glenn schrooyenandClaude Opus 5 4bd659c499 TEL-01 review fixes: stop the age sensor tripping installs that have no meter
T-1, and it was a fleet-wide trip to zero. publish() emitted p1_age
unconditionally, and published_age_s counts from P1Ingest.__init__ when no
sample has ever arrived. With meter_source defaulting to off, every existing
install would have published sensor.p1_sample_age_s climbing without bound; the
ESP32 does `has_state() && state >= max_age_s` and forces the layer-1 failsafe,
so each of them would have pinned its inverter at 0 W within 30 s. Exactly the
opposite of the zero-regression the off default was for. The key is now omitted
from the payload AND from MQTT discovery when P1 is off, so the entity does not
exist at all - which is the status quo, and what has_state() is testing for.
The predicate is one function, is_enabled(), because the grid reading, the task
start and the discovery announcement have to agree or this comes back.

T-2, connect no longer manufactures a sample. get_states returns whatever HA
currently holds, which after a Core restart is a RestoreEntity value of unknown
age; stamping it with ingest_ts=now reset the age and reported a fresh meter
that could have been dead for an hour. run()'s own docstring already said a
reconnect must emit nothing - the code disagreed with it, and a test asserted
the violation. The cache is still primed, so the first real state_changed
builds a complete sample; the age just stays honest until one arrives.

T-3, gaps are no longer filled with the last held value. The averager held a
sample forward across any interval, so a meter dying at 5 kW and returning ten
minutes later credited 5 kW x 600 s to the capacity-tariff accumulator - a
fabricated peak on a permanent record. The hold is capped at max_age_s: past
that the stretch is walked so block boundaries still land correctly, but
nothing accumulates and elapsed does not grow, which is what finally makes the
comment about a gap dragging the billed average down true. Same threshold for
control and billing: a reading too old to steer by is too old to bill by.

T-4, the out-of-order/duplicate guard is covered. It was untested, and the
reason is worth recording: the obvious assertion passes without the guard,
because the negative interval is separately refused by the covered > 0 test.
What the guard prevents is the timestamp REWIND, which only shows up one sample
later as a re-integrated window. The test now goes one sample later.

T-6, DOCS was wrong about latency. meter_max_age_s and stale_input_s stack, so
meter death to 0 W is 45 s and not 30. Documented as a table with both clocks.

Also documented the T-5 asymmetry rather than papering over it: the age
measures arrival, not change, so a stuck MQTT bridge republishing its last
telegram still looks fresh. Correct on ha_dsmr, not detectable on mqtt_p1
without a change-detector. Written up as a known limit.

Writing the T-1 test caught a second defect in the test itself: it recorded
only MQTT topics, and object_id lives in the payload, so "the age sensor is not
announced" had been passing for the wrong reason.

test_p1.py: 99 -> 122 checks. 14 mutations run, all 14 red, files restored
byte-identical - including one per fix above.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 23:16:31 +02:00

244 lines
12 KiB
Markdown
Raw Permalink Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# GoodWe RS485 Controller
Drives a GoodWe ES/BP battery inverter over its RS485 meter bus: holds net grid
exchange at zero, and runs a monthly battery maintenance cycle so the BMS can
balance cells and recalibrate its coulomb counter.
Installers: read `FIELD-GUIDE.md` in the repository. It is not optional reading —
it contains the commissioning gates and the failure modes.
## Before you start
You need:
- A GoodWe **ES / BP family** inverter (AA55 / RS485 meter-bus generation)
- The vendor's meter-emulating controller **disconnected** from the bus
- A T-CAN485 (ESP32) flashed with `firmware/goodwe-master.yaml`
- A grid-power sensor already working in Home Assistant, updating every ~510 s
## The safety model, in short
The inverter **holds its last command forever** — it has no meter-timeout. So:
- The ESP32 commands 0 W if this add-on stops refreshing for ~30 s, and keeps
commanding it.
- This add-on commands 0 W when its inputs go missing, when you stop control,
and when it shuts down.
- The **optional RS485 e-stop** is the only thing that covers this machine
dying. Without it, a failed host leaves the battery latched at its last
command until someone intervenes.
**If anything looks wrong: stop the add-on.** That commands 0 W and the
hardware holds it there.
## Configuration
### Sources
| option | required | meaning |
|---|---|---|
| `meter_entity` | yes | Net grid power. **Positive must mean importing** |
| `meter_invert` | | Flip the sign if the meter reports the other way |
| `soc_entity` | yes | Battery state of charge — use the **ESP32's own read** |
| `batt_entity` | yes | Battery power — again the ESP32's read, `+` = discharging |
| `batt_invert` | | Flip if needed |
| `setpoint_entity` | yes | The ESPHome `number.*_goodwe_setpoint_w` |
Use the ESP32's readings rather than the inverter's cloud or dongle sensors:
those serve cached values, and a stale reading here ends the maintenance charge
phase having charged nothing.
### P1 meter ingestion
`meter_entity` above expects one signed sensor, which usually means a template
someone wrote by hand. A Belgian P1 meter does not publish one: it publishes two
**unsigned** registers, consumption and injection. Setting `meter_source` moves
that subtraction into the add-on, where it is done once and tested, and replaces
`meter_entity` entirely.
| option | default | meaning |
|---|---|---|
| `meter_source` | `off` | `off` keeps `meter_entity`. `ha_dsmr` subscribes to the DSMR integration over the HA WebSocket; `mqtt_p1` reads a topic |
| `meter_phases` | 1 | 1 or 3. Must match the telegram, or every telegram is rejected and logged |
| `meter_max_age_s` | 30 | Beyond this the reading is stale and grid power reads as *missing*. On its own it does **not** command 0 W — see the timing note below. It is also the longest a reading is held forward into the 15-minute average |
| `meter_mqtt_topic` | | `mqtt_p1` only |
| `p1_import_entity` | | The **unsigned** consumption sensor. Do not point this at a signed template |
| `p1_export_entity` | | The **unsigned** injection sensor |
| `p1_phase_import_entities` | `[]` | L1..L3, in order. Needed for the capacity-tariff peak on a three-phase connection |
| `p1_phase_export_entities` | `[]` | L1..L3, in order |
#### How long a dead meter takes to reach 0 W
`meter_max_age_s` and `stale_input_s` **stack**. They are two different clocks
and neither one is the whole answer:
| step | option | default |
|---|---|---|
| telegrams stop, P1 sample goes stale, grid power starts reading *missing* | `meter_max_age_s` | 30 s |
| inputs have been missing long enough for the loop to command 0 W | `stale_input_s` | 15 s |
| **total, meter death → 0 W commanded by this add-on** | | **45 s** |
So in P1 mode `stale_input_s` is *not* "how long inputs may be missing before
commanding 0 W" measured from the meter dying — it is measured from the moment
the P1 sample already went stale. Size the pair together: the ESP32's own
watchdog commands 0 W after ~30 s of silence from this add-on regardless, and
that layer is unaffected by either option.
There is **no fallback to an inverter-side power figure**, deliberately. The
inverter's own AC power tracks its battery almost perfectly and the real meter
hardly at all, so a controller that failed over to it would be regulating
against its own output while looking healthy.
The `mqtt_p1` payload is one JSON object per telegram, and the schema is strict —
a key it does not recognise is a telegram from something other than what was
tested, and guessing a key here means guessing a kilowatt:
```json
{"import_w": 1234.0,
"export_w": 0.0,
"phases": [{"import_w": 500, "export_w": 0},
{"import_w": 400, "export_w": 0},
{"import_w": 334, "export_w": 0}],
"timestamp": "2026-08-24T18:00:05+02:00"}
```
`phases` and `timestamp` are optional; `timestamp` must carry a UTC offset. Where
it is present it is used for the age, which is what stops a retained message
replayed on reconnect from presenting a ten-minute-old reading as current.
#### `sensor.p1_sample_age_s`
Published over MQTT discovery whenever a broker is available: **seconds since the
newest accepted telegram**, refreshed every second rather than only when a
telegram lands. The ESP32's stale-input watchdog subscribes to this exact entity
id, so do not rename it.
The reason it is recomputed against the clock is that Home Assistant only pushes
a state when the state *changes*. A meter sitting at a genuinely constant reading
emits nothing, which is indistinguishable — to anything watching the value — from
a meter that has died. Watching the age instead separates the two: it climbs when
telegrams stop and resets when they arrive, whatever the reading says.
The entity is only created when `meter_source` is not `off`. With P1 ingestion
disabled there is nothing feeding it, and an age sensor climbing with no ingester
behind it would trip the firmware watchdog on a system that is working fine.
> **Known limit, `mqtt_p1` only.** The age measures *arrival*, not change. On the
> `ha_dsmr` path that is exactly right: a frozen meter emits no `state_changed`,
> so nothing arrives and the age climbs. On the MQTT path a bridge that is stuck
> republishing its last telegram keeps arriving, so the age stays near zero and a
> frozen meter still looks fresh. Detecting *that* needs a change-detector rather
> than an arrival-detector, and it is not in this version. Prefer `ha_dsmr` where
> both are available.
### Control
| option | default | meaning |
|---|---|---|
| `max_w` | 2000 | Hard limit on what may be commanded. Start low, raise after commissioning |
| `gain` | 0.6 | Correction per cycle. **At the limit — do not raise** |
| `slew_w` | 1000 | Maximum change per cycle |
| `deadband_w` | 15 | Ignore errors smaller than this |
| `target_grid_w` | -10 | What the meter should rest at. Negative = a slight export |
| `step_w` | 10 | Quantisation |
| `saturation_w` | 500 | Divergence that counts as "the inverter is at a limit" |
| `saturation_cycles` | 3 | How many consecutive cycles before freezing. A cycle is one *changed* meter reading, not a fixed period - see the note below. **Do not set to 1** |
| `integrator_max_w` | 0 | Bound on the loop's accumulator, and 0 means "same as `max_w`". Caps how much stale error can be waiting to unwind when the sign flips. **Do not raise it above `max_w`** - the output clamp already bounds what is commanded, so the only thing extra headroom buys is more cycles of wrong-direction power after every saturation event. Lowering it below `max_w` is the useful direction |
| `heartbeat_s` | 10 | Refresh interval; must stay well under the firmware watchdog |
| `stale_input_s` | 15 | How long inputs may be missing before commanding 0 W. In P1 mode this clock starts only *after* `meter_max_age_s` has already expired — the two stack, see "How long a dead meter takes to reach 0 W" |
| `auto_start` | false | Start controlling on boot (only after commissioning) |
#### Saturation is counted in cycles, not seconds
The specification states the saturation window as **"> 10 s"**. This add-on counts
**cycles** instead, and that is a deliberate, accepted deviation rather than an
oversight - the acceptance criterion is not met as literally written.
A cycle here is one *changed* meter reading: the controller only runs the loop when the
meter value differs from the previous poll. At the reference P1's ~5 s update rate the
default of 3 cycles is usually around 15 s, but there is **no guaranteed wall-clock
window** - a meter that repeats the same value stalls the counter for as long as it
repeats.
Two reasons that is acceptable:
- the control law is a pure function with no clock, which is what makes it testable
without hardware, and a seconds-based window would have to live in the controller;
- a stalled counter is a detection-latency limit and not a runaway risk. The condition
that stalls it - an unchanging meter - stops the whole loop, so nothing accumulates
while it is stalled.
If a guaranteed window matters on your site, raise `saturation_cycles` for a fast meter,
and treat the figure as "N meter updates" rather than "N seconds".
#### Why `target_grid_w` is not zero
The deadband is a one-way ratchet: any resting point inside it holds until
something disturbs it. Import and export are **separate registers on the
meter**, so a rest point of +14 W is billed for every second it holds and no
amount of export cancels it - 14 W all day is 0.34 kWh.
Biasing the target below zero moves that residue into the export register,
which is not billed. The resting band becomes `target ± deadband`, so:
| `target_grid_w` | resting band | worst billed leak | export given away |
|---|---|---|---|
| 0 | -15 … +15 W | ~15 W (0.35 kWh/day) | none |
| **-10** | -25 … +5 W | ~5 W (0.12 kWh/day) | ~10 W |
| -15 | -30 … 0 W | none | ~15 W (0.36 kWh/day) |
Set it to `-deadband_w` if injection is worth nothing to you and you would
rather give the energy away than buy it back. Set it to `0` if you are paid
properly for export, or if you are debugging and want the loop centred.
⚠️ This is a **billing** knob, not a speed knob. If import is arriving in
bursts rather than as a trickle, the cause is tracking lag, and this will not
help - see "Why the tuning is what it is".
### Maintenance
| option | default | meaning |
|---|---|---|
| `maintenance_enabled` | false | Enable the monthly cycle |
| `maintenance_interval_days` | 28 | Minimum gap between cycles |
| `maintenance_start_hour` | 10 | Hour of day a due cycle begins |
| `maintenance_discharge_w` | 2500 | Drain rate (exports the surplus) |
| `maintenance_charge_w` | 2500 | Charge ceiling, capped again by peak headroom |
| `maintenance_soc_floor` | 11 | Drain target — stay just above the inverter's own floor |
| `maintenance_soc_target` | 99 | Charge target |
| `maintenance_hold_min` | 120 | Hold at full so the BMS can balance |
### Tariff (all optional)
| option | meaning |
|---|---|
| `peak_forecast_entity` | Quarter-hour demand forecast, for capacity-tariff markets. Empty = no cap |
| `peak_cap_w` | The site's capacity-tariff target |
| `price_now_entity`, `price_avg_entity` | Dynamic tariff. Empty = never force a paid grid top-up |
On a capacity-tariff site the maintenance charge is capped by the headroom left
under `peak_cap_w`, and if the forecast goes over the cap the charge-only clamp
is dropped so the battery can shave the peak instead. Money outranks the
maintenance schedule.
### Site
| option | meaning |
|---|---|
| `estop_fitted` | Whether the RS485 e-stop is installed. Drives the warning banner |
| `log_level` | `trace`/`debug`/`info`/`warning`/`error` |
## The Web UI
The ingress panel shows live values, why the controller is commanding what it
is, and a **Commissioning** checklist that names any problem in words. It also
carries the three buttons: start/stop control, force a maintenance cycle, and
abort one.
## Status entities
If an MQTT broker is available the add-on publishes setpoint, grid power,
battery power, state of charge, maintenance phase and controller status by MQTT
discovery. This is observability only — the controller works fine without a
broker, and MQTT problems can never affect control.