SAFETY-13: the bound came from the wrong half of a two-sided measurement
NOTES.md 5.10 measured the 1.78 kW step BOTH ways - "Up: ~18 s from step to
deadband. Down: ~23 s" (NOTES.md:1550). SAFETY-39 takes 18 correctly: its
bound is a REFUSAL and the looser number refuses less. This branch reused
PLANT_SETTLE_S for the opposite job - how long the plant may still be the
EXPLANATION for a divergence - where the conservative half is the longer one.
ceil(23/2) = 12, not 9, and being short there does not refuse anything, it
accuses.

The false positive is real and is measured here. One inverter, one compute(),
one plant, no second writer anywhere in the harness: the command falls through
zero while the pack is still coasting the old way, unasked_power() calls our
own power "unasked", the counter reaches 9 while it is still coasting, and the
law emits "freeze-released". At the plant's own measured 18 s/23 s shape, over
272 load-step pairs, the 9-cycle bound fires in 62 and the 12-cycle bound in 2.

  PLANT_SETTLE_DOWN_S = 23.0 is added beside PLANT_SETTLE_S = 18.0, because
  the plant's settling time is a PAIR and each bound has to say which half it
  means and why.
  SETTLE_CYCLES = ceil(PLANT_SETTLE_DOWN_S / LOOP_TICK_S) = 12. It is no
  longer the reciprocal of SLEW_RAIL_FRAC; that was a coincidence of both
  reading the same half, and test_control.py now asserts the inequality.
  _SAT_COUNT_CAP moves with it, 10 -> 13. config.yaml accepts
  saturation_cycles as int(1,10), so the whole accepted range is now strictly
  BELOW the bound and the degenerate configuration this branch used to
  document no longer exists - pinned against config.yaml's own schema line.

Three shipped statements were falsified by that measurement and are rewritten,
not renumbered - at 12 the residual is smaller, not zero:

  unasked_power()'s docstring said anything outside the interval "was put
  there by something other than this loop". It was our own power: eight cycles
  after a +1990 W command the command is 0 and the pack still reads +522.3 W.
  control.py said "SO THE BOUND BELONGS TO (b) AND ONLY TO (b)". It fired in
  case (a).
  DOCS.md told an operator "if you see freeze-released, look for the second
  writer" - on a single-inverter install, hunting something that does not
  exist. Replaced by a section that gives the innocent causes first (a large
  load or PV swing; a plant slower than the one measured, 8/320 scenarios at
  23 s rising to 268/320 at 50 s) and the second writer only when the state
  STANDS.

Round 1's own results are kept and re-graded, not weakened. The release/1.0
sweep had to widen to reach the new bound (3780 cases): 3267 bit-identical,
432 releases, 27 command changes - all still charge starts from prev_w == 0 -
and 81 differing in the saturation counter alone, which nothing downstream can
read. The card's case releases on the twelfth saturated cycle instead of the
ninth and settles at the same -1190 W against the same frozen integrator.

Also corrected, because they were claims and did not reproduce: the coverage
table's "output freeze" row was 11, and the mutation form its own note
describes gives 6 on this tree, 6 on the first SAFETY-13 commit and 2 on
release/1.0; the detector row was left at 11 and is 15; the frozen = False
footnote was left at 10 and is 13. And section 6 reported 107 625 as "released
states" when it is the number of states SWEPT - 67 500 of them release, and
both are counted now.

Nothing here reached the inverter. 22/22 test files pass in goodwe-addon-ci,
tree rsynced to a plain path, mounted :ro, python3 -B, __pycache__ purged and
printed first (0 dirs / 0 .pyc; the worktree carries none).

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-06 18:32:03 +02:00

397 lines
21 KiB
Markdown
Raw Permalink Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# SAFETY-13 — the output freeze gets an exit, and only where it cannot end on its own
**Status:** decided and implemented on branch `SAFETY-13`, off `release/1.0` @ `c8dcb38`.
**Card:** SAFETY-13 — *"Bound the no-start-while-saturated output block"*
([Trello](https://trello.com/c/uZjmuF7B)).
**Nothing here reached the inverter.** Every figure below is from the pure control
law run in a container against a plant model, on this branch and on a pristine
`c8dcb38` for the before-figures. No rig, no ESP32, no Home Assistant.
---
## 0. The four things a reader should take away
1. **The card's headline case is real, and the route to it is not the obvious
one.** The block does not engage on the way down into an export; the slew
limit moves the command off zero before the counter reaches 3. It engages
from the **deadband** — a site resting at its target with another writer on
the bus, counting saturated cycles while nothing is wrong — and 0 W is then a
fixed point. §2.
2. **`prev_w == 0` is not a special case, so the fix is not one either.** The
same run pins at −800 W against its own integrator standing at −2388 W, at a
non-zero `prev_w`, with
the same absence of an exit. Zero is only the instance where the pinned
magnitude is the whole of what the battery could have done. §3.
3. **The decision is not "how long", it is "which".** A divergence a *limit*
could have produced clears itself and gets no exit — `release/1.0` unchanged.
A divergence a limit could not have produced may not, and gets one. The
predicate is physical, not statistical — and it is **not** a second-writer
detector; §4.1 and §8 say what it can and cannot tell apart.
4. **Releasing the output freeze does not unfreeze the loop**, and that is what
makes the release bounded rather than merely different. §6.
5. **The bound comes from the SLOWER half of a two-sided measurement, and the
first version of this branch took the faster half.** §8 is the correction and
the measurement behind it; it is the reason `SETTLE_CYCLES` is 12 and not 9.
---
## 1. What was there, in the terms the code uses
`control.py`, in `compute()`, after the clamp and the slew limit:
```python
if frozen:
target = min(target, prev_w) if prev_w > 0 else max(target, prev_w)
reason = "saturated-freeze"
```
"Magnitude may fall, never rise." At `prev_w == 0` the magnitude is zero and
`max(target, 0)` forbids any negative command, so a charge cannot **start**.
The reason is written in the file and it is a good one: `frozen` means the
inverter's reported power has diverged from the command by more than
`saturation_w` for `saturation_cycles` consecutive cycles, and at a command of
zero that means the actuator is producing power nobody in this add-on asked for.
Starting to push the other way into it is the configuration §1.5 of the
specification rules out — *"any configuration in which two writers can reach one
actuator"*.
**The defect is that it has no end.** Not the error growing, not the integrator
moving, not time. `sat_count` stops rising at its cap and the state is a fixed
point.
---
## 2. Reproducing it — and correcting the route
Driven at the live install's shape: `max_w 5000`, `slew_w 400`,
`target_grid_w -10`, `saturation_w 500`, `saturation_cycles 3`, `gain 0.6`.
Another writer holds the pack at **+700 W** whatever is commanded.
**The route that does NOT reach it.** Start at `prev_w = 0` with 2 kW of export
already standing. On `c8dcb38` the loop moves off zero at the slew limit before
the counter reaches 3 — commands −400, −800 — so by the time `frozen` is true
`prev_w` is −800 and the block that gets applied is `max(target, −800)`. The
site charges at 800 W, not 0 W, for as long as the run lasts.
**The route that does.** The site is *resting*. `grid == target_grid_w`, so the
loop is in its deadband and the command is 0 — and `saturated_now` is computed
**before** the deadband branch, so the counter climbs anyway. Three cycles later
the loop is frozen at `prev_w == 0` with nothing wrong. Then the export arrives:
| cycle | grid | actual | prev | command | integrator | sat | reason |
|---|---|---|---|---|---|---|---|
| 0–1 | −10 | +700 | 0 | 0 | 0 | 1–2 | `deadband` |
| 2–5 | −10 | +700 | 0 | **0** | 0 | 3–6 | `saturated-freeze` |
| 6 | −2000 | +700 | 0 | **0** | −1194 | 7 | `saturated-freeze` |
| 7… | −2000 | +700 | 0 | **0** | −1194 | 8→10 | `saturated-freeze` |
On `c8dcb38` the command is `0.0` on **every** cycle from there on. The
integrator has moved to −1194 W and stopped (its own freeze holds it), the site
exports 2 kW, and the battery is idle until the other writer leaves.
That is the card's sentence — *"the site can sit exporting 2 kW with an idle
battery indefinitely"* — reproduced, with the route corrected: it is entered
from the **deadband**, not from a correction that ran out of room.
---
## 3. …and `prev_w == 0` is not where it stops
The same tuning, same writer, but the loop starts from zero with the export
already standing (the route from §2 that "does not reach it"):
| | `c8dcb38` |
|---|---|
| command after the freeze engages | **−800 W**, on every cycle |
| the loop's integrator, frozen | −2388 W |
| what ends it | nothing |
So the missing exit is a property of the **output freeze**, not of the zero
case. `prev_w == 0` is the instance where the pinned magnitude happens to be
zero. A rule written for zero alone would have left −800 W exactly as unbounded
as it found it — which is why the change below is written against the freeze and
not against a special case of it.
**And this is the half that escalates at two inverters.** `actual_w` is
`site_batt_w`, the SUM (ALLOC-01, DEV-02), so the comparison is a site command
against two units' power. One unit still moving after the other has stopped is
enough to put the site into the freeze with no external actor at all.
⚠️ **What that claim is and is not.** The escalation is stated from the code —
`prev_w` is `self.target`, the site total, and `actual_w` is the site sum — and
from the single-unit runs above. **It is not measured on two inverters.**
Inverter B does not physically exist (`NOTES.md` §1.1b: on paper, from datasheet
and serial), and `sim/plantsim.py:216` `INVERTER_B` is `INVERTER_A` copied with
`measured=False`. Any two-inverter number would be two copies of A.
---
## 4. The decision: which freezes get an exit, not how long the block lasts
Three answers were on the table, and the card named them: lift after N frozen
cycles, exempt above some export magnitude, or keep it unbounded and write down
the cost.
**A plain cycle bound was rejected**, because it bounds the wrong thing. The
freeze is right to be permanent in one case and cannot be permanent in the
other, and a single N treats them alike:
| the inverter is… | can the freeze clear itself? |
|---|---|
| doing **less** than the command, in the command's own direction — a cold pack, a curtailment, an export cap, the plant still ramping | **Yes.** The command is pinned at something the inverter can reach, so it catches up, `saturated_now` goes false, and the freeze ends. Asking for more would achieve nothing anyway. |
| doing something **outside** what the command can explain — overshooting it, or the opposite sign | **No.** Clearing the freeze requires the inverter to track *our* command, and the other writer is precisely what stops that. |
**An export-magnitude exemption was rejected** for a narrower reason: it makes
the block's end depend on how big the other actor's disturbance happens to be,
which is not a property of the thing the block is about.
So the rule implemented is:
> The output freeze applies as before, **unless** the inverter's reported power
> cannot be explained by the command not being met **and** the divergence has
> outlasted the plant that would otherwise have explained it.
### 4.1 The predicate is physical
`unasked_power(prev_w, actual_w, saturation_w)`. A limit can only make the
inverter do **less** than the command, in the command's own direction. It cannot
make it overshoot the command and it cannot make it produce the opposite sign.
So everything a limit can produce lies in the closed interval spanned by `0` and
`prev_w`, widened by `saturation_w` for noise, ramp lag and idle draw.
⚠️ **What it does NOT establish is that anything outside was put there by
something else.** The first version of this branch said exactly that, in the
docstring, in `control.py` and in DOCS.md, and it is false: the predicate
compares against **one cycle's** command while the pack carries every command
before it, so our own coast-down through zero lands outside our own interval.
§8 measures it. What the predicate guarantees is only its own first sentence —
*this cycle's command does not account for this cycle's reading* — and the time
bound below is what turns that into a reason to act.
| prev | actual | interval | verdict |
|---|---|---|---|
| +2000 | +700 | [0, 2000] | a limit |
| −5000 | −700 | [−5000, 0] | a limit |
| 0 | +700 | [−500, +500] | **unasked** |
| −800 | +700 | [−1300, +500] | **unasked** |
⚠️ **At `prev_w == 0` this predicate and the saturation detector are the same
test** — asserted in `test_control.py` over 801 readings. That is not a
coincidence to tidy away: with nothing commanded there is no interval left for a
limit to live in, which is exactly why the zero case is the one that strands.
⚠️ **It is not a detector and nothing alarms on it.** A stale, wrong-signed or
noisy reading lands outside the interval too. All it decides is whether the
freeze gets an exit; being wrong about it costs a bounded command (§6).
SAFETY-30's `unit_sign_disagree_w` is the thing that alarms on sign, and it is
deliberately a different test with a different threshold.
### 4.2 The bound, and which half of the measurement it comes from
`SETTLE_CYCLES = ceil(PLANT_SETTLE_DOWN_S / LOOP_TICK_S)` = **12**.
⚠️ **`PLANT_SETTLE_DOWN_S` is new, and adding it is the point rather than a
cost.** `NOTES.md` §5.10 did not measure *a* settling time; it measured the same
1.78 kW step in **both directions** — "Up: ~18 s from step to deadband. Down:
~23 s from a −1784 W export excursion" (`NOTES.md:1550`). So the plant's
settling time is a **pair**, and which half is the safe one depends on which way
being wrong hurts:
| the bound | the question | the safe half | why |
|---|---|---|---|
| SAFETY-39's `SLEW_RAIL_FRAC` | may this configuration be **refused**? | **18 s**, the shorter | a looser bound refuses fewer working configurations |
| this one | may the plant still be the **explanation**? | **23 s**, the longer | a shorter bound stops believing the plant too early, and then it accuses |
The first version of this branch reused `PLANT_SETTLE_S` and got 9 — three
cycles short of the plant's own measured down-ramp, on the side that produces a
false positive. §8 is the measurement and the correction.
⚠️ **It is no longer the reciprocal of `SLEW_RAIL_FRAC`, and it never should
have been read as one.** The two were equal only while both were being derived
from the same half of the pair, and that coincidence read as a derivation. They
are 9 and 12 now; `test_control.py` asserts the inequality so they cannot be
quietly re-fused.
⚠️ **It inherits SAFETY-39's caveat about `LOOP_TICK_S`, in the opposite
direction.** A meter **slower** than 2 s makes 12 cycles cover more than 23 s, so
the freeze holds longer than the plant needs: that costs energy, never safety. A
meter **faster** makes them cover less, so the freeze can release while the
plant is still moving — bounded by §6 rather than by luck.
**`_SAT_COUNT_CAP` moved with it, from 10 to 13**, because it is written as
`SETTLE_CYCLES + 1` — a counter capped below the longest bound read from it
would silently delete the exit. That has a consequence worth stating on its own:
`config.yaml` accepts `saturation_cycles` as `int(1,10)`, so at the old bound of
9 a legal setting could sit **above** the exit and delete the block. At 12 the
whole accepted range is strictly below the bound, and the degenerate
configuration this branch used to document no longer exists. §7.
---
## 5. What actually changed, graded against `release/1.0`
`test_control.py`'s sweep still compares this law against a transcription of
`release/1.0` — the transcription was **not** taught the new rule, because an
oracle taught the change compares the law against itself. What changed is the
assertion: every case must be identical, or be a release with both of its
conditions true, or differ **in the saturation counter alone**.
⚠️ **The sweep had to be widened to keep grading anything.** Its `sat_count`
fixtures ran to 9; with the bound at 12 the counter never reached the exit and
every release silently vanished from the table, which is what the assertion on
the count caught. It runs to 12 now, at 3780 cases.
| | cases |
|---|---|
| total | 3780 |
| **bit-identical to `release/1.0`** | **3267** |
| releases | 432 |
| …of those, reason-only (the freeze was not binding) | 405 |
| …of those, **the command changes** | **27** |
| differ in the **saturation counter alone** | 81 |
All 27 command changes are at `prev_w == 0`, all with `release/1.0` commanding
exactly `0.0 W`, and every new command is **negative** — a charge start that was
refused.
⚠️ **The 81 are the counter's ceiling moving, and they reach nothing.**
`_SAT_COUNT_CAP` went from 10 to 13 with the bound, so above `release/1.0`'s own
ceiling the two counters differ. Nothing else may differ in those cases, and the
sweep asserts that: `frozen` is `sat_count >= saturation_cycles`, `config.yaml`
accepts that at most 10, and no other line in `compute()` reads the counter's
value — so a counter reading 13 instead of 10 cannot change what is commanded.
The 81 all sit at an `sc` above 10, which is a state `release/1.0` could never
hold at all.
The behaviour after the fix, on §2's run: the command holds at 0 W through
`sat_count` 3–11, releases on the **twelfth** saturated cycle, and walks
0 → −400 → −800 → **−1190 W**, where it stops — the same settling point as at
the old bound, three cycles later.
The genuine-limit case, driven for 30 cycles with the inverter curtailed to
±1000 W against a 4 kW import: `freeze-released` never appears and the command
stays pinned at +2400 W. Unchanged, deliberately.
---
## 6. Why the release cannot become windup (the card's fourth criterion)
**The integrator freeze is not lifted with the output freeze.** The command is
derived from `i_w`, then clamped, then slew-limited from `prev_w` — so a
released cycle can only move the command *toward* an accumulator that stopped
accumulating when the freeze engaged, by at most one slew step, and never past
it. `test_control.py` sweeps 107 625 states, of which **67 500 release**: no
released case leaves the interval between the previous command and the frozen
integrator, and none moves further than one slew step.
⚠️ **107 625 was previously reported as the number of released states. It is
the number of states swept**, and the assertion only ever graded the subset that
released. Both numbers are counted and printed now.
On §2's run that shows up as the settling point: **−1190 W against a frozen
integrator of −1194 W**, not the 5000 W rail. The tech lead's note on SAFETY-04
— that the carried `i_w` and `release/1.0`'s recomputed value land on the same
slew-limited command — is preserved: the `i_w=None` path is still graded against
the transcription, cycle for cycle, everywhere except the 432 releases.
⚠️ **The first form of this check was wrong and the sweep said so**, which is
left in the test file. It asserted `|target| <= |i_w|` on a released cycle and
produced `prev −5000, i_w −3000, target −4600`: the command was walking back
from −5000 toward the integrator and had not arrived. It was moving the right
way and the assertion still failed, because "never exceeds the integrator" is
not what no-windup means here.
---
## 7. What this does NOT buy, said plainly
**The site still does not reach its target while another writer is on the bus.**
It settles at the frozen integrator, not at the meter's target. What the exit
buys is that the battery stops being *idle* while the site exports; it does not
buy correct regulation against an actuator somebody else is also writing to, and
nothing in a rules engine can. A standing grid error with a second writer
present is the symptom of a configuration this add-on refuses to support.
**`freeze-released` is a place to start looking, not a finding.** It says the
divergence outlasted the plant's own measured settling time, and that is all it
says — §8. DOCS.md now tells the operator the innocent causes first (a large
load or PV swing, a plant slower than the one that was measured) and the second
writer only when the state **stands**. It is carried on `Decision.reason`, which
nothing after the freeze overwrites. No new alarm was added: SAFETY-41 removed
one that narrated normal anti-windup, and this state is not yet known to be
worth waking anybody for.
**No accepted configuration removes the block any more.** `config.yaml` accepts
`saturation_cycles` as `int(1,10)`; the bound is 12, so every accepted value is
strictly below it and the freeze always engages before its exit is due. This
paragraph used to say the opposite — at a bound of 9, settings of 9 and 10
deleted the block silently and the branch documented that as a known
consequence. Moving the bound closed it by construction. `test_control.py` pins
it against `config.yaml`'s own schema line rather than a transcription of it.
**Nothing was measured on two inverters.** See the warning in §3.
---
## 8. ⚠️ ROUND 2: the bound was derived from the wrong half, and it accused
**What was wrong.** `SETTLE_CYCLES` was `ceil(PLANT_SETTLE_S / LOOP_TICK_S)` = 9.
`PLANT_SETTLE_S` is 18 s, the **up**-ramp of `NOTES.md` §5.10's kettle step;
the same measurement recorded ~23 s coming back **down** (`NOTES.md:1550`).
SAFETY-39 takes 18 correctly — its bound is a refusal, and the looser number
refuses less. This bound asks the opposite question, and the looser number stops
believing the plant three cycles too early.
**Why that is not a tuning quibble.** The predicate has no memory. `prev_w` is
one cycle's command; the pack carries every command before it. A command that
falls **through zero** — the ordinary end of a load or PV step — leaves the pack
coasting in the old direction, so the reading has the sign the command *used* to
have and lands outside the interval spanned by 0 and the new `prev_w`.
`unasked_power()` calls that "unasked". With the bound three cycles short of the
plant's own down-ramp, the counter reaches it while the coast-down is still
going, and the law emits `freeze-released` on **one inverter with nothing else
on the bus.**
**Measured, in the container, N = 1.** One `compute()`, one plant model, one
command; no second writer anywhere in the harness. The plant is a first-order
lag whose two time constants come from the two measured settling times
(tau = t/3, since a first-order step is 95 % done at 3 tau) with
`sim/plantsim.py`'s measured 800 W/s ramp cap. It is a **model**, and it is
labelled one wherever it is used.
| | bound 9 | bound 12 |
|---|---|---|
| 1280 closed-loop scenarios (a grid of plant pairs, slews, `saturation_cycles`, load steps) | **113 fire** | **24 fire** |
| 272 load-step pairs at the measured 18 s / 23 s plant, `slew_w 400` | **62 fire** | **2 fire** |
The single case now pinned in `test_control.py`: a 4 kW export falling to
2.5 kW. At cycle 34 the command is −310 W, the pack is still at −1343.4 W
coasting down from −4860 W a few cycles earlier, `unasked_power(−310, −1343.4,
500)` is True, `sat_count` is 9, and the law says `freeze-released`. At 12 the
same run never releases.
**What the fix does not fix.** The bound makes the false positive rare on *the
plant that was measured*. It cannot make it impossible, because it is a
measurement and the plant can be slower than the measurement. Same sweep, bound
held at 12, lengthening only the plant's down-ramp: 8 of 320 scenarios at the
measured 23 s, 59 of 320 at 34 s, 268 of 320 at 50 s. That residual is why the
three statements below were corrected rather than merely re-numbered.
**Three shipped statements were falsified by this and are now rewritten:**
1. `unasked_power()`'s docstring — *"Anything outside that interval was put
there by something other than this loop."* It was our own power. The
docstring now says what the predicate does guarantee (this cycle's command
does not account for this cycle's reading) and states the coast-down as its
known blind spot.
2. `control.py`, in `compute()` — *"SO THE BOUND BELONGS TO (b) AND ONLY TO
(b)"*. It fired in case (a). The comment now says the bound is a reason to
stop believing (a), not a proof of (b), and that the release is written to be
survivable when the inference is wrong.
3. **DOCS.md — *"If you see `freeze-released` in the action log, look for the
second writer."*** This is the one that reaches a person, and on a
single-inverter install it sent them hunting something that does not exist.
Replaced by a section that gives the innocent causes first and the second
writer only when the state stands.