Review approved and found four things worth fixing. Three are cosmetic; the fourth is the same defect this card is about, one level up. ⚠️ THE FLOOR WAS PRINTED AS 59 AND ASSERTED AS `> 15`. So a manifest change dropping the required count to 20 would have passed while the sentence beside it still said 59 - a number displayed but not graded, which is exactly what let UX-01's AC 3 survive review in the first place, and exactly the shape `test_translations.py` was already fixed for. Now DERIVED and graded in two separate assertions, because they are two different claims: 1. `_EXPECT_REQ = len(schema) - len(_OPTIONAL)`, where optional is Supervisor's own rule - a `?` suffix, plus `inverters` because `UiOptions` marks a list optional - asserted EQUAL to Supervisor's required count. The printed number is computed, so it cannot go stale. 2. ⚠️ AND THE WITHDRAWAL'S PREMISE, SEPARATELY. The equality alone is not enough and I checked why: both sides read the same `?` convention, so marking a key optional moves BOTH and it stays green - measured, by making `slew_w` optional and watching it pass. That grades Supervisor agreeing with us, NOT the thing AC 3 was withdrawn for. The second assertion grades the premise: the floor is still far above the ~15 AC 3 asked for, and if it ever is not, the withdrawal needs re-arguing rather than re-asserting. Driven, both directions, against the real 2026.08.0 image: clean PASS "floor is DERIVED: 71 schema keys minus 12 optional ones is 59, and Supervisor's own required flag agrees" premise threshold 15 -> 40 FAIL "the floor of 59 is still far above the ~40 AC 3 asked for" Also: a dangling reference to `DECISIONS/UX-04-hiding-and-the-deepmerge.md`, which was never the filename shipped, and `DOCS.md` still saying section F "prints" what it now grades. Not changed, and review agreed both are disclosed rather than defects: the pair-keyed ledger cannot see a SECOND site for a pair it already holds (the site count can grow while the pair set cannot), and the probe's assertions run by hand rather than in CI because they need the Supervisor image - the same status as before this card, not a regression. Suite: 27 files, all pass. Probe: all cases passed on ghcr.io/home-assistant/amd64-hassio-supervisor:2026.08.0, --network none. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
GoodWe RS485 Controller — Home Assistant add-on repository
Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.
repository.yaml add-on repository metadata
goodwe_controller/ the add-on
config.yaml manifest + options schema (the per-site config form)
app/ the controller
control.py the control law — pure functions, no I/O
maintenance.py the monthly cycle state machine
hass.py Supervisor/Core API access
store.py persistent state in /data
mqtt.py optional status entities
web.py ingress UI — routes only, status and configuration
config_page.py the configuration page's markup, style and script
configui.py its field model, built from the Supervisor's own
schema + translations — owns no key, label or rule
selfconfig.py reading and writing this add-on's own options,
with the validate-first / compare-and-swap gate
main.py orchestration, heartbeat, failsafe behaviour
test_control.py runnable checks — no framework needed
test_maintenance.py runnable checks — walks a full cycle in fake time
DOCS.md the add-on's documentation tab
MUTATION.md how to run a mutation so the result means something
tools/mutation_run.sh the mutation harness - purges bytecode, then grades
tools/supervisor_selfapi_probe.py what the Supervisor really permits and
returns, run against its own release image
firmware/goodwe-master.yaml ESPHome config for the T-CAN485
estop/rs485_log.py optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf the guide techs carry (10pp, A4)
docs/build_guide.py its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md how to edit and rebuild the guide
Picking this up after a break? Read HANDOVER.md first — current state,
what is known broken, and what to do next.
Install
Settings → Add-ons → Add-on store → ⋮ → Repositories → add
https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install GoodWe RS485 Controller.
⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
goodwe_controller/ into the machine's /addons/ folder, then
ha store reload — it appears as a Local add-on.
⚠️ Bump version: in goodwe_controller/config.yaml for every change.
Supervisor keys the built image by that version, so without a bump it silently
reuses the old image and your fix appears not to work — on your bench and on
every client's machine.
Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.
Read this first
The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.
Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:
- ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
- Wind-down before firmware updates — 0 W written before the update starts.
- RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.
Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md
§10 signed.
Development
The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:
cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py
Both must pass before shipping any change. To prove a check bites - the way
almost every claim in this repository was established - mutate the module and
run tools/mutation_run.sh, which clears __pycache__ first. It is not
optional: a same-size edit reverted inside one second leaves CPython reusing the
old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md
has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre —
each assertion corresponds to a rule whose absence produced an observed failure
on real hardware, and the comments in control.py say which.
Compatibility
Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:
| tag | platform | verdict |
|---|---|---|
ESU EMU ESA BPS BPU EMJ IJL |
105 — ES/EM/BP, AA55-era meter bus | supported |
SPB SPN |
745 — SBP G2 (GW…-SBP-20) |
no |
ESN ESC |
745 — ES G2 (GW…-ES-20) |
no |
ETU EHU BTU … |
205/745/753 — ET/EH/BT hybrids | no |
SDT DST MSU NSU … |
PV-only inverters — no battery to control | no |
A "-20" or "G2" suffix means a different platform with a different meter
protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which
is also what Home Assistant's own integration uses to pick a protocol.
- GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
- The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.