a false trip reachable at `gain: 0.05`, `slew_w: 50` and an ordinary
# 2.2 kW load reversal. 325 s is 1.51x that, inside the 900 s billing quarter,
# and still inside every episode of the 2026-08-20 fault day.
site_sign_disagree_w: 300
site_sign_disagree_s: 325
# Seconds the meter may keep answering with an UNCHANGED measurement while the
# command stands at the rail before the add-on raises an alarm. Both halves
# are required: neither one alone is safe, and app/freeze.py carries why.
#
# ALARM ONLY. It does not command 0 W and does not latch. A false trip parks
# the battery; a false notification costs an alert.
#
# ⚠️ Only `meter_source: homewizard_local` can see this at all - it is the
# only transport that reads the meter's own document. On every other source
# the status page says NOT COVERED rather than "armed".
#
# 300 s is measured, not chosen. Over 2399 s of the live house at the
# converged operating point (sim/scenarios/p1-age-2026-08-26.jsonl.gz, mean
# grid -14.2 W, 1194 polls, 735 of them repeating the previous reading) the
# LONGEST run without a distinct reading is 15.4 s (the largest unchanged_s any
# sample observes is 8.0 s). 300 s is 19.5x the pessimistic figure, and
# still inside the 900 s quarter that bills the capacity tariff.
meter_freeze_s: 300
# ⚠️ CFG-03. THESE TWO LINES ARE THE SOURCE OF TRUTH FOR THESE DEFAULTS, and
# `app/circulation.py`'s `CIRC_OPTION_DEFAULTS` is the ONE in-code copy - the
# Dockerfile does not put this file in the image, so the running add-on cannot
# read it. test_watchdog.py pins the copy by READING these lines, so a drift
# goes red in CI rather than shipping. Add a third option in three places -
# options:, schema:, CIRC_OPTION_DEFAULTS - and in no fourth.
#
# Circulating power is sum(|Bi|) - |sum(Bi)| over MEASURED per-inverter power:
# two inverters pushing against each other, which NETS TO ZERO AT THE METER
# and is therefore invisible to every other guard in this add-on. Both numbers
# below were measured on the TEST-19 two-master rig over 924 closed-loop runs
# in which nothing was faulty; circulation.py carries the curve they were read
# off and the argument for each. They are NOT sensitivity preferences.
#
# Both are ignored at one inverter, where the quantity is identically zero.
circulation_w: 700
circulation_hold_s: 75
# ⚠️ CFG-03. THIS LINE IS THE SOURCE OF TRUTH FOR THIS DEFAULT, and
# `app/delivery.py`'s `DELIVERY_OPTION_DEFAULTS` is the ONE in-code copy -
# the Dockerfile does not put this file in the image, so the running add-on
# cannot read it. test_delivery.py pins the copy by READING this line, so a
# drift goes red in CI rather than shipping. Two places - options:, schema: -
# plus that one dict, and no fourth.
#
# ⚠️ THERE IS NO `delivery_w` TO GO WITH IT, AND THAT IS DELIBERATE. The watts
# half of this check is `saturation_w`, the option two blocks down, read
# directly: it is already the gap at which the control law itself concludes
# the inverter is not following, and a second key would be a fourth place a
# threshold has to be kept in step and a way for the two to disagree. So
# RAISING `saturation_w` raises this check with it, and test_delivery.py part
# 4b holds that promise by running the same fault at two different
# `saturation_w` values and requiring two different answers - a check that
# only ever ran at 500 could not tell this wiring from a hard-coded number.
#
# How long ONE inverter may stand at a discharge share it is not producing -
# short by more than `saturation_w` - while at least one sibling is NOT in
# that state, before the add-on names it. It REPORTS: nothing is commanded
# differently, the loop is untouched, and the site goes on running short by
# that unit's share until somebody looks. app/delivery.py carries why, with
# the rig measurements on both sides of the decision.
#
# Ignored at one inverter, where the check is inert by construction: with no
# sibling, "this box cannot deliver" and "this plant cannot deliver" are the
# same observation.
# ⚠️ MEASURED ON THE TEST-19 TWO-MASTER RIG, NOT CHOSEN. 2640 closed-loop runs
# at a roster of two in which nothing was faulty, over 6 gains x 5 slews - the
# whole range this schema accepts - across load reversals, a flapping load and
# ASYMMETRIC SPLITS, plus 1890 runs at a roster of ONE as the control. At the
# shipped threshold the worst CONTINUOUS legitimate episode is 30.0 s (the
# weighted family; 20.0 s on reversals, 0.0 s on flapping, and 0.0 s at every
# threshold in all 1890 one-inverter runs). 185 s is 6.2x that.
#
# ⚠️ AND THE MARGIN IS SIZED ON A MEASUREMENT, NOT ON A FEELING, BECAUSE
# INVERTER B DOES NOT PHYSICALLY EXIST. The rig's B is A copied. Sweeping a
# DIFFERENT second unit through that campaign: the worst legitimate episode is
# insensitive to B's ramp (30.0 s at half A's ramp) and scales with its LAG -
# 45.0 s at twice A's measured 10 s lag, 90.0 s at four times it. 185 s is
# 2.06x even the four-times-slower case.
#
# DELIBERATELY NOT 180 - that is SAFETY-02's site hold and this is not it -
# and not 150 or 200. 37 control cycles.
delivery_hold_s: 185
# ==========================================================================
# ADVANCED - the control law and diagnostics
# ==========================================================================
auto_start: false
gain: 0.6
# ⚠️ SAFETY-39. 0 IS NOT "UNSET" AND IT IS NOT "NO LIMIT" - IT IS "FOLLOW THE
# RAIL", and it is the shipped value. `control.slew_limit_w()` resolves it to
# `SLEW_RAIL_FRAC * max_w`, which is 222 W against the 2000 W default here,
# 556 W against the live install's 5000 W, and 1067 W against the ~9600 W a
# second inverter makes of the site. `integrator_max_w: 0` two lines down has
# meant exactly this since it was added; this key now means it too.
#
# ⚠️ WHY IT IS A RATIO AND NOT A NUMBER, WHICH IS THE WHOLE OF THIS CARD. It
# WAS a number: 1000, derived 2026-08-22 against a clamp of 1500 W
# (goodwe/NOTES.md, "Simulated 2 kW load step (gain 0.6, clamp 1500)") on the
# grounds that it caps "how far the loop can jump ahead of the inverter". The
# rail then went to 5000 on the live install and the constant did not move, so
# 1000 W per 2 s tick crossed the whole output range in 10 s against a plant
# NOTES.md §5.10 measured at ~18 s up / ~23 s down. Measured on the owner's
# system 2026-09-05 11:43-11:46: a 3.4 kW export drove the setpoint 380 -> 5000
# in five ticks, the battery to -5154 W past a 5000 VA rating, and the grid
# from 3.4 kW of EXPORT to 2.8 kW of IMPORT. Large (>= 900 W) steps per 30 min
# went 2 -> 1 -> 13 -> 43 that morning. Nothing was broken; the rail moved.
#
# An explicit number is still accepted and is not clamped - the live install
# has run 400 since 2026-09-05 12:00, which is slower than the rail implies
# and is fine. What validate.py rule 10 refuses is a number FASTER than the
# rail implies, because at that setting the stated limit is not the limit and
# the layer that overrules it is the plant, which has no status row.
#
# ⚠️ AND THE COST IS REAL AND IS NOT HIDDEN: following the rail is slower to
# converge than 1000 was. Measured over 51 export steps on the in-repo model
# (test_control.py) the largest tick step falls from 1000 W to 556 W and the
# >= 900 W step disappears from every run - but the OVER-ABSORPTION does not
# move, because that is a `gain` term and not a slew term. See
# DECISIONS/SAFETY-39-slew-against-the-rail.md, which says so at length rather
# than letting this card be read as more than it is.
slew_w: 0
deadband_w: 15
target_grid_w: -10
step_w: 10
saturation_w: 500
saturation_cycles: 3
integrator_max_w: 0
heartbeat_s: 10
stale_input_s: 15
cycle_floor_s: 15
log_level: info
schema:
# ==========================================================================
# HARDWARE - the inverter, its actuator and its own sensors
# ==========================================================================
setpoint_entity: str
soc_entity: str
batt_entity: str
batt_invert: bool
# CFG-04. THE ONE LIST-OF-OBJECTS IN THIS FILE, and see the options block for
# the measurement that says Supervisor 2026.08.0 accepts it: nested types are
# enforced per entry, a missing required key names the key, a scalar where the
# list belongs is refused, and the UI renders it as a repeatable section.
#
# ⚠️ THREE KEYS ARE REQUIRED PER ENTRY AND THAT IS DELIBERATE. An entry with
# no `name` has no Store namespace and would share another unit's SAFETY-02
# latch; one with no `setpoint_entity` is a unit nothing can command; one with
# no `max_w` would have to borrow a rating, which is the sibling-grading
# defect DEV-02 removed. The optional pair is the sensors, whose absence
# honestly means "this unit reports none".
#
# ⚠️ THIS BLOCK IS DECLARED BEFORE `max_w:` ON PURPOSE. `max_w` now appears
# TWICE under `schema:` - once nested here, once flat below - and a reader
# that matches a stripped line takes the nested one FIRST. That is the
# first-match trap this card had to fix in three checks; leaving the nesting
# first keeps the trap baited, so the fix stays graded rather than assumed.
# test_inverter.py part 12 asserts the ordering is still hostile.
inverters:
- name: str
setpoint_entity: str
max_w: int(100,5000)
bms_soc_floor: int(0,50)
soc_entity: str?
batt_entity: str?
batt_invert: bool?
estop_fitted: bool
# ==========================================================================
# METER - where the grid reading comes from
# ==========================================================================
meter_source: list(off|ha_dsmr|mqtt_p1|ha_signed|homewizard_local)
meter_entity: str
meter_invert: bool
# ⚠️ 2 is accepted by this range but is not a real Belgian connection. A
# telegram whose phase count disagrees is rejected at ingest and logged, so a
# mis-set 2 shows up immediately as "0 telegrams accepted" rather than as a
# quietly wrong number.
meter_phases: int(1,3)
p1_host: str?
meter_poll_s: int(1,60)
meter_max_age_s: int(5,300)
meter_mqtt_topic: str?
p1_import_entity: str?
p1_export_entity: str?
p1_net_entity: str?
p1_phase_import_entities:
- str
p1_phase_export_entities:
- str
p1_phase_net_entities:
- str
# ==========================================================================
# RATINGS AND LIMITS - what this site is allowed to do
# ==========================================================================
max_w: int(100,5000)
bms_soc_floor: int(0,50)
peak_cap_w: int(500,15000)
peak_forecast_entity: str?
# SAFETY-24. No "off" value: a guard that can command a discharge does not get
# a supported way to have no energy bound at all. The ranges OVERLAP on
# purpose - the schema cannot express "above bms_soc_floor", so validate.py
# rule 8 is what refuses the pair, with a message naming both numbers.
peak_soc_floor: int(5,60)
# ==========================================================================
# TARIFF - what energy costs, and whether to trade on it
# ==========================================================================
# ⚠️ The provider list is written out rather than left as `str`, so the
# Supervisor rejects a typo in the UI. validate.py ALSO refuses an unknown id
# against app/price.py's PROVIDERS registry, because sim/inject.py and the
# checks reach validate_startup_config() with a dict the Supervisor never saw.
# Adding a sixth plugin means adding it here and to PROVIDERS - and nowhere
# else, which is AC2.
price_provider: list(off|generic_dayahead|engie_dynamic|totalenergies_dynamic|eneco_eddy|manual_csv)
price_markup_eur_kwh: float(0,1)
price_taxes_eur_kwh: float(0,1)
# ⚠️ The lower bound is NEGATIVE on purpose. Belgian injection tariffs have
# gone below zero (you pay to export at midday in summer), and a schema that
# bottoms out at 0 would make that site inexpressible.
export_price_eur_kwh: float(-1,1)
# A JSON string rather than a nested schema, deliberately: it is ONE option
# key (§14 has one), it survives config.yaml's flat options block, and
# parse_static_profile() accepts an already-parsed dict too, so a future
# nested schema is a config.yaml change and no code change at all.
static_profile: str?
price_csv_path: str?
price_feed_url: str?
price_horizon_h: int(1,72)
price_timeout_s: int(2,60)
price_now_entity: str?
price_avg_entity: str?
# OPT-04. ⚠️ The threshold's lower bound is 0 and not negative: it is a COST,
# and a negative one is a threshold every spread clears - arbitrage with the
# brake removed. app/arbitrage.py refuses it in code too, because
# validate_startup_config() is also sim/inject.py's entry point and can be
# handed any dict at all.
arbitrage_enabled: bool
cycle_cost_threshold_eur: float(0,1)
arbitrage_soc_floor: int(5,95)
arbitrage_soc_ceiling: int(10,100)
# ==========================================================================
# MAINTENANCE - the monthly battery recalibration cycle
# ==========================================================================
# ⚠️ CFG-03 - THIS IS WHERE A RANGE LIVES, AND THE ONLY PLACE IT LIVES. The
# `options:` block above holds the DEFAULT; this block holds the BOUNDS, and
# `MAINT_OPTION_DEFAULTS` deliberately mirrors the former and not the latter -
# the Supervisor is what enforces a range and the Supervisor reads only this
# file, so a second copy of `int(500,5000)` in Python would be a place to
# disagree and nothing else. What is NOT expressible here is a relation
# BETWEEN keys: `maintenance_charge_w` must also stay at or below `max_w`, the
# schema grammar has no way to say so, and that is why validate.py's rule 6 is
# written in code instead. Add a ninth maintenance option in three places -
# options:, schema:, MAINT_OPTION_DEFAULTS - and in no fourth.
maintenance_enabled: bool
maintenance_interval_days: int(1,90)
maintenance_start_hour: int(0,23)
maintenance_discharge_w: int(500,5000)
maintenance_charge_w: int(500,5000)
maintenance_soc_floor: int(5,30)
maintenance_soc_target: int(50,100)
maintenance_hold_min: int(5,480)
# ==========================================================================
# SAFETY - DERIVED CONSTANTS. Every number below was measured. Do not change
# one without re-deriving it
# ==========================================================================
# No "off" value, deliberately: this is a P0 safety check and the schema is
# not the place to make disarming it a supported configuration.
sign_disagree_w: int(50,5000)
sign_disagree_s: int(30,1800)
# SAFETY-30. No "off" value, for SAFETY-02's reason.
#
# ⚠️ THE THRESHOLD'S RANGE IS THE SAME AS THE SITE CHECK'S ON PURPOSE, AND THE
# WINDOW'S FLOOR IS NOT. On the two-inverter rig the per-unit comparison's
# worst continuous legitimate opposition is nearly FLAT in the threshold -
# 25.0 s at 50 W, 15.0 s at 150 W, 10.0 s at 250 W, 5.0 s at 500 W - because a
# unit's own power chases its own command rather than the load. So no value in
# this range puts the guard outside the regime it can be answered for, and the
# floor does not have to be a knee the way `circulation_w`'s does.
unit_sign_disagree_w: int(50,5000)
# The floor of 30 is `inverter.LINK_STALE_S`, the firmware's own veto window:
# below it, a unit not executing its share is a LINK fault the add-on already
# answers by dropping the unit from the split, and firing inside that window
# would be a second, louder alarm about a state that is already being handled.
unit_sign_disagree_s: int(30,1800)
# SAFETY-30's SITE pair. Same ranges as `sign_disagree_*`, because it is the
# same comparison asked of the site total - and no "off" value, for the same
# reason. ⚠️ THERE IS DELIBERATELY NO validate.py RULE PAIRING
# site_sign_disagree_w WITH max_w, unlike the other two thresholds: the bound
# on the SITE command is `Controller.site_max_w`, the ROSTER SUM, and
# `validate_startup_config()` is handed options rather than a roster. A rule
# written against max_w would refuse a perfectly reachable two-inverter
# configuration the day CFG-04 lands. The schema range is the bound here.
site_sign_disagree_w: int(50,5000)
site_sign_disagree_s: int(30,1800)
# No "off" value, for SAFETY-02's reason: disarming a safety alarm is not a
# supported configuration. ⚠️ THE FLOOR OF 60 IS NOT A RECOMMENDATION. At 300 s
# the slowest a HEALTHY meter's 1 Wh register can tick and still look unchanged
# is 12 W, which is inside the 15 W deadband, so the two terms of the
# conjunction are mutually exclusive rather than merely far apart. At 60 s that
# figure is 60 W and the argument is gone - only the margin is left. See
# app/freeze.py.
meter_freeze_s: int(60,3600)
# SAFETY-31. No "off" value, for SAFETY-02's and meter_freeze_s's reason:
# disarming a safety alarm is not a supported configuration.
#
# ⚠️ THE FLOOR OF 400 IS NOT A RECOMMENDATION, IT IS THE MEASURED EDGE OF THE
# REGIME IN WHICH THIS GUARD CAN BE ANSWERED FOR. On the TEST-19 rig, the
# worst CONTINUOUS opposition produced by a site where nothing is faulty - a
# flapping load reversing every control cycle, swept over the whole range this
# schema accepts for `gain` and `slew_w` - is 5.0 s at a 400 W threshold and
# above, 10.0 s at 300 W, 40.0 s at 250 W and 505.0 s at 100 W. Below the
# knee, legitimate operation holds the sensor over the threshold for MINUTES
# and no window shorter than the 900 s billing quarter could tell that from a
# fault. A configurable value under 400 W would be a false-alarm generator
# that this project's own doctrine (SAFETY-15, SAFETY-19) forbids shipping.
circulation_w: int(400,5000)
# The floor of 30 is `inverter.LINK_STALE_S`: below the firmware's own veto
# window a unit still executing a stale share is a LINK fault the add-on
# already handles by dropping it from the split, and firing inside that window
# would raise a second, louder alarm about a state already being managed. The
# ceiling of 900 is the quarter that bills the capacity tariff - a circulating
# loop must be caught and acted on well inside one.
circulation_hold_s: int(30,900)
# SAFETY-42. The floor of 30 is `inverter.LINK_STALE_S`, for
# `circulation_hold_s`'s reason and the same one SAFETY-30's per-unit window
# takes it from: below the firmware's own veto window a unit not executing its
# share is a LINK fault the add-on already answers by dropping it from the
# split and saying so in the action log, and reporting inside that window
# would be a second, louder alarm about a state already being handled. The
# ceiling of 900 is the quarter that bills the capacity tariff - a site
# running short of one unit's share must be reported well inside one.
delivery_hold_s: int(30,900)
# ==========================================================================
# ADVANCED - the control law and diagnostics
# ==========================================================================
auto_start: bool
gain: float(0.05,1.0)
# ⚠️ THE FLOOR IS 0, NOT 50, AND 0 IS THE SHIPPED VALUE - see the options block
# above. It means "follow max_w", so the range starts at the setting that
# cannot go stale rather than at the smallest number somebody could type.
# ⚠️ THE CEILING IS STILL 5000 AND IS STILL NOT THE BOUND THAT MATTERS. The
# binding one is `SLEW_RAIL_FRAC * max_w`, a relation BETWEEN keys, and this
# grammar cannot express a relation - which is the same reason
# `maintenance_charge_w`'s ceiling is not its real bound either (see the note
# above it). validate.py rule 10 is where it is written.
slew_w: int(0,5000)
deadband_w: int(0,500)
target_grid_w: float(-200,200)
step_w: int(1,100)
saturation_w: int(100,2000)
saturation_cycles: int(1,10)
integrator_max_w: int(0,15000)
heartbeat_s: int(2,25)
stale_input_s: int(5,120)
cycle_floor_s: int(5,60)
log_level: list(trace|debug|info|warning|error)