checks / unit (pull_request) Successful in 6m20s
`delivery.delinquent()` named a unit whose `short_by()` gap exceeded an
ABSOLUTE `min_w = Tuning.saturation_w = 500 W`. OPT-09's SoC-aware weights
shrink a low-headroom unit's share, and shrinking the share shrinks the gap, so
a unit standing at +125 W and delivering 0 W - 100 % delinquent - was never
named. Measured end to end on the real loop (test_packshare.py part 8b):
load 1500 W, B wedged at 15 %, equal weights named on 199/200 cycles
load 1500 W, B wedged at 15 %, OPT-09 weights named on 0/200 cycles
⚠️ The suppressed regime is the quiet one: at a load the healthy sibling covers,
the meter is satisfied, `unmet_w` is 0 and no action-log line fires, so this
alarm is the ONLY instrument that would have told the operator.
WHAT CHANGED, in one line:
named if short_by() > min_w OR short_by() > frac * share
⚠️ `min_w` WAS NOT LOWERED. It exists to stop normal saturation being reported
as delinquency, and lowering it trades a missed alarm for a false one on every
unit at once - SAFETY-41's four-attempt regime. This is a SECOND way to be
named, not a looser first one: all seven of test_delivery.py part 1's existing
fixtures answer identically under both rules, and the absolute arm's suppression
window is still exactly 1000 W / 6500 W, still asserted in part 8b.
THE FRACTION IS DERIVED, 0.85. admin/goodwe:sim/delivery_window.py gained a
`--fractions` axis and grades the constant over the SAME 2640 no-fault runs that
produced `delivery_hold_s`'s 35.0 s floor. Worst continuous legitimate episode,
worst of three families, twenty fractions:
frac 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50
worst 90.0 90.0 70.0 70.0 60.0 55.0 55.0 60.0 45.0 45.0 s
frac 0.55 0.60 0.65 0.70 0.75 0.80 *0.85 0.90 0.95 0.99
worst 40.0 40.0 45.0 45.0 45.0 45.0 40.0 40.0 40.0 40.0 s
absolute arm alone: 35.0 s (SAFETY-42 §3.3, reproduced in the same runs)
⚠️ NO CLIFF ANYWHERE: 0.45-0.99 is flat within one control cycle, and it is not
monotone - §3.3's own mechanism (c). ⚠️ "Zero false namings" is NOT achievable
at any fraction and the record says so; what is zero is false ALARMS - 90.0 s
worst against a 185 s hold, so nothing comes within 95 s of notifying anybody.
N=1 control 0.0 s at every fraction in all 2640 one-inverter runs; flapping
0.0 s in all 840.
DRIVEN. Part 8b pinned the SUPPRESSED behaviour and said "if it ever goes red
because the alarm fired, read the card that made it fire". It now grades BOTH
rules on one run - `share_frac=None` is SAFETY-42's rule exactly:
OPT-09 weights, absolute arm alone named on 0/200
OPT-09 weights, the shipped rule named on 200/200
POSITIVE CONTROL. Same fixture, same weights, same 125 W share, one legitimate
fact changed: a pack at its own 10 % cut-out is named on 0/200 (account() still
gates it), and a unit delivering HALF its share is named on 0/200.
N=1 BYTE-IDENTICAL, asserted: `plan()` handed a `weights` mapping that raises on
any read still answers identically at a roster of one, and the same mapping
raises at a roster of two; `delinquent()` answers {} on all 84 single-unit
(share, measured, rule) combinations including 0 of 125 W.
MUTATION, run on fresh :ro trees: M12 (drop the relative arm), M13 (frac -> 1.0)
and M14 (frac -> 0.05) are all red on named checks. The constant cannot move in
either direction unseen.
⚠️ CFG-07 gets ONE CONTROL CYCLE WORSE and is deliberately not fixed here: the
worst legitimate episode goes 35.0 -> 40.0 s, so the schema's `int(30,900)`
false-tripping band widens from [30,35] to [30,40]. CFG-07 should be re-derived
against 40.0 s.
No option value, no schema bound and no default changed. 27/27 suites green.