AC3 says "verified on the rig". The previous commit drove hwsim in-process
because `riglock status` reported UNKNOWN - which is the tool declining to
observe, not an observation. riglock shells out to the local docker CLI; on a
Windows host without DOCKER_HOST that resolves to a Docker Desktop npipe which
is not running, and the result is indistinguishable from a genuinely absent rig.
The rig was up the whole time. With DOCKER_HOST=ssh://homelab@192.168.2.147 it
reads FREE.
Re-run under sim/riglock.py against the real goodwe-sim compose project, with
the shipped modules staged into goodwe-sim-plant so they poll that container's
own hwsim while plantsim drives it. Both phases passed, lock released cleanly.
The rig produced a result the in-process stub could not, and it strengthens the
design rather than merely confirming it: in the NEGATIVE twin - +8000 W of house
load, healthy meter, correctly railed command - `active_power_w` did not move at
all, sitting at exactly 10130.0 W for 26 consecutive polls. The only thing
keeping `unchanged_s` at 0.0 s was the kWh registers advancing.
So the register terms in measurement_fingerprint() are not belt-and-braces for
this detector, they ARE the negative case: fingerprinted on the power figure
alone it would have raised a false alarm on a healthy meter under a real load,
which is precisely how a safety guard gets switched off. Recorded in freeze.py
so nobody simplifies the fingerprint without meeting that run first.
No behaviour change - documentation and the harness note only.