Release 0.21.0: release/1.0 -> master #242

Merged
admin merged 33 commits from release/1.0 into master 2026-11-08 17:27:33 +01:00
33 Commits
Author SHA1 Message Date
admin 16029d7cb8 Merge pull request 'Release 0.21.0' (#241) from release-0.21.0 into release/1.0
infra-pin / fresh (push) Successful in 2s
checks / unit (pull_request) Successful in 23m41s
infra-pin / fresh (pull_request) Successful in 2s
2026-11-08 10:46:27 +01:00
Claude review 8e26574b03 Release 0.21.0: CHANGELOG wording (SAFETY-136, SAFETY-138 known issues)
checks / unit (pull_request) Successful in 24m11s
infra-pin / fresh (pull_request) Successful in 2s
SAFETY-136: the line said 10 to 15 s late is not caught, then that 15 s late
is caught after about 4 minutes. It now says 10 s is not caught and 15 s only
after about 4 minutes, as the card says.
SAFETY-138: the 30 s timer that zeroes a late write is the ESPHome board's
watchdog (README), not the inverter's own.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-11-08 10:20:46 +01:00
Claude 0f208a0500 Release 0.21.0: version bump and CHANGELOG
checks / unit (pull_request) Successful in 33m53s
infra-pin / fresh (pull_request) Successful in 2s
Minor bump, no option changes. Folds "Not in a release yet" into a new
0.21.0 section, adds the contents table for the nine merges on release/1.0
since master 0.20.1, updates the known issues, and rewrites the 0.20.1
SAFETY-128 known issue to say it ships in 0.21.0.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-08 09:08:59 +01:00
admin b3cfcf2df4 Merge pull request 'SAFETY-137: the shutdown 0 W must be the last write every unit hears' (#240) from SAFETY-137 into release/1.0
infra-pin / fresh (push) Successful in 2s
2026-11-08 04:20:04 +01:00
Claude 8953be0362 SAFETY-137: the shutdown and Stop 0 W is the last write every unit hears
checks / unit (pull_request) Successful in 22m59s
infra-pin / fresh (pull_request) Successful in 1s
The 0 W of shutdown and of the Stop button now waits (bounded, 2 s) for a
write already on its way to the same unit, for every driver, GoodWe included.
Once shutdown has begun, cycle, heartbeat and safety-stop writes are dropped
right before the write is created. One shared wait (_await_inflight) serves
the 0 W and SMA-10's _release_last.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-08 02:39:38 +01:00
admin dbdc37b959 Merge pull request 'SMA-10: two idle states, hold 0 W or hand the inverter back' (#239) from SMA-10 into release/1.0
infra-pin / fresh (push) Successful in 1s
2026-11-07 23:43:14 +01:00
glenn schrooyenandClaude 6cae5a2f8f SMA-10 round 4: pin the Dutch default "de eigen sturing"
checks / unit (pull_request) Successful in 30m41s
infra-pin / fresh (pull_request) Successful in 2s
The NL default for a hand-back driver without words (handback._BACK_NL) was
changed to "de eigen sturing" in round 2 at the PR #239 review's request
(comment 2495: the article as in the generic clause). The brief does not name
it, so DECISIONS now says where it came from and a test checks the exact Dutch
sentence. No app code change.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-07 22:45:08 +01:00
glenn schrooyenandClaude 313503724d SMA-10 round 3: Start clears a failed hand-back streak; the hook is tested
checks / unit (pull_request) Successful in 23m23s
infra-pin / fresh (pull_request) Successful in 2s
When control takes the unit again, release_fails, release_retry_at and
release_zero_sent are reset, so the next Stop is a new streak with its own one
0 W, error line and event. Tests: a streak that Start interrupts without a
recovery; a driver that overrides release_fallback(). _BACK_NL "de eigen
sturing" (round 2) is kept.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-07 21:31:28 +01:00
glenn schrooyenandClaude d26cc573fe SMA-10 round 2: a failed release sends 0 W once, retries at heartbeat pace
checks / unit (pull_request) Successful in 23m37s
infra-pin / fresh (pull_request) Successful in 2s
When release() fails (False, raises or hangs past RELEASE_BUDGET_S) the unit
gets one bounded write(0) through the new Driver.release_fallback() hook
(default write(0)), then nothing more, so the inverter's own fallback timer is
not reset. The release is retried once per heartbeat, not on every idle
write. One error line and one action-log event per failure streak, one line on
recovery. Dutch default "terug naar de eigen sturing". DECISIONS says what a
unit is left at.

test_messages.py: the RELEASE_BUDGET_S data entry is gone again (the line
that needed it is gone).

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-07 20:17:01 +01:00
glenn schrooyenandClaude a1be9c48b3 SMA-10: two idle states, hold 0 W or hand the inverter back
checks / unit (pull_request) Successful in 24m9s
infra-pin / fresh (pull_request) Successful in 1s
A driver now says whether its release() hands the inverter back
(Driver.hands_back; GoodWe is False, so release() stays write(0) and the
Controller never calls it). command_site_release() sits next to
command_site_zero(): the Stop button and shutdown() (so SIGTERM, restart,
control task death and a late config refusal) hand a hand-back unit back,
once, and zero every other unit as before. Safety stops and refusals still
hold 0 W for every unit. Shadow mode releases a hand-back unit. After a
release nothing is written to the unit (heartbeat and cycle included) until
control starts again. release() is bounded by RELEASE_BUDGET_S (= the write
budget), runs concurrently per unit, and a raising or hanging release on one
unit does not stop the others.

The "set to 0 W" sentences for Stop, restart, shadow mode and the stopped
banner are built from the roster (app/handback.py, EN and NL, words from the
driver); a GoodWe-only roster keeps every old literal. A handed-back unit
shows "Back under <its control>" on Home.

Existing test edited: test_messages.py (two classification entries for the
CRITICAL line that moved into a roster builder, and the new release bound).

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-07 18:21:28 +01:00
admin 57c8d1b912 Merge pull request 'SMA-2: each inverter is reached through a driver; GoodWe behaviour unchanged' (#238) from SMA-2 into release/1.0
infra-pin / fresh (push) Successful in 2s
2026-11-07 14:46:58 +01:00
glenn schrooyenandClaude c015230452 SMA-2 round 2: keep the driver keys out of the schema, translations and labels
checks / unit (pull_request) Successful in 23m13s
infra-pin / fresh (pull_request) Successful in 1s
Owner decision 2026-11-07: clients see nothing new until SMA-4. config.yaml,
translations, labels and the page layout are back to 23ff9d0's. The validation
of the keys stays for callers that skip the schema.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-07 13:09:31 +01:00
glenn schrooyenandClaude 0b20f53cf8 SMA-2 round 2: census keeps ACTUATOR_WRITE_KEYS, setters, NaN/inf port refused, tests
Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-07 12:20:56 +01:00
glenn schrooyenandClaude e56eeef8f0 SMA-2: each inverter is reached through a driver; GoodWe behaviour unchanged
checks / unit (pull_request) Successful in 23m14s
infra-pin / fresh (pull_request) Successful in 2s
app/drivers.py holds one Driver per roster entry (configured, actuator_id,
limits, read, write, release, probe, link_stale_s, batt_bound, settle_s, brand,
words). GoodWeEsphomeDriver makes the calls the code it replaced made, in the
same order. Inverter gets driver; has_writer, is_live and link_note read it. The
SoC/power read, the write, the device range (run_control, amain, the settings
panel), rule 2 per unit and the SAFETY-28 census go through it.

setpoint_entity is optional per entry beside driver, host, port, unit_id and
maintenance; only goodwe_esphome is selectable, the rest are checked and unused.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-07 11:28:47 +01:00
admin 23ff9d0920 Merge pull request 'OPT-38: keep tomorrow's solar forecast when one sensor goes stale in the afternoon' (#237) from OPT-38 into release/1.0
infra-pin / fresh (push) Successful in 1s
2026-11-07 06:56:10 +01:00
glenn schrooyenandClaude 0bacafadf0 OPT-38 round 2: a kept tomorrow reading is flagged kept only from 20:00
checks / unit (pull_request) Successful in 23m11s
infra-pin / fresh (pull_request) Successful in 1s
Before the bell ends it replaced today's Home line and the event log with
the kept-for-tonight wording. stand_in() docstring covers the tomorrow case.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-07 06:02:00 +01:00
glenn schrooyenandClaude c43873b142 OPT-38: a kept tomorrow forecast reading stands in at any hour
checks / unit (pull_request) Successful in 22m54s
infra-pin / fresh (pull_request) Successful in 1s
One stale Forecast.Solar tomorrow sensor dropped the whole OPT-17 sum from
17:54 to 20:00. Today readings and the OPT-34 morning rules are unchanged.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-07 04:24:01 +01:00
admin b291262ee1 Merge pull request 'SAFETY-129: find late Home Assistant readings sooner at a 5 s meter' (#236) from SAFETY-129 into release/1.0
infra-pin / fresh (push) Successful in 2s
2026-11-07 01:24:39 +01:00
glenn schrooyenandClaude c70eeb6916 SAFETY-129 round 3: the real reason for the 16 s limit, a slow-start check, the row's tail
checks / unit (pull_request) Successful in 23m1s
infra-pin / fresh (pull_request) Successful in 1s
Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-07 00:12:33 +01:00
glenn schrooyenandClaude 03541a1eee SAFETY-129 round 2: next() with a default in test_safety129
checks / unit (pull_request) Successful in 23m26s
infra-pin / fresh (pull_request) Successful in 2s
Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-06 22:12:39 +01:00
glenn schrooyenandClaude 85433edac6 SAFETY-129 round 2: shorter test_safety129, pinned 5 s row, 100 s bound
Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-06 21:24:37 +01:00
glenn schrooyenandClaude 2667cf0dda SAFETY-129: the 5 s row no longer waits for the batteries' figure
checks / unit (pull_request) Successful in 23m52s
infra-pin / fresh (pull_request) Successful in 1s
At a 5 s meter the slow meter fit now finds 30 s late first, and the hold leaves
the batteries' fit nothing to measure, so the row says it without a figure.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-06 20:04:08 +01:00
glenn schrooyenandClaude 5b6cb0bf08 SAFETY-129: find readings 30 s late within about 90 s at a 5 s meter
The meter's delay fit needed 16 new values in 60 s, so at the owner's 5 s P1
only the batteries' fit ran and 30 s late was found after about 3 minutes
(export to -420 W). A meter that slow is now also fitted over 120 s; it calls
a delay late only over 16 s, on two fits in a row, with the same corroboration
as before, and never ends a verdict, so a slow battery (R2-1) runs as before.
Found about 90 s after the start, export above -200 W. 10 s late at a 5 s
meter is not found (nothing swings; it cannot be told from a 10 s battery).

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-06 19:38:21 +01:00
admin c66aa7f69a Merge pull request 'UX-77 round 2: Home's roll shares the peak room by room left, as control does' (#235) from UX-77-2 into release/1.0
infra-pin / fresh (push) Successful in 1s
2026-11-06 11:19:20 +01:00
glenn schrooyenandClaude 6d2b9b5335 UX-77: Home's roll shares the peak room by room left to full, as control does
checks / unit (pull_request) Successful in 26m34s
infra-pin / fresh (pull_request) Successful in 2s
The cheap-run roll (cheaproll._Charge) shared the peak room by rating, control
shares it by room left to full (packshare.weights). With unequal levels one
battery's drawn block ended too early (rig F-1). The roll now uses
packshare.weights over the simulated levels, each battery capped at its rating,
a full one dropping out. test_ux77 gains two unequal-level walks and a
by-rating mutant; its walks model control's split by room too.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-06 09:11:00 +01:00
admin 47c89a13d0 Merge pull request 'UX-77: Home draws today's grid charge for the hours control will really charge' (#234) from UX-77 into release/1.0
infra-pin / fresh (push) Successful in 1s
2026-11-06 00:11:03 +01:00
glenn schrooyenandClaude 45535e19d7 UX-77: Home draws today's grid charge for the hours control will really charge
checks / unit (pull_request) Successful in 27m7s
infra-pin / fresh (pull_request) Successful in 1s
The cheap run is sized at the full rating, so under the peak limit a battery is
still short when it ends, and control plans the next run then. Home drew only
the run under way. `cheaproll` rolls the run on the way control does
(`modetrade.energy()` + `priceruns.plan()` at each run end, lifted from
`dayview._levels()`), reading the levels at the charge power the peak limit
leaves (peak aim less the house, else the rating). `homeview.mode_runs()` and
`price_windows()` use it for today: the grid block, the Today line and the
chart's cheap bars run to where control stops, each battery's block to its
own stop. Display only: no control change.

test_ux54: today's grid block of the night-before scenario now follows the roll.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-05 21:48:56 +01:00
admin af2d0d2f61 Merge pull request 'Sync 0.20.1 (master) into release/1.0' (#233) from sync-0.20.1 into release/1.0
infra-pin / fresh (push) Successful in 2s
2026-11-05 21:15:14 +01:00
glenn schrooyenandClaude 4f96397a60 Merge origin/master (0.20.1) into release/1.0
checks / unit (pull_request) Successful in 32m4s
infra-pin / fresh (pull_request) Successful in 2s
Brings OPT-36 (#229) and TEST-37 (#231) onto release/1.0, which keeps
SAFETY-128 (#228). No textual conflicts. CHANGELOG: the SAFETY-128 entry
moved out of the released 0.20.0 section into "Not in a release yet" above
## 0.20.1; the 0.20.0 and 0.20.1 sections are identical to master.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-05 18:34:34 +01:00
admin 371961e51c Merge pull request 'SAFETY-128: control does not act on late Home Assistant readings' (#228) from SAFETY-128 into release/1.0
infra-pin / fresh (push) Successful in 1s
2026-11-02 05:49:07 +01:00
glenn schrooyenandClaude Opus 5.5 7de77a5a09 SAFETY-128 review: DECISIONS states the slow-battery limit as measured
checks / unit (pull_request) Successful in 32m0s
infra-pin / fresh (pull_request) Successful in 1s
Round 2 review: a 10 s dead time reads late at 1-2 s meters, and a 15-20 s
lag gives late fits; the note said 3-20 s and 6-10 s gave none.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Bdqr7PiaHcBnzPituu2yTC
2026-11-02 05:16:28 +01:00
glenn schrooyenandClaude d3f4f9f48b SAFETY-128 round 2: find late readings from the batteries, not the meter alone
checks / unit (pull_request) Successful in 26m50s
infra-pin / fresh (pull_request) Successful in 2s
Review B1: the meter fit took repeating house loads (ovens, a heat pump)
for late readings on healthy 1-2 s sites, about 9 % of the recorded
house. B2: at a 5 s meter it never ran. M1: no hysteresis. M2: an
unbounded check.

lateness.Delay now fits how long each battery's reading takes to show
its own request, which the house does not move, from the 1 s reads
(read_inputs -> Answer.watch). The meter fit stays for speed at 1-3 s
meters, but counts only when an ask was slow to start and no battery
fit said on time. Late from 9.5 s after 2 fits, on time under 6.5 s,
dropped after 120 s without a fit. Fits are bounded (a few ms).

Readings on time: no verdict in any reviewer scenario (22 shapes at
1/2/5 s meters, 7 harm runs) nor in 2 days of the recorded house at
1, 2 and 5 s ticks; digests equal to 77fe31b. Late: found 36-68 s after
the start at 1-2 s, about 3 min at 5 s. The row gives the batteries'
delay, or no figure while only the meter has shown it.

Co-Authored-By: Claude <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Bdqr7PiaHcBnzPituu2yTC
2026-11-02 04:32:04 +01:00
glenn schrooyenandClaude 09e1fbb898 SAFETY-128: control does not act on late Home Assistant readings
checks / unit (pull_request) Successful in 19m36s
infra-pin / fresh (pull_request) Successful in 1s
Readings that Home Assistant delivers late but still changing passed
every staleness gate, so the loop corrected again each cycle an error
its last command had already fixed (10 s late: the give run swung and
exported to -1.9 kW), and the peak guard pushed to the inverter limit
on the same late figures (OPT-34 F-2).

app/lateness.py fits how long after a power request the meter shows
it. Over 8 s the readings are late: a request the battery reading has
not answered holds the loop (it may not lead the reading by more than
100 W) and caps the peak guard at what stands; unanswered for 23 s it
holds, then 0 W after stale_input_s. An amber row and one log line per
episode say so. With readings on time nothing changes (digests equal).

DECISIONS/SAFETY-128-late-readings.md; test_safety128.py.

Co-Authored-By: Claude <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Bdqr7PiaHcBnzPituu2yTC
2026-11-01 23:45:03 +01:00