glenn schrooyenandClaude Opus 5 f4914a174a
checks / unit (pull_request) Successful in 2m38s
TARIFF-01: measure the month's billed peak, and make it survive a restart
The 15-minute block average was already built and unwired. p1.QuarterAverager
computes clock-aligned 900 s blocks, time-weighted over irregular telegram
spacing, offtake-only and per-phase; P1Ingest.blocks was a 96-entry list in
memory that a restart erased. So this is the persistence and the monthly
reduction, not a second accumulator - a second one would be a second source of
truth for the exact quantity the money depends on.

BLOCKS, NOT A SLIDING WINDOW. The card says "rolling"; 9.1 bills "the highest
15-minute average offtake" and states its own worked case per QUARTER - one
4998 W quarter moving a monthly peak from 4832 to 5013 W. A trailing window
reports a peak the meter never bills, and reports it HIGH: a burst straddling
:15 fills the window completely while contributing to two block averages at
partial weight.

DELIVERED, NOT INTENDED. tariff.py only ever sees P1Sample - the meter's own
reading - and never a setpoint. SAFETY-20's open question does not arise for a
capacity tariff: the utility integrates the current that flowed.

AN UNREADABLE STORE IS NOT A ZERO PEAK. peak() answers OBSERVED / NO_RECORD /
NOT_OBSERVED with peak_w None unless observed, which is riglock.holder()'s fix
applied to something that spends money. A peak read as 0 W hands SAFETY-07
maximum headroom and disarms the guard at the moment its own storage breaks.

Restart mid-block resumes the accumulator through a new snapshot()/restore()
pair, checkpointed every 15 s and cleared in the same breath as a block close.
The held sample keeps its ORIGINAL timestamp, so an outage is integrated under
the same max_hold_s rule a running process would apply. quarter_start is the
primary key and a re-bank may only ever RAISE a figure.

Calendar months are LOCAL: a quarter starting 22:15 UTC on 31 August bills in
September.

No new option (the limit is the existing peak_cap_w), so config.yaml and
validate.py are untouched and CFG-03 is not widened. No second peak entity:
peak_forecast_entity stays the input to maintenance_charge_floor(), because
repointing that consumer changes what moves energy and belongs to SAFETY-07.

AC 3 is NOT met. It asks for 30 days of replay; two days of this house's real
meter exist and are committed here. test_tariff.py part 9 replays them, reports
the percentage next to the sample size in days, and asserts nothing about 95 %.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
2026-08-30 19:13:58 +02:00

GoodWe RS485 Controller — Home Assistant add-on repository

Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.

repository.yaml            add-on repository metadata
goodwe_controller/         the add-on
  config.yaml              manifest + options schema (the per-site config form)
  app/                     the controller
    control.py             the control law — pure functions, no I/O
    maintenance.py         the monthly cycle state machine
    hass.py                Supervisor/Core API access
    store.py               persistent state in /data
    mqtt.py                optional status entities
    web.py                 ingress UI
    main.py                orchestration, heartbeat, failsafe behaviour
  test_control.py          runnable checks — no framework needed
  test_maintenance.py      runnable checks — walks a full cycle in fake time
  DOCS.md                  the add-on's documentation tab
firmware/goodwe-master.yaml  ESPHome config for the T-CAN485
estop/rs485_log.py           optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf  the guide techs carry (10pp, A4)
docs/build_guide.py          its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md             how to edit and rebuild the guide

Picking this up after a break? Read HANDOVER.md first — current state, what is known broken, and what to do next.

Install

Settings → Add-ons → Add-on store → ⋮ → Repositories → add

https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon

then install GoodWe RS485 Controller.

⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it anonymously; against a private repo the store shows nothing and gives no useful error. If it must stay private, install locally instead: copy goodwe_controller/ into the machine's /addons/ folder, then ha store reload — it appears as a Local add-on.

⚠️ Bump version: in goodwe_controller/config.yaml for every change. Supervisor keys the built image by that version, so without a bump it silently reuses the old image and your fix appears not to work — on your bench and on every client's machine.

Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.

Read this first

The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.

Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:

  1. ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
  2. Wind-down before firmware updates — 0 W written before the update starts.
  3. RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.

Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md §10 signed.

Development

The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:

cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py

Both must pass before shipping any change. They are not unit-test theatre — each assertion corresponds to a rule whose absence produced an observed failure on real hardware, and the comments in control.py say which.

Compatibility

Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:

tag platform verdict
ESU EMU ESA BPS BPU EMJ IJL 105 — ES/EM/BP, AA55-era meter bus supported
SPB SPN 745 — SBP G2 (GW…-SBP-20) no
ESN ESC 745 — ES G2 (GW…-ES-20) no
ETU EHU BTU … 205/745/753 — ET/EH/BT hybrids no
SDT DST MSU NSU … PV-only inverters — no battery to control no

A "-20" or "G2" suffix means a different platform with a different meter protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which is also what Home Assistant's own integration uses to pick a protocol.

  • GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
  • The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.