glenn schrooyenandClaude Opus 5 4bd659c499 TEL-01 review fixes: stop the age sensor tripping installs that have no meter
T-1, and it was a fleet-wide trip to zero. publish() emitted p1_age
unconditionally, and published_age_s counts from P1Ingest.__init__ when no
sample has ever arrived. With meter_source defaulting to off, every existing
install would have published sensor.p1_sample_age_s climbing without bound; the
ESP32 does `has_state() && state >= max_age_s` and forces the layer-1 failsafe,
so each of them would have pinned its inverter at 0 W within 30 s. Exactly the
opposite of the zero-regression the off default was for. The key is now omitted
from the payload AND from MQTT discovery when P1 is off, so the entity does not
exist at all - which is the status quo, and what has_state() is testing for.
The predicate is one function, is_enabled(), because the grid reading, the task
start and the discovery announcement have to agree or this comes back.

T-2, connect no longer manufactures a sample. get_states returns whatever HA
currently holds, which after a Core restart is a RestoreEntity value of unknown
age; stamping it with ingest_ts=now reset the age and reported a fresh meter
that could have been dead for an hour. run()'s own docstring already said a
reconnect must emit nothing - the code disagreed with it, and a test asserted
the violation. The cache is still primed, so the first real state_changed
builds a complete sample; the age just stays honest until one arrives.

T-3, gaps are no longer filled with the last held value. The averager held a
sample forward across any interval, so a meter dying at 5 kW and returning ten
minutes later credited 5 kW x 600 s to the capacity-tariff accumulator - a
fabricated peak on a permanent record. The hold is capped at max_age_s: past
that the stretch is walked so block boundaries still land correctly, but
nothing accumulates and elapsed does not grow, which is what finally makes the
comment about a gap dragging the billed average down true. Same threshold for
control and billing: a reading too old to steer by is too old to bill by.

T-4, the out-of-order/duplicate guard is covered. It was untested, and the
reason is worth recording: the obvious assertion passes without the guard,
because the negative interval is separately refused by the covered > 0 test.
What the guard prevents is the timestamp REWIND, which only shows up one sample
later as a re-integrated window. The test now goes one sample later.

T-6, DOCS was wrong about latency. meter_max_age_s and stale_input_s stack, so
meter death to 0 W is 45 s and not 30. Documented as a table with both clocks.

Also documented the T-5 asymmetry rather than papering over it: the age
measures arrival, not change, so a stuck MQTT bridge republishing its last
telegram still looks fresh. Correct on ha_dsmr, not detectable on mqtt_p1
without a change-detector. Written up as a known limit.

Writing the T-1 test caught a second defect in the test itself: it recorded
only MQTT topics, and object_id lives in the payload, so "the age sensor is not
announced" had been passing for the wrong reason.

test_p1.py: 99 -> 122 checks. 14 mutations run, all 14 red, files restored
byte-identical - including one per fix above.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 23:16:31 +02:00

12 KiB
Raw Permalink Blame History

GoodWe RS485 Controller

Drives a GoodWe ES/BP battery inverter over its RS485 meter bus: holds net grid exchange at zero, and runs a monthly battery maintenance cycle so the BMS can balance cells and recalibrate its coulomb counter.

Installers: read FIELD-GUIDE.md in the repository. It is not optional reading — it contains the commissioning gates and the failure modes.

Before you start

You need:

  • A GoodWe ES / BP family inverter (AA55 / RS485 meter-bus generation)
  • The vendor's meter-emulating controller disconnected from the bus
  • A T-CAN485 (ESP32) flashed with firmware/goodwe-master.yaml
  • A grid-power sensor already working in Home Assistant, updating every ~510 s

The safety model, in short

The inverter holds its last command forever — it has no meter-timeout. So:

  • The ESP32 commands 0 W if this add-on stops refreshing for ~30 s, and keeps commanding it.
  • This add-on commands 0 W when its inputs go missing, when you stop control, and when it shuts down.
  • The optional RS485 e-stop is the only thing that covers this machine dying. Without it, a failed host leaves the battery latched at its last command until someone intervenes.

If anything looks wrong: stop the add-on. That commands 0 W and the hardware holds it there.

Configuration

Sources

option required meaning
meter_entity yes Net grid power. Positive must mean importing
meter_invert Flip the sign if the meter reports the other way
soc_entity yes Battery state of charge — use the ESP32's own read
batt_entity yes Battery power — again the ESP32's read, + = discharging
batt_invert Flip if needed
setpoint_entity yes The ESPHome number.*_goodwe_setpoint_w

Use the ESP32's readings rather than the inverter's cloud or dongle sensors: those serve cached values, and a stale reading here ends the maintenance charge phase having charged nothing.

P1 meter ingestion

meter_entity above expects one signed sensor, which usually means a template someone wrote by hand. A Belgian P1 meter does not publish one: it publishes two unsigned registers, consumption and injection. Setting meter_source moves that subtraction into the add-on, where it is done once and tested, and replaces meter_entity entirely.

option default meaning
meter_source off off keeps meter_entity. ha_dsmr subscribes to the DSMR integration over the HA WebSocket; mqtt_p1 reads a topic
meter_phases 1 1 or 3. Must match the telegram, or every telegram is rejected and logged
meter_max_age_s 30 Beyond this the reading is stale and grid power reads as missing. On its own it does not command 0 W — see the timing note below. It is also the longest a reading is held forward into the 15-minute average
meter_mqtt_topic mqtt_p1 only
p1_import_entity The unsigned consumption sensor. Do not point this at a signed template
p1_export_entity The unsigned injection sensor
p1_phase_import_entities [] L1..L3, in order. Needed for the capacity-tariff peak on a three-phase connection
p1_phase_export_entities [] L1..L3, in order

How long a dead meter takes to reach 0 W

meter_max_age_s and stale_input_s stack. They are two different clocks and neither one is the whole answer:

step option default
telegrams stop, P1 sample goes stale, grid power starts reading missing meter_max_age_s 30 s
inputs have been missing long enough for the loop to command 0 W stale_input_s 15 s
total, meter death → 0 W commanded by this add-on 45 s

So in P1 mode stale_input_s is not "how long inputs may be missing before commanding 0 W" measured from the meter dying — it is measured from the moment the P1 sample already went stale. Size the pair together: the ESP32's own watchdog commands 0 W after ~30 s of silence from this add-on regardless, and that layer is unaffected by either option.

There is no fallback to an inverter-side power figure, deliberately. The inverter's own AC power tracks its battery almost perfectly and the real meter hardly at all, so a controller that failed over to it would be regulating against its own output while looking healthy.

The mqtt_p1 payload is one JSON object per telegram, and the schema is strict — a key it does not recognise is a telegram from something other than what was tested, and guessing a key here means guessing a kilowatt:

{"import_w": 1234.0,
 "export_w": 0.0,
 "phases": [{"import_w": 500, "export_w": 0},
            {"import_w": 400, "export_w": 0},
            {"import_w": 334, "export_w": 0}],
 "timestamp": "2026-08-24T18:00:05+02:00"}

phases and timestamp are optional; timestamp must carry a UTC offset. Where it is present it is used for the age, which is what stops a retained message replayed on reconnect from presenting a ten-minute-old reading as current.

sensor.p1_sample_age_s

Published over MQTT discovery whenever a broker is available: seconds since the newest accepted telegram, refreshed every second rather than only when a telegram lands. The ESP32's stale-input watchdog subscribes to this exact entity id, so do not rename it.

The reason it is recomputed against the clock is that Home Assistant only pushes a state when the state changes. A meter sitting at a genuinely constant reading emits nothing, which is indistinguishable — to anything watching the value — from a meter that has died. Watching the age instead separates the two: it climbs when telegrams stop and resets when they arrive, whatever the reading says.

The entity is only created when meter_source is not off. With P1 ingestion disabled there is nothing feeding it, and an age sensor climbing with no ingester behind it would trip the firmware watchdog on a system that is working fine.

Known limit, mqtt_p1 only. The age measures arrival, not change. On the ha_dsmr path that is exactly right: a frozen meter emits no state_changed, so nothing arrives and the age climbs. On the MQTT path a bridge that is stuck republishing its last telegram keeps arriving, so the age stays near zero and a frozen meter still looks fresh. Detecting that needs a change-detector rather than an arrival-detector, and it is not in this version. Prefer ha_dsmr where both are available.

Control

option default meaning
max_w 2000 Hard limit on what may be commanded. Start low, raise after commissioning
gain 0.6 Correction per cycle. At the limit — do not raise
slew_w 1000 Maximum change per cycle
deadband_w 15 Ignore errors smaller than this
target_grid_w -10 What the meter should rest at. Negative = a slight export
step_w 10 Quantisation
saturation_w 500 Divergence that counts as "the inverter is at a limit"
saturation_cycles 3 How many consecutive cycles before freezing. A cycle is one changed meter reading, not a fixed period - see the note below. Do not set to 1
integrator_max_w 0 Bound on the loop's accumulator, and 0 means "same as max_w". Caps how much stale error can be waiting to unwind when the sign flips. Do not raise it above max_w - the output clamp already bounds what is commanded, so the only thing extra headroom buys is more cycles of wrong-direction power after every saturation event. Lowering it below max_w is the useful direction
heartbeat_s 10 Refresh interval; must stay well under the firmware watchdog
stale_input_s 15 How long inputs may be missing before commanding 0 W. In P1 mode this clock starts only after meter_max_age_s has already expired — the two stack, see "How long a dead meter takes to reach 0 W"
auto_start false Start controlling on boot (only after commissioning)

Saturation is counted in cycles, not seconds

The specification states the saturation window as "> 10 s". This add-on counts cycles instead, and that is a deliberate, accepted deviation rather than an oversight - the acceptance criterion is not met as literally written.

A cycle here is one changed meter reading: the controller only runs the loop when the meter value differs from the previous poll. At the reference P1's ~5 s update rate the default of 3 cycles is usually around 15 s, but there is no guaranteed wall-clock window - a meter that repeats the same value stalls the counter for as long as it repeats.

Two reasons that is acceptable:

  • the control law is a pure function with no clock, which is what makes it testable without hardware, and a seconds-based window would have to live in the controller;
  • a stalled counter is a detection-latency limit and not a runaway risk. The condition that stalls it - an unchanging meter - stops the whole loop, so nothing accumulates while it is stalled.

If a guaranteed window matters on your site, raise saturation_cycles for a fast meter, and treat the figure as "N meter updates" rather than "N seconds".

Why target_grid_w is not zero

The deadband is a one-way ratchet: any resting point inside it holds until something disturbs it. Import and export are separate registers on the meter, so a rest point of +14 W is billed for every second it holds and no amount of export cancels it - 14 W all day is 0.34 kWh.

Biasing the target below zero moves that residue into the export register, which is not billed. The resting band becomes target ± deadband, so:

target_grid_w resting band worst billed leak export given away
0 -15 … +15 W ~15 W (0.35 kWh/day) none
-10 -25 … +5 W ~5 W (0.12 kWh/day) ~10 W
-15 -30 … 0 W none ~15 W (0.36 kWh/day)

Set it to -deadband_w if injection is worth nothing to you and you would rather give the energy away than buy it back. Set it to 0 if you are paid properly for export, or if you are debugging and want the loop centred.

⚠️ This is a billing knob, not a speed knob. If import is arriving in bursts rather than as a trickle, the cause is tracking lag, and this will not help - see "Why the tuning is what it is".

Maintenance

option default meaning
maintenance_enabled false Enable the monthly cycle
maintenance_interval_days 28 Minimum gap between cycles
maintenance_start_hour 10 Hour of day a due cycle begins
maintenance_discharge_w 2500 Drain rate (exports the surplus)
maintenance_charge_w 2500 Charge ceiling, capped again by peak headroom
maintenance_soc_floor 11 Drain target — stay just above the inverter's own floor
maintenance_soc_target 99 Charge target
maintenance_hold_min 120 Hold at full so the BMS can balance

Tariff (all optional)

option meaning
peak_forecast_entity Quarter-hour demand forecast, for capacity-tariff markets. Empty = no cap
peak_cap_w The site's capacity-tariff target
price_now_entity, price_avg_entity Dynamic tariff. Empty = never force a paid grid top-up

On a capacity-tariff site the maintenance charge is capped by the headroom left under peak_cap_w, and if the forecast goes over the cap the charge-only clamp is dropped so the battery can shave the peak instead. Money outranks the maintenance schedule.

Site

option meaning
estop_fitted Whether the RS485 e-stop is installed. Drives the warning banner
log_level trace/debug/info/warning/error

The Web UI

The ingress panel shows live values, why the controller is commanding what it is, and a Commissioning checklist that names any problem in words. It also carries the three buttons: start/stop control, force a maintenance cycle, and abort one.

Status entities

If an MQTT broker is available the add-on publishes setpoint, grid power, battery power, state of charge, maintenance phase and controller status by MQTT discovery. This is observability only — the controller works fine without a broker, and MQTT problems can never affect control.