glenn schrooyenandClaude Opus 5 9aed43990b SAFETY-02: a loop can be fresh, tracking and inside its rating and still push the wrong way
The stale-input watchdog asks whether the meter is still talking. The saturation
freeze asks whether the inverter can follow. The output clamp asks whether the
number is too big. A loop can pass all three while charging the battery out of
the grid, because the only thing wrong is the sign.

On 2026-08-20 a commercial controller did exactly that four times in one day,
for up to 77 minutes at a stretch, reaching a commanded -14 768 W against a
±5000 W inverter. app/watchdog.py compares the emitted setpoint against the
authoritative P1 figure and, when they oppose each other with both over 300 W
for 180 s continuously, files a failsafe SET claim at P_SAFETY, commands 0 W and
latches there until an operator starts control again.

Validated against that day rather than against an argument: sim/replay_sign.py
in the infra repo drives this module over the committed captures of both
2026-08-20 and the healthy 2026-08-23 and reaches 18 trips on the fault day -
every one inside a window NOTES.md §4.7 accounts for - and 0 on the healthy day.
The four episodes do share one signature: 0.3 / 0.9 / 10.5 / 0.0 % sign
agreement inside them against 92.9 % healthy.

Three decisions the ticket could not make:

- It is DISARMED whenever the grid-following loop is not what is driving. Sign
  agreement is a property of a loop that follows the meter, and a maintenance
  grid charge opposes the meter by design - 2500 W of charge into a house
  drawing 500 W is +3000 W on the meter against a -2500 W command, for hours.
  The gate tests the emitted number, not the winning claim's name, because a
  limit claim can let the loop "win" and still replace its value.
- The trip LATCHES. Commanding 0 W removes the command side of the comparison,
  so the disagreement always clears the moment the trip works.
- sign_disagree_w at or above max_w is refused at startup. The arbiter never
  lets a command exceed max_w, so such a threshold leaves the watchdog incapable
  of firing while the status page still reports it armed.

What it does not catch, said out loud: an inverter that ACTS opposite to its
command moves the meter further the same way, leaving command and meter in
agreement. That is the saturation freeze's job.