NOTES.md 5.10 measured the 1.78 kW step BOTH ways - "Up: ~18 s from step to deadband. Down: ~23 s" (NOTES.md:1550). SAFETY-39 takes 18 correctly: its bound is a REFUSAL and the looser number refuses less. This branch reused PLANT_SETTLE_S for the opposite job - how long the plant may still be the EXPLANATION for a divergence - where the conservative half is the longer one. ceil(23/2) = 12, not 9, and being short there does not refuse anything, it accuses. The false positive is real and is measured here. One inverter, one compute(), one plant, no second writer anywhere in the harness: the command falls through zero while the pack is still coasting the old way, unasked_power() calls our own power "unasked", the counter reaches 9 while it is still coasting, and the law emits "freeze-released". At the plant's own measured 18 s/23 s shape, over 272 load-step pairs, the 9-cycle bound fires in 62 and the 12-cycle bound in 2. PLANT_SETTLE_DOWN_S = 23.0 is added beside PLANT_SETTLE_S = 18.0, because the plant's settling time is a PAIR and each bound has to say which half it means and why. SETTLE_CYCLES = ceil(PLANT_SETTLE_DOWN_S / LOOP_TICK_S) = 12. It is no longer the reciprocal of SLEW_RAIL_FRAC; that was a coincidence of both reading the same half, and test_control.py now asserts the inequality. _SAT_COUNT_CAP moves with it, 10 -> 13. config.yaml accepts saturation_cycles as int(1,10), so the whole accepted range is now strictly BELOW the bound and the degenerate configuration this branch used to document no longer exists - pinned against config.yaml's own schema line. Three shipped statements were falsified by that measurement and are rewritten, not renumbered - at 12 the residual is smaller, not zero: unasked_power()'s docstring said anything outside the interval "was put there by something other than this loop". It was our own power: eight cycles after a +1990 W command the command is 0 and the pack still reads +522.3 W. control.py said "SO THE BOUND BELONGS TO (b) AND ONLY TO (b)". It fired in case (a). DOCS.md told an operator "if you see freeze-released, look for the second writer" - on a single-inverter install, hunting something that does not exist. Replaced by a section that gives the innocent causes first (a large load or PV swing; a plant slower than the one measured, 8/320 scenarios at 23 s rising to 268/320 at 50 s) and the second writer only when the state STANDS. Round 1's own results are kept and re-graded, not weakened. The release/1.0 sweep had to widen to reach the new bound (3780 cases): 3267 bit-identical, 432 releases, 27 command changes - all still charge starts from prev_w == 0 - and 81 differing in the saturation counter alone, which nothing downstream can read. The card's case releases on the twelfth saturated cycle instead of the ninth and settles at the same -1190 W against the same frozen integrator. Also corrected, because they were claims and did not reproduce: the coverage table's "output freeze" row was 11, and the mutation form its own note describes gives 6 on this tree, 6 on the first SAFETY-13 commit and 2 on release/1.0; the detector row was left at 11 and is 15; the frozen = False footnote was left at 10 and is 13. And section 6 reported 107 625 as "released states" when it is the number of states SWEPT - 67 500 of them release, and both are counted now. Nothing here reached the inverter. 22/22 test files pass in goodwe-addon-ci, tree rsynced to a plain path, mounted :ro, python3 -B, __pycache__ purged and printed first (0 dirs / 0 .pyc; the worktree carries none). Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
GoodWe RS485 Controller — Home Assistant add-on repository
Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.
repository.yaml add-on repository metadata
goodwe_controller/ the add-on
config.yaml manifest + options schema (the per-site config form)
app/ the controller
control.py the control law — pure functions, no I/O
maintenance.py the monthly cycle state machine
hass.py Supervisor/Core API access
store.py persistent state in /data
mqtt.py optional status entities
web.py ingress UI
main.py orchestration, heartbeat, failsafe behaviour
test_control.py runnable checks — no framework needed
test_maintenance.py runnable checks — walks a full cycle in fake time
DOCS.md the add-on's documentation tab
MUTATION.md how to run a mutation so the result means something
tools/mutation_run.sh the mutation harness - purges bytecode, then grades
firmware/goodwe-master.yaml ESPHome config for the T-CAN485
estop/rs485_log.py optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf the guide techs carry (10pp, A4)
docs/build_guide.py its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md how to edit and rebuild the guide
Picking this up after a break? Read HANDOVER.md first — current state,
what is known broken, and what to do next.
Install
Settings → Add-ons → Add-on store → ⋮ → Repositories → add
https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install GoodWe RS485 Controller.
⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
goodwe_controller/ into the machine's /addons/ folder, then
ha store reload — it appears as a Local add-on.
⚠️ Bump version: in goodwe_controller/config.yaml for every change.
Supervisor keys the built image by that version, so without a bump it silently
reuses the old image and your fix appears not to work — on your bench and on
every client's machine.
Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.
Read this first
The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.
Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:
- ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
- Wind-down before firmware updates — 0 W written before the update starts.
- RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.
Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md
§10 signed.
Development
The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:
cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py
Both must pass before shipping any change. To prove a check bites - the way
almost every claim in this repository was established - mutate the module and
run tools/mutation_run.sh, which clears __pycache__ first. It is not
optional: a same-size edit reverted inside one second leaves CPython reusing the
old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md
has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre —
each assertion corresponds to a rule whose absence produced an observed failure
on real hardware, and the comments in control.py say which.
Compatibility
Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:
| tag | platform | verdict |
|---|---|---|
ESU EMU ESA BPS BPU EMJ IJL |
105 — ES/EM/BP, AA55-era meter bus | supported |
SPB SPN |
745 — SBP G2 (GW…-SBP-20) |
no |
ESN ESC |
745 — ES G2 (GW…-ES-20) |
no |
ETU EHU BTU … |
205/745/753 — ET/EH/BT hybrids | no |
SDT DST MSU NSU … |
PV-only inverters — no battery to control | no |
A "-20" or "G2" suffix means a different platform with a different meter
protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which
is also what Home Assistant's own integration uses to pick a protocol.
- GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
- The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.