SAFETY-13: the bound came from the wrong half of a two-sided measurement
checks / unit (pull_request) Successful in 5m34s
NOTES.md 5.10 measured the 1.78 kW step BOTH ways - "Up: ~18 s from step to deadband. Down: ~23 s" (NOTES.md:1550). SAFETY-39 takes 18 correctly: its bound is a REFUSAL and the looser number refuses less. This branch reused PLANT_SETTLE_S for the opposite job - how long the plant may still be the EXPLANATION for a divergence - where the conservative half is the longer one. ceil(23/2) = 12, not 9, and being short there does not refuse anything, it accuses. The false positive is real and is measured here. One inverter, one compute(), one plant, no second writer anywhere in the harness: the command falls through zero while the pack is still coasting the old way, unasked_power() calls our own power "unasked", the counter reaches 9 while it is still coasting, and the law emits "freeze-released". At the plant's own measured 18 s/23 s shape, over 272 load-step pairs, the 9-cycle bound fires in 62 and the 12-cycle bound in 2. PLANT_SETTLE_DOWN_S = 23.0 is added beside PLANT_SETTLE_S = 18.0, because the plant's settling time is a PAIR and each bound has to say which half it means and why. SETTLE_CYCLES = ceil(PLANT_SETTLE_DOWN_S / LOOP_TICK_S) = 12. It is no longer the reciprocal of SLEW_RAIL_FRAC; that was a coincidence of both reading the same half, and test_control.py now asserts the inequality. _SAT_COUNT_CAP moves with it, 10 -> 13. config.yaml accepts saturation_cycles as int(1,10), so the whole accepted range is now strictly BELOW the bound and the degenerate configuration this branch used to document no longer exists - pinned against config.yaml's own schema line. Three shipped statements were falsified by that measurement and are rewritten, not renumbered - at 12 the residual is smaller, not zero: unasked_power()'s docstring said anything outside the interval "was put there by something other than this loop". It was our own power: eight cycles after a +1990 W command the command is 0 and the pack still reads +522.3 W. control.py said "SO THE BOUND BELONGS TO (b) AND ONLY TO (b)". It fired in case (a). DOCS.md told an operator "if you see freeze-released, look for the second writer" - on a single-inverter install, hunting something that does not exist. Replaced by a section that gives the innocent causes first (a large load or PV swing; a plant slower than the one measured, 8/320 scenarios at 23 s rising to 268/320 at 50 s) and the second writer only when the state STANDS. Round 1's own results are kept and re-graded, not weakened. The release/1.0 sweep had to widen to reach the new bound (3780 cases): 3267 bit-identical, 432 releases, 27 command changes - all still charge starts from prev_w == 0 - and 81 differing in the saturation counter alone, which nothing downstream can read. The card's case releases on the twelfth saturated cycle instead of the ninth and settles at the same -1190 W against the same frozen integrator. Also corrected, because they were claims and did not reproduce: the coverage table's "output freeze" row was 11, and the mutation form its own note describes gives 6 on this tree, 6 on the first SAFETY-13 commit and 2 on release/1.0; the detector row was left at 11 and is 15; the frozen = False footnote was left at 10 and is 13. And section 6 reported 107 625 as "released states" when it is the number of states SWEPT - 67 500 of them release, and both are counted now. Nothing here reached the inverter. 22/22 test files pass in goodwe-addon-ci, tree rsynced to a plain path, mounted :ro, python3 -B, __pycache__ purged and printed first (0 dirs / 0 .pyc; the worktree carries none). Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
6c4565659b |
SAFETY-13: the output freeze gets an exit, and only where it needs one
checks / unit (pull_request) Successful in 5m30s
While the loop is frozen the command's magnitude may fall but never rise. At prev_w == 0 there is no magnitude left to fall, so a charge cannot START. That refusal is deliberate and it is kept: the inverter reporting power we did not command means another writer is on the actuator, which is the §1.5 non-goal. What it did not have was an END - nothing cleared it but the other writer leaving. Reproduced on release/1.0 @ |