SAFETY-13: the bound came from the wrong half of a two-sided measurement
NOTES.md 5.10 measured the 1.78 kW step BOTH ways - "Up: ~18 s from step to
deadband. Down: ~23 s" (NOTES.md:1550). SAFETY-39 takes 18 correctly: its
bound is a REFUSAL and the looser number refuses less. This branch reused
PLANT_SETTLE_S for the opposite job - how long the plant may still be the
EXPLANATION for a divergence - where the conservative half is the longer one.
ceil(23/2) = 12, not 9, and being short there does not refuse anything, it
accuses.

The false positive is real and is measured here. One inverter, one compute(),
one plant, no second writer anywhere in the harness: the command falls through
zero while the pack is still coasting the old way, unasked_power() calls our
own power "unasked", the counter reaches 9 while it is still coasting, and the
law emits "freeze-released". At the plant's own measured 18 s/23 s shape, over
272 load-step pairs, the 9-cycle bound fires in 62 and the 12-cycle bound in 2.

  PLANT_SETTLE_DOWN_S = 23.0 is added beside PLANT_SETTLE_S = 18.0, because
  the plant's settling time is a PAIR and each bound has to say which half it
  means and why.
  SETTLE_CYCLES = ceil(PLANT_SETTLE_DOWN_S / LOOP_TICK_S) = 12. It is no
  longer the reciprocal of SLEW_RAIL_FRAC; that was a coincidence of both
  reading the same half, and test_control.py now asserts the inequality.
  _SAT_COUNT_CAP moves with it, 10 -> 13. config.yaml accepts
  saturation_cycles as int(1,10), so the whole accepted range is now strictly
  BELOW the bound and the degenerate configuration this branch used to
  document no longer exists - pinned against config.yaml's own schema line.

Three shipped statements were falsified by that measurement and are rewritten,
not renumbered - at 12 the residual is smaller, not zero:

  unasked_power()'s docstring said anything outside the interval "was put
  there by something other than this loop". It was our own power: eight cycles
  after a +1990 W command the command is 0 and the pack still reads +522.3 W.
  control.py said "SO THE BOUND BELONGS TO (b) AND ONLY TO (b)". It fired in
  case (a).
  DOCS.md told an operator "if you see freeze-released, look for the second
  writer" - on a single-inverter install, hunting something that does not
  exist. Replaced by a section that gives the innocent causes first (a large
  load or PV swing; a plant slower than the one measured, 8/320 scenarios at
  23 s rising to 268/320 at 50 s) and the second writer only when the state
  STANDS.

Round 1's own results are kept and re-graded, not weakened. The release/1.0
sweep had to widen to reach the new bound (3780 cases): 3267 bit-identical,
432 releases, 27 command changes - all still charge starts from prev_w == 0 -
and 81 differing in the saturation counter alone, which nothing downstream can
read. The card's case releases on the twelfth saturated cycle instead of the
ninth and settles at the same -1190 W against the same frozen integrator.

Also corrected, because they were claims and did not reproduce: the coverage
table's "output freeze" row was 11, and the mutation form its own note
describes gives 6 on this tree, 6 on the first SAFETY-13 commit and 2 on
release/1.0; the detector row was left at 11 and is 15; the frozen = False
footnote was left at 10 and is 13. And section 6 reported 107 625 as "released
states" when it is the number of states SWEPT - 67 500 of them release, and
both are counted now.

Nothing here reached the inverter. 22/22 test files pass in goodwe-addon-ci,
tree rsynced to a plain path, mounted :ro, python3 -B, __pycache__ purged and
printed first (0 dirs / 0 .pyc; the worktree carries none).

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-06 18:32:03 +02:00

GoodWe RS485 Controller — Home Assistant add-on repository

Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.

repository.yaml            add-on repository metadata
goodwe_controller/         the add-on
  config.yaml              manifest + options schema (the per-site config form)
  app/                     the controller
    control.py             the control law — pure functions, no I/O
    maintenance.py         the monthly cycle state machine
    hass.py                Supervisor/Core API access
    store.py               persistent state in /data
    mqtt.py                optional status entities
    web.py                 ingress UI
    main.py                orchestration, heartbeat, failsafe behaviour
  test_control.py          runnable checks — no framework needed
  test_maintenance.py      runnable checks — walks a full cycle in fake time
  DOCS.md                  the add-on's documentation tab
  MUTATION.md              how to run a mutation so the result means something
  tools/mutation_run.sh    the mutation harness - purges bytecode, then grades
firmware/goodwe-master.yaml  ESPHome config for the T-CAN485
estop/rs485_log.py           optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf  the guide techs carry (10pp, A4)
docs/build_guide.py          its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md             how to edit and rebuild the guide

Picking this up after a break? Read HANDOVER.md first — current state, what is known broken, and what to do next.

Install

Settings → Add-ons → Add-on store → ⋮ → Repositories → add

https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon

then install GoodWe RS485 Controller.

⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it anonymously; against a private repo the store shows nothing and gives no useful error. If it must stay private, install locally instead: copy goodwe_controller/ into the machine's /addons/ folder, then ha store reload — it appears as a Local add-on.

⚠️ Bump version: in goodwe_controller/config.yaml for every change. Supervisor keys the built image by that version, so without a bump it silently reuses the old image and your fix appears not to work — on your bench and on every client's machine.

Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.

Read this first

The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.

Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:

  1. ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
  2. Wind-down before firmware updates — 0 W written before the update starts.
  3. RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.

Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md §10 signed.

Development

The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:

cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py

Both must pass before shipping any change. To prove a check bites - the way almost every claim in this repository was established - mutate the module and run tools/mutation_run.sh, which clears __pycache__ first. It is not optional: a same-size edit reverted inside one second leaves CPython reusing the old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre — each assertion corresponds to a rule whose absence produced an observed failure on real hardware, and the comments in control.py say which.

Compatibility

Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:

tag platform verdict
ESU EMU ESA BPS BPU EMJ IJL 105 — ES/EM/BP, AA55-era meter bus supported
SPB SPN 745 — SBP G2 (GW…-SBP-20) no
ESN ESC 745 — ES G2 (GW…-ES-20) no
ETU EHU BTU … 205/745/753 — ET/EH/BT hybrids no
SDT DST MSU NSU … PV-only inverters — no battery to control no

A "-20" or "G2" suffix means a different platform with a different meter protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which is also what Home Assistant's own integration uses to pick a protocol.

  • GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
  • The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.