@@ -81,6 +81,59 @@ a Supervisor install (every key is always supplied) and reachable only from
|
||||
tests/`sim`. The real fix is one source of truth for option defaults, which is
|
||||
bigger than this ticket and touches files another ticket is in.
|
||||
|
||||
## 0.5.2
|
||||
|
||||
**A meter frozen at a wrong-but-fresh value now raises an alarm. It still is not
|
||||
stopped.** (SAFETY-18)
|
||||
|
||||
A meter that answers `200 OK` with a stale document forever is *arriving* on
|
||||
every poll, so every freshness mechanism in the stack reads it as healthy:
|
||||
`meter_max_age_s` is reset by each response, the firmware watchdog is fed by the
|
||||
heartbeat and by a sample age that never climbs, and the arbiter contributes only
|
||||
±`max_w`. The loop integrates a constant error and rails — replaying the real
|
||||
`compute()` at 15 s cycles, in 150/60/30 s at `max_w: 2000` for a meter frozen at
|
||||
350/1000/≥3000 W, and 360/135/75 s at `max_w: 5000`. **The live install runs
|
||||
`max_w: 5000`**, which is both the schema maximum and the device rating.
|
||||
|
||||
The new detector (`app/freeze.py`) is a **conjunction**, not the bare
|
||||
`unchanged_s` threshold TEL-05 measured and rejected:
|
||||
|
||||
unchanged_s ≥ meter_freeze_s AND |command| within 5 % of max_w
|
||||
|
||||
Both terms already existed and were already on the status page. They fail for
|
||||
independent reasons: at the converged point the command is nowhere near the rail,
|
||||
and at the rail against a real load the kWh registers move within seconds. At the
|
||||
shipped 300 s there is also a structural relation, not just a margin — the
|
||||
slowest a healthy 1 Wh register can tick and still look unchanged is 12 W, which
|
||||
is inside the 15 W deadband, so the command there is parked at 0 W and the two
|
||||
halves cannot both be true.
|
||||
|
||||
**Notification only, deliberately.** An HA persistent notification (fixed
|
||||
`notification_id`, so a repeat replaces rather than stacks), an `ERROR` log line,
|
||||
a UI event and a red status banner. No claim, no latch, no 0 W: a false trip
|
||||
parks the battery and the operator's next move is to switch the guard off; a
|
||||
false notification costs an alert. The trip is a separate decision that needs
|
||||
data from a real install.
|
||||
|
||||
- New option `meter_freeze_s` (default 300, range 60–3600, no "off").
|
||||
- **Only `meter_source: homewizard_local` is covered** — it is the only transport
|
||||
that sees the meter's own document. Everywhere else the status page says
|
||||
**NOT COVERED** rather than "armed".
|
||||
- `DOCS.md` now states the **capacity-tariff exposure** this does *not* close:
|
||||
`peak_cap_w` caps maintenance charging and nothing caps the loop, so a lying
|
||||
meter can drive a 5 kW unattended import, and ≥15 minutes of that sets the
|
||||
month's billed peak (measured: one 4998 W quarter moved a monthly peak from
|
||||
4832 → 5013 W). That cap is SAFETY-07.
|
||||
- `test_freeze.py` grades it in both directions: silent over 40 minutes of the
|
||||
live house's real converged capture (committed as
|
||||
`scenarios/p1-age-2026-08-26.jsonl.gz`), silent over an hour of TEL-05's
|
||||
low-power case where a bare threshold is shown to fire, and alarming on a
|
||||
genuinely frozen meter driven over real HTTP through the real
|
||||
`HomeWizardLocalSource` — against the rig's own `hwsim` `freeze` fault when the
|
||||
infra repo is reachable, an equivalent stub otherwise. Its negative twin is the
|
||||
load-bearing one: the same railed command against a meter that is still moving
|
||||
must stay silent at the same threshold.
|
||||
|
||||
## 0.5.1
|
||||
|
||||
**SAFETY-02's latch now survives an add-on restart, which is the difference
|
||||
|
||||
@@ -30,6 +30,10 @@ The inverter **holds its last command forever** — it has no meter-timeout. So:
|
||||
- The **optional RS485 e-stop** is the only thing that covers this machine
|
||||
dying. Without it, a failed host leaves the battery latched at its last
|
||||
command until someone intervenes.
|
||||
- This add-on **raises an alarm — and nothing more —** when the meter keeps
|
||||
answering with a reading that never changes while the command sits at the
|
||||
rail. See "The frozen-meter alarm" and, before you rely on it, "Capacity-tariff
|
||||
exposure of the grid-following loop".
|
||||
|
||||
**If anything looks wrong: stop the add-on.** That commands 0 W and the
|
||||
hardware holds it there.
|
||||
@@ -433,6 +437,95 @@ under `peak_cap_w`, and if the forecast goes over the cap the charge-only clamp
|
||||
is dropped so the battery can shave the peak instead. Money outranks the
|
||||
maintenance schedule.
|
||||
|
||||
#### Capacity-tariff exposure of the grid-following loop
|
||||
|
||||
⚠️ **`peak_cap_w` caps MAINTENANCE charging. It does not cap the loop.** The
|
||||
grid-following loop is bounded by `max_w` and by the device rating, and by
|
||||
nothing else. That is deliberate — the loop exists to *reduce* what crosses the
|
||||
meter, so under every healthy condition it lowers the peak rather than raising
|
||||
it — but it means one thing is true and worth writing down:
|
||||
|
||||
**If the meter lies, the loop will happily buy `max_w` from the grid for as long
|
||||
as the lie lasts, and no cap in this add-on stops it.** A meter frozen at a large
|
||||
export reads as "the house is exporting hard", the loop charges the battery to
|
||||
correct it, and the correction is a grid import. At the schema maximum
|
||||
`max_w: 5000` — which is what this house runs, and is also the device rating —
|
||||
that is a 5 kW unattended import.
|
||||
|
||||
The bill is not the energy. In the Belgian capaciteitstarief the month is billed
|
||||
on its highest quarter-hour average, so **fifteen minutes of this sets the whole
|
||||
month's peak.** A measured case: one 4998 W quarter moved a monthly peak from
|
||||
4832 W to 5013 W, and every day of that month was billed at the higher figure.
|
||||
|
||||
What exists today, and what does not:
|
||||
|
||||
| | |
|
||||
|---|---|
|
||||
| `max_w` bounds the magnitude | ✅ — but the exposure IS the magnitude |
|
||||
| Maintenance charging capped under `peak_cap_w` | ✅ |
|
||||
| **Loop capped under `peak_cap_w`** | ❌ — not built. This is SAFETY-07 |
|
||||
| Frozen meter detected | ✅ on `homewizard_local` only, **alarm only** |
|
||||
| Frozen meter *stopped* | ❌ — the alarm does not command anything |
|
||||
| SoC guard on the loop | ❌ — the BMS is the only energy backstop |
|
||||
|
||||
So the frozen-meter alarm below **narrows the window; it does not close it.** On
|
||||
a capacity-tariff site where an unattended runaway is unacceptable, the mitigation
|
||||
today is operational: set `max_w` no higher than the loop actually needs (the
|
||||
tuning was measured at 2000 W and a 1.78 kW load step is tracked fine there), fit
|
||||
the e-stop, and watch for the alarm.
|
||||
|
||||
### The frozen-meter alarm
|
||||
|
||||
A meter that has died is easy — it stops answering, the sample age climbs past
|
||||
`meter_max_age_s`, the reading becomes missing, and the add-on and the ESP32 both
|
||||
command 0 W. A meter that keeps answering `200 OK` with a document that never
|
||||
changes is the hard one: **every freshness mechanism in the stack reads it as
|
||||
healthy**, because it really is arriving on every poll. The loop then integrates
|
||||
a constant error and winds to the rail, in 75–360 s at `max_w: 5000`.
|
||||
|
||||
The add-on alarms when **both** of these are true at once:
|
||||
|
||||
- the meter's own document (power figure *and* both kWh registers) has not
|
||||
changed for `meter_freeze_s` — 300 s by default; **and**
|
||||
- the command standing on the wire is at the rail, within 5 % of `max_w`.
|
||||
|
||||
Neither half is usable alone. A bare "unchanged for N seconds" rule false-trips
|
||||
at the exact operating point this controller aims for — at a converged −10 W a
|
||||
1 Wh register legitimately takes about six minutes to move — and a bare "at the
|
||||
rail" rule fires on any genuinely large load. Together they are safe in both
|
||||
directions, because a real railed condition means kilowatts still crossing the
|
||||
meter, and a kilowatt advances a 1 Wh register every 3.6 s.
|
||||
|
||||
**It is an alarm and nothing else.** It does not command 0 W, does not latch, and
|
||||
does not claim the actuator. A false trip here parks the battery; a false
|
||||
notification costs an alert. Turning it into a trip is a separate decision that
|
||||
needs data from a real install — and an answer to "what should the loop do
|
||||
instead", given that 0 W is itself an import of whatever the house is drawing.
|
||||
|
||||
When it fires you get a Home Assistant persistent notification
|
||||
(`goodwe_meter_frozen`, replaced rather than stacked on a repeat), an `ERROR` in
|
||||
the add-on log, an entry in the UI's event list, and a red banner on the status
|
||||
page. **The loop keeps running.** If the meter really is stuck, stop control from
|
||||
the add-on UI.
|
||||
|
||||
⚠️ **Only `meter_source: homewizard_local` is covered.** It is the only transport
|
||||
that reads the meter's own document; on `ha_dsmr`, `mqtt_p1`, `ha_signed` and
|
||||
`off` there is no signal to threshold and the status page says **NOT COVERED**
|
||||
rather than pretending the guard is armed.
|
||||
|
||||
| option | default | meaning |
|
||||
|---|---|---|
|
||||
| `meter_freeze_s` | 300 | Seconds of an unchanged measurement, *while the command is at the rail*, before the alarm |
|
||||
|
||||
Why 300 s: over 2399 s of this house at the converged operating point (mean grid
|
||||
−14.2 W, 1194 polls, 735 of them repeating the previous reading) the largest
|
||||
`unchanged_s` any sample sees is **8.0 s**, and the longest interval serving no
|
||||
distinct reading at all is **15.4 s**. There is also a structural reason not to
|
||||
lower it much: at 300 s the slowest a *healthy* register can tick and still look
|
||||
unchanged is 12 W, which is inside the 15 W deadband — so the command there is
|
||||
parked at 0 W and the two halves of the rule cannot both be true. At the schema
|
||||
floor of 60 s that figure is 60 W and only the margin is left.
|
||||
|
||||
### Site
|
||||
|
||||
| option | meaning |
|
||||
|
||||
@@ -0,0 +1,275 @@
|
||||
"""SAFETY-18 - the frozen-but-fresh meter detector.
|
||||
|
||||
WHAT IT CATCHES, in one sentence: a meter that keeps answering 200 OK with a
|
||||
document that never changes, which every freshness mechanism in this stack reads
|
||||
as perfectly healthy while the loop winds to the rail and stays there.
|
||||
|
||||
THE FAILURE NEEDS NO FAULT ANYWHERE ELSE. A frozen-but-talking meter is
|
||||
*arriving* on every poll, so:
|
||||
|
||||
- `meter_max_age_s` is structurally blind. Every response resets the arrival
|
||||
stamp (p1.py, `HomeWizardLocalSource`), so the age never climbs. Age catches
|
||||
a meter that stops TALKING; this one stops CHANGING.
|
||||
- firmware layer 1 is fed. Its watchdog keys on setpoint staleness, which the
|
||||
heartbeat satisfies, and on `sensor.goodwe_p1_sample_age`, which a talking
|
||||
meter satisfies.
|
||||
- the arbiter contributes only the device rating and +-`max_w` - it bounds the
|
||||
magnitude, which is the number this fault drives us to, not away from.
|
||||
- there is no SoC guard on the grid-following loop at all. `soc_floor` belongs
|
||||
to the maintenance cycle; the BMS is the sole energy backstop.
|
||||
|
||||
The loop reads a constant error and integrates it. Time from freeze to the rail,
|
||||
replaying the real `control.compute()` at 15 s cycles:
|
||||
|
||||
meter frozen at to rail, max_w 2000 to rail, max_w 5000
|
||||
350 W 150 s 360 s
|
||||
1000 W 60 s 135 s
|
||||
>= 3000 W 30 s 75 s
|
||||
|
||||
⚠️ THE LIVE INSTALL RUNS `max_w: 5000`, which is both the schema maximum and the
|
||||
device rating, so the right-hand column is the one that describes this house.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
THIS HAS A EURO FIGURE, AND IT IS THE REASON THE TICKET IS P1
|
||||
|
||||
`maintenance_charge_floor()` caps MAINTENANCE charging against `peak_cap_w`. The
|
||||
grid-following loop is not capped by anything but `max_w`. A meter frozen
|
||||
reading a large export drives a 5 kW unattended grid IMPORT, and >= 15 minutes
|
||||
of that sets the month's billed capaciteitstarief peak: specs.md:583 records a
|
||||
measured case where a single 4998 W quarter moved a monthly peak from 4832 W to
|
||||
5013 W and billed the whole month at it.
|
||||
|
||||
⚠️ THIS CUT DOES NOT CAP THAT. It notifies. See DOCS.md, "Capacity-tariff
|
||||
exposure of the grid-following loop", and SAFETY-07.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
WHY IT IS A CONJUNCTION AND NOT AN `unchanged_s` THRESHOLD
|
||||
|
||||
`unchanged_s` (p1.py) already measures exactly the right thing: seconds since
|
||||
the meter served a DIFFERENT measurement, fingerprinted over the power figure
|
||||
and both energy registers. It is computed, it is on the status page, and TEL-05
|
||||
deliberately refused to threshold it - correctly:
|
||||
|
||||
this controller regulates grid power toward ~0 W, and at a converged -10 W
|
||||
the export register takes about six minutes to advance by its 1 Wh
|
||||
resolution while the power figure legitimately repeats.
|
||||
|
||||
So a bare `unchanged_s > N` false-trips at the exact operating point we aim for,
|
||||
and `p1.py` says as much in a note that ends "whoever wires a freeze detector
|
||||
must handle the low-power case first". This is that handling, and it is not a
|
||||
smaller number:
|
||||
|
||||
unchanged_s >= hold_s AND |commanded_w| is at the rail
|
||||
|
||||
The second term is what TEL-05's case cannot satisfy. At the converged point the
|
||||
command is nowhere near +-`max_w`; on the 40 minutes of live converged behaviour
|
||||
in `sim/scenarios/p1-age-2026-08-26.jsonl.gz` the meter never once leaves
|
||||
+-500 W, so the loop never even approaches a 5000 W rail. And the reverse case -
|
||||
a command genuinely pinned at the rail by a real 8 kW load - cannot satisfy the
|
||||
FIRST term, because a real railed condition means kilowatts still crossing the
|
||||
meter, and a kilowatt advances a 1 Wh register every 3.6 s.
|
||||
|
||||
The two terms fail for independent reasons. That is the whole design.
|
||||
|
||||
⚠️ AND THE SECOND HALF OF THAT WAS MEASURED ON THE RIG, WITH A RESULT WORTH
|
||||
READING CAREFULLY. Driving the real transport against the rig's own hwsim under
|
||||
+8000 W of house load - a genuinely railed command, meter perfectly healthy - the
|
||||
POWER FIGURE DID NOT MOVE AT ALL: `active_power_w` sat at exactly 10130.0 W for
|
||||
26 consecutive polls. What kept `unchanged_s` pinned at 0.0 s was the kWh
|
||||
registers advancing, and nothing else.
|
||||
|
||||
So the register terms in `measurement_fingerprint()` are not belt-and-braces
|
||||
here, they are the entire negative case. A freeze detector fingerprinted on the
|
||||
power figure alone would have raised a false alarm on that rig run - a healthy
|
||||
meter, a real load, a correctly railed command - which is the exact failure mode
|
||||
that gets a safety guard switched off. Anyone tempted to simplify the fingerprint
|
||||
should read that run first.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
WHERE `hold_s` COMES FROM
|
||||
|
||||
Measured on `sim/scenarios/p1-age-2026-08-26.jsonl.gz` - 2399 s (40 min) of the
|
||||
live house at the converged operating point, mean grid -14.2 W, 1194 polls:
|
||||
|
||||
polls that repeated the previous reading 735 of 1193 (61.6 %)
|
||||
distinct-reading transitions 458
|
||||
median gap between distinct readings 6.0 s
|
||||
p95 gap 6.0 s
|
||||
LARGEST `unchanged_s` any sample observes 8.0 s
|
||||
longest interval serving no distinct reading 15.4 s
|
||||
samples outside +-500 W 0
|
||||
|
||||
The default 300 s is 37x the largest `unchanged_s` this house has been recorded
|
||||
producing while converged, and 19.5x the longest interval in which it served no
|
||||
distinct reading at all. The two figures differ because the capture has an 11.4 s
|
||||
hole in its OWN polling; the second is quoted because it is the pessimistic one.
|
||||
300 s is not fitted to either margin - it is picked as "clearly past any
|
||||
plausible register-tick interval, and clearly inside the 900 s quarter that bills
|
||||
the capacity tariff". test_freeze.py re-measures both every run, so this
|
||||
paragraph cannot quietly stop being true.
|
||||
|
||||
⚠️ BE PRECISE ABOUT WHAT THAT CAPTURE PROVES. It is POWER-ONLY - the shipped
|
||||
fingerprint also covers both kWh registers, so a real `unchanged_s` on that data
|
||||
can only be shorter, never longer, which makes it a conservative measurement of
|
||||
the converged case. But it does NOT on its own refute a bare `unchanged_s`
|
||||
threshold, and saying it did would be exactly the overstatement this project
|
||||
keeps having to walk back: at 8 s worst, a bare 300 s threshold is silent on it
|
||||
too. The case that refutes the bare threshold is the one below, which no capture
|
||||
of THIS meter contains because this meter's power figure jitters.
|
||||
|
||||
The floor on the other side: at the rail, the smallest residual grid flow that
|
||||
still ticks a 1 Wh register inside 300 s is 12 W. Any condition that genuinely
|
||||
pins this loop at +-5000 W has three orders of magnitude more than that crossing
|
||||
the meter.
|
||||
|
||||
⚠️ AND THOSE TWO NUMBERS DO NOT MERELY HAVE MARGIN - THEY CANNOT BOTH BE TRUE.
|
||||
The worry the conjunction has to answer is "a HEALTHY meter whose register is
|
||||
slower than `hold_s`". At 300 s that is |grid| < 12 W. The shipped `deadband_w`
|
||||
is 15 W, so anywhere the register is that slow the control law is already inside
|
||||
its deadband and the command is parked - the rail term is not merely unlikely to
|
||||
be true there, it is 0 W. The two terms are mutually exclusive by construction
|
||||
at the defaults, not just far apart, and the check re-derives that every run.
|
||||
|
||||
That relationship is the one to protect. `hold_s` may be lowered only while
|
||||
3600/hold_s stays under `deadband_w`; at the schema floor of 60 s that is 60 W
|
||||
against a 15 W deadband, and the mutual exclusion is gone. A 60 s `meter_freeze_s`
|
||||
is a supported configuration that gives up this argument and keeps only the
|
||||
margin - do not set one without a capture that says the margin is enough.
|
||||
|
||||
⚠️ WHAT `hold_s` DOES NOT BUY IS DETECTION SPEED. The alert lands at
|
||||
max(hold_s, time-to-rail) after the freeze, so at the shipped default and
|
||||
`max_w: 5000` that is 300-360 s. The rail is REACHED first, from 75 s. A
|
||||
notification is not a brake; see the DOCS.md note.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
THE RAIL TERM, PRECISELY
|
||||
|
||||
abs(commanded_w) >= RAIL_FRAC * max_w
|
||||
|
||||
`commanded_w` is the EMITTED setpoint - what the arbiter resolved and
|
||||
`write_setpoint()` put on the wire - not the loop's raw wish, for the same
|
||||
reason SAFETY-02 uses the emitted value: the wire carries the emitted number.
|
||||
|
||||
RAIL_FRAC is 0.95 and is a constant rather than an option. The command is
|
||||
quantised to `step_w` (max 100) and clamped to `max_w` (min 100), so at the rail
|
||||
the emitted value IS `max_w` on every schema-legal combination; the 5 % is slack
|
||||
for a device rating that clips `max_w` slightly in `write_setpoint()`, not a
|
||||
tuning knob. Making it configurable would offer a way to widen the one term that
|
||||
carries the whole no-false-positive argument.
|
||||
|
||||
⚠️ NOT GATED ON `following`, and that is deliberate. A maintenance charge
|
||||
commands against the meter on purpose and can sit at the rail for hours - but it
|
||||
does so while pushing kilowatts through the meter, so the FIRST term is what
|
||||
excludes it, and it excludes it on physics rather than on bookkeeping. Gating on
|
||||
`following` as well would additionally blind the detector to a maintenance phase
|
||||
running against a meter that really has frozen, which is the same fault with a
|
||||
worse actuator behind it.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
NOTIFY, DO NOT TRIP
|
||||
|
||||
First cut is an alarm and nothing else: an HA persistent notification, an ERROR
|
||||
in the log, an event on the status page, and a failed check row. It does NOT
|
||||
claim the actuator, does NOT file a P_SAFETY claim and does NOT latch.
|
||||
|
||||
That is a deliberate ordering of costs, not timidity. A false trip here parks
|
||||
the battery - on a house that is running this loop precisely to avoid buying
|
||||
power at the wrong moment - and the operator's response to a parked battery is
|
||||
to switch the guard off. A false notification costs one alert. The trip is a
|
||||
separate decision that has to be earned with observed data from a real install,
|
||||
and it needs an answer to a question this cut does not have one for: what should
|
||||
the loop do instead, given that 0 W is itself a grid import of whatever the
|
||||
house is drawing.
|
||||
|
||||
⚠️ TRANSPORT-CONDITIONAL. `unchanged_s` exists ONLY on `homewizard_local`,
|
||||
because it is the only transport that sees the meter's own document. Under
|
||||
`ha_dsmr`, `mqtt_p1`, `ha_signed` and `meter_source: off` this detector is
|
||||
silent and the exposure above is uncovered. The caller passes None and gets
|
||||
False; there is no half-measure available on those paths, and pretending
|
||||
otherwise would be worse than the gap.
|
||||
"""
|
||||
|
||||
from dataclasses import dataclass
|
||||
from datetime import datetime
|
||||
|
||||
# See "THE RAIL TERM, PRECISELY" above. A constant, on purpose.
|
||||
RAIL_FRAC = 0.95
|
||||
|
||||
|
||||
@dataclass(frozen=True)
|
||||
class FreezeWatchdogConfig:
|
||||
"""Default, not a constant - config.yaml carries `meter_freeze_s`."""
|
||||
|
||||
hold_s: float = 300.0
|
||||
|
||||
|
||||
def rail_w(max_w) -> float:
|
||||
"""The magnitude at or above which a command counts as railed."""
|
||||
return abs(float(max_w)) * RAIL_FRAC
|
||||
|
||||
|
||||
def looks_frozen(unchanged_s, commanded_w, max_w,
|
||||
cfg: FreezeWatchdogConfig) -> bool:
|
||||
"""The predicate, and the ONLY place the conjunction is written down.
|
||||
|
||||
Public for the same reason `watchdog.disagrees()` is: the checks that grade
|
||||
it must assert on THE SHIPPED EXPRESSION. A safety predicate transcribed
|
||||
into its own test is one copy plus a future disagreement about what the
|
||||
check means, and the copy that drifts is always the one doing the grading.
|
||||
|
||||
`unchanged_s` seconds since the meter served a different measurement, or
|
||||
None on a transport that cannot know (see the module note).
|
||||
`commanded_w` the EMITTED setpoint standing on the wire.
|
||||
`max_w` the configured output bound the rail is measured against.
|
||||
"""
|
||||
if unchanged_s is None or commanded_w is None or not max_w:
|
||||
return False
|
||||
return (float(unchanged_s) >= cfg.hold_s
|
||||
and abs(float(commanded_w)) >= rail_w(max_w))
|
||||
|
||||
|
||||
class FreezeWatchdog:
|
||||
"""One instance per controller, evaluated once per control cycle.
|
||||
|
||||
Level-triggered state with an EDGE for the alarm: `evaluate()` returns True
|
||||
on the cycle the conjunction first becomes true and False on every cycle
|
||||
after, so the caller raises one notification per episode rather than one
|
||||
every second. `active` is the level, for the status page.
|
||||
|
||||
No latch, deliberately - see "NOTIFY, DO NOT TRIP". A latch exists so a trip
|
||||
cannot erase its own evidence by working; nothing here acts, so there is
|
||||
nothing to erase. When the meter starts moving again the alert clears
|
||||
itself, which is the honest report of the state.
|
||||
"""
|
||||
|
||||
def __init__(self, cfg: FreezeWatchdogConfig | None = None):
|
||||
self.cfg = cfg or FreezeWatchdogConfig()
|
||||
self.active = False
|
||||
self.since: datetime | None = None
|
||||
self.reason = ""
|
||||
self.episodes = 0
|
||||
|
||||
def evaluate(self, unchanged_s, commanded_w, max_w, now: datetime) -> bool:
|
||||
"""Advance one cycle. Returns True ONLY on the rising edge.
|
||||
|
||||
`now` is the caller's clock so this stays testable and replayable - the
|
||||
same discipline as `SignWatchdog.evaluate()`.
|
||||
"""
|
||||
if not looks_frozen(unchanged_s, commanded_w, max_w, self.cfg):
|
||||
self.active = False
|
||||
self.since = None
|
||||
self.reason = ""
|
||||
return False
|
||||
|
||||
self.reason = (
|
||||
f"METER_FROZEN: the meter has answered {float(unchanged_s):.0f} s "
|
||||
f"without its measurement changing while the command stands at "
|
||||
f"{float(commanded_w):+.0f} W, at the {float(max_w):.0f} W rail "
|
||||
f"(limits: unchanged over {self.cfg.hold_s:.0f} s, command over "
|
||||
f"{rail_w(max_w):.0f} W)")
|
||||
if self.active:
|
||||
return False
|
||||
self.active = True
|
||||
self.since = now
|
||||
self.episodes += 1
|
||||
return True
|
||||
@@ -36,6 +36,7 @@ from .arbiter import (
|
||||
P_LOOP, P_MAINT_SHAPE, P_MAINTENANCE, P_SAFETY, Claim, resolve,
|
||||
)
|
||||
from .control import Tuning, compute, maintenance_charge_floor, peak_at_risk
|
||||
from .freeze import FreezeWatchdog, FreezeWatchdogConfig, rail_w
|
||||
from .hass import HomeAssistant
|
||||
from .maintenance import IDLE, MaintConfig, Maintenance
|
||||
from .mqtt import MqttPublisher
|
||||
@@ -127,6 +128,18 @@ class Controller:
|
||||
"once you know why the command opposed the meter.",
|
||||
self.sign_wd.reason or "(reason not recorded)")
|
||||
|
||||
# SAFETY-18. The frozen-but-fresh meter detector - see freeze.py for why
|
||||
# it is a conjunction and not an `unchanged_s` threshold, and for the
|
||||
# measurements behind the default.
|
||||
#
|
||||
# ⚠️ NOT restored from the store, unlike SAFETY-02's latch, and the
|
||||
# asymmetry is the point: this one does not latch because it does not
|
||||
# act. A restart re-derives its state from the meter within one
|
||||
# `meter_freeze_s` window, and until then the honest report is "not
|
||||
# alarming yet" rather than an alarm nobody can clear.
|
||||
self.freeze_wd = FreezeWatchdog(
|
||||
FreezeWatchdogConfig(hold_s=float(opts.get("meter_freeze_s", 300))))
|
||||
|
||||
# P1 ingestion (TEL-01). `meter_source: off` keeps the original
|
||||
# single-entity meter_entity path, so an existing install is unchanged
|
||||
# until it opts in.
|
||||
@@ -393,6 +406,53 @@ class Controller:
|
||||
self.reason = resolution.explain()
|
||||
await self.write_setpoint(self.target)
|
||||
|
||||
# --- SAFETY-18, and it runs LAST on purpose --------------------------
|
||||
# Both terms of the conjunction describe the state that now exists: the
|
||||
# command that has just gone on the wire, and how long the meter that
|
||||
# chose it has been standing still. Evaluated before write_setpoint()
|
||||
# it would be reasoning about the PREVIOUS command against THIS cycle's
|
||||
# meter - the one combination that is true of neither moment.
|
||||
await self.check_meter_frozen()
|
||||
|
||||
async def check_meter_frozen(self) -> None:
|
||||
"""SAFETY-18. Alarm on a meter that answers forever without changing.
|
||||
|
||||
Notification only - no claim, no latch, no 0 W. freeze.py carries the
|
||||
reasoning and the euro figure; DOCS.md carries the exposure this does
|
||||
NOT close.
|
||||
|
||||
⚠️ getattr, not an attribute access: `unchanged_s` exists only on
|
||||
`homewizard_local`, and `p1_source` is None until amain() builds the
|
||||
transport. Every other meter_source hands the predicate None and gets
|
||||
False, which is the honest answer - see the transport note in freeze.py.
|
||||
"""
|
||||
unchanged = getattr(self.p1_source, "unchanged_s", None)
|
||||
fired = self.freeze_wd.evaluate(unchanged, self.target,
|
||||
float(self.o.get("max_w", 2000)),
|
||||
datetime.now(timezone.utc))
|
||||
if not fired:
|
||||
return
|
||||
self.log_event("METER FROZEN? " + self.freeze_wd.reason)
|
||||
_LOG.error(
|
||||
"SAFETY-18 - %s. The grid-following loop is regulating against a "
|
||||
"number that has stopped moving, and nothing in this stack stops "
|
||||
"it: the meter is still answering, so the age is fresh, the "
|
||||
"firmware watchdog is fed and the arbiter only bounds the "
|
||||
"magnitude. CHECK THE METER. Sustained for a quarter of an hour "
|
||||
"this sets the month's billed capacity-tariff peak. This is an "
|
||||
"ALARM ONLY - the loop is still running.", self.freeze_wd.reason)
|
||||
# ⚠️ A fixed notification_id, so a second episode REPLACES the first
|
||||
# rather than stacking. An operator who has to dismiss eleven identical
|
||||
# notifications learns to dismiss the twelfth without reading it.
|
||||
await self.hass.call("persistent_notification", "create", {
|
||||
"notification_id": "goodwe_meter_frozen",
|
||||
"title": "GoodWe: the P1 meter may be frozen",
|
||||
"message": (
|
||||
f"{self.freeze_wd.reason}.\n\nThe controller is STILL RUNNING "
|
||||
f"and still following this reading. Check the meter; if it is "
|
||||
f"stuck, stop control from the add-on UI."),
|
||||
})
|
||||
|
||||
# -- tasks ---------------------------------------------------------------
|
||||
async def run_control(self) -> None:
|
||||
entity = self.o.get("setpoint_entity", "")
|
||||
@@ -581,6 +641,33 @@ class Controller:
|
||||
f"{self.p1.parse_errors} rejected"
|
||||
+ (f", measurement unchanged for {unchanged:.0f} s"
|
||||
if unchanged is not None else "")})
|
||||
# SAFETY-18. Reported in both states, for the reason SAFETY-02 is:
|
||||
# a detector nobody can see is armed is a detector nobody trusts
|
||||
# when it fires. ok=False/warn=False so the banner goes red - this
|
||||
# is an alarm, and the banner is the loudest surface we own. It
|
||||
# changes NOTHING about control; see check_meter_frozen().
|
||||
if self.freeze_wd.active:
|
||||
out.append({"ok": False, "warn": False,
|
||||
"text": "METER MAY BE FROZEN - " + self.freeze_wd.reason
|
||||
+ ". The loop is STILL FOLLOWING it and is "
|
||||
"still running. Check the meter. Held here "
|
||||
"for a quarter of an hour this sets the "
|
||||
"month's billed capacity peak."})
|
||||
elif getattr(self.p1_source, "unchanged_s", None) is None:
|
||||
# Not "armed". Every transport but homewizard_local is invisible
|
||||
# to this check, and saying "armed" there would be a lie the
|
||||
# status page tells on behalf of a guard that cannot run.
|
||||
out.append({"ok": False, "warn": True,
|
||||
"text": f"freeze detector: NOT COVERED on "
|
||||
f"meter_source {o.get('meter_source')} - only "
|
||||
f"homewizard_local sees whether the meter's own "
|
||||
f"document changes"})
|
||||
else:
|
||||
out.append({"ok": True, "warn": False,
|
||||
"text": f"freeze detector: armed (alerts after "
|
||||
f"{self.freeze_wd.cfg.hold_s:.0f} s unchanged "
|
||||
f"while the command is over "
|
||||
f"{rail_w(self.o.get('max_w', 2000)):.0f} W)"})
|
||||
rows = [("battery SoC", self.soc, o.get("soc_entity")),
|
||||
("battery power", self.batt, o.get("batt_entity"))]
|
||||
if not self.p1_enabled:
|
||||
|
||||
@@ -1,5 +1,5 @@
|
||||
name: GoodWe RS485 Controller
|
||||
version: "0.5.1"
|
||||
version: "0.5.2"
|
||||
slug: goodwe_controller
|
||||
description: >-
|
||||
Drives a GoodWe ES/BP battery inverter over RS485 by emulating its smart
|
||||
@@ -114,6 +114,26 @@ options:
|
||||
sign_disagree_w: 300
|
||||
sign_disagree_s: 180
|
||||
|
||||
# --- SAFETY-18 frozen-but-fresh meter detector -----------------------------
|
||||
# Seconds the meter may keep answering with an UNCHANGED measurement while the
|
||||
# command stands at the rail before the add-on raises an alarm. Both halves
|
||||
# are required: neither one alone is safe, and app/freeze.py carries why.
|
||||
#
|
||||
# ALARM ONLY. It does not command 0 W and does not latch. A false trip parks
|
||||
# the battery; a false notification costs an alert.
|
||||
#
|
||||
# ⚠️ Only `meter_source: homewizard_local` can see this at all - it is the
|
||||
# only transport that reads the meter's own document. On every other source
|
||||
# the status page says NOT COVERED rather than "armed".
|
||||
#
|
||||
# 300 s is measured, not chosen. Over 2399 s of the live house at the
|
||||
# converged operating point (sim/scenarios/p1-age-2026-08-26.jsonl.gz, mean
|
||||
# grid -14.2 W, 1194 polls, 735 of them repeating the previous reading) the
|
||||
# LONGEST run without a distinct reading is 15.4 s (the largest unchanged_s any
|
||||
# sample observes is 8.0 s). 300 s is 19.5x the pessimistic figure, and
|
||||
# still inside the 900 s quarter that bills the capacity tariff.
|
||||
meter_freeze_s: 300
|
||||
|
||||
# --- maintenance -----------------------------------------------------------
|
||||
maintenance_enabled: false
|
||||
maintenance_interval_days: 28
|
||||
@@ -196,6 +216,15 @@ schema:
|
||||
sign_disagree_w: int(50,5000)
|
||||
sign_disagree_s: int(30,1800)
|
||||
|
||||
# No "off" value, for SAFETY-02's reason: disarming a safety alarm is not a
|
||||
# supported configuration. ⚠️ THE FLOOR OF 60 IS NOT A RECOMMENDATION. At 300 s
|
||||
# the slowest a HEALTHY meter's 1 Wh register can tick and still look unchanged
|
||||
# is 12 W, which is inside the 15 W deadband, so the two terms of the
|
||||
# conjunction are mutually exclusive rather than merely far apart. At 60 s that
|
||||
# figure is 60 W and the argument is gone - only the margin is left. See
|
||||
# app/freeze.py.
|
||||
meter_freeze_s: int(60,3600)
|
||||
|
||||
maintenance_enabled: bool
|
||||
maintenance_interval_days: int(1,90)
|
||||
maintenance_start_hour: int(0,23)
|
||||
|
||||
Binary file not shown.
@@ -0,0 +1,539 @@
|
||||
"""Runnable check for SAFETY-18, the frozen-but-fresh meter detector.
|
||||
|
||||
python3 test_freeze.py
|
||||
|
||||
Three parts, and the last two are the ones that matter:
|
||||
|
||||
1. the predicate's boundaries and the edge-trigger, table-driven;
|
||||
2. SILENT ON REAL CONVERGED DATA. `scenarios/p1-age-2026-08-26.jsonl.gz` is
|
||||
40 minutes of this house's live meter at the operating point, committed
|
||||
here from the infra repo's `sim/scenarios/`. It is replayed through the
|
||||
REAL `control.compute()` at the real cycle rule, and the detector must not
|
||||
make a sound. This is the acceptance criterion TEL-05's objection is
|
||||
about, and it is verified rather than argued;
|
||||
3. FIRES ON A GENUINELY FROZEN METER, over real HTTP, through the REAL
|
||||
`HomeWizardLocalSource` - the transport is what computes `unchanged_s`, so
|
||||
a check that calls the predicate directly would not be testing the thing
|
||||
that ships. Uses the rig's own `sim/hwsim.py --fault freeze` when the infra
|
||||
repo is next to this one (or `$GOODWE_SIM`), and an equivalent local stub
|
||||
otherwise. Both are exercised; the run says which one it used.
|
||||
|
||||
⚠️ Part 3 runs in WALL CLOCK - `unchanged_s` is `time.monotonic()` and the
|
||||
transport really polls - so it drives the detector at `hold_s=10`, not the
|
||||
shipped 300. The THRESHOLD is config; the MECHANISM is what is under test, and
|
||||
the mechanism cannot be hurried. Part 2 uses the shipped 300 because that data
|
||||
is replayed rather than lived.
|
||||
|
||||
⚠️ Part 3 also runs its NEGATIVE twin, and that is the load-bearing half: the
|
||||
same railed command against a meter that is still MOVING, at the same 10 s
|
||||
threshold. If that one alarms, the detector is a `unchanged_s` threshold with
|
||||
extra steps and the whole reason for the conjunction is gone.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
THE RIG RUN THIS STANDS IN FOR
|
||||
|
||||
Part 3 is the portable version of a run done on the real rig - the `goodwe-sim`
|
||||
compose project on 192.168.2.147, under `sim/riglock.py`, with the driver staged
|
||||
into `goodwe-sim-plant` so it polls that container's own hwsim while plantsim
|
||||
drives it. Both phases passed there. To repeat it:
|
||||
|
||||
DOCKER_HOST=ssh://homelab@192.168.2.147 python sim/riglock.py status
|
||||
|
||||
⚠️ WITHOUT `DOCKER_HOST` SET, ON A WINDOWS HOST, `riglock status` REPORTS
|
||||
`rig: UNKNOWN` - it shells out to the local `docker` CLI, which resolves to a
|
||||
Docker Desktop npipe that is not running. That is INDISTINGUISHABLE from a
|
||||
genuinely absent rig, and it is not one: the rig lives on the homelab box and was
|
||||
up the whole time. `UNKNOWN` is the tool declining to observe, not an
|
||||
observation. Do not read it as "no rig" (this cost this ticket a wrong caveat).
|
||||
|
||||
The rig run also produced a result part 3's stub cannot: under +8000 W of house
|
||||
load the meter's POWER FIGURE never moved - 10130.0 W for 26 consecutive polls -
|
||||
and only the kWh registers kept `unchanged_s` at zero. See the note in
|
||||
freeze.py; it is why the fingerprint's register terms are the negative case
|
||||
rather than a nicety.
|
||||
"""
|
||||
|
||||
import asyncio
|
||||
import gzip
|
||||
import json
|
||||
import os
|
||||
import subprocess
|
||||
import sys
|
||||
import time
|
||||
from datetime import datetime, timedelta, timezone
|
||||
from pathlib import Path
|
||||
|
||||
import aiohttp
|
||||
|
||||
from app.control import Tuning, compute
|
||||
from app.freeze import (
|
||||
RAIL_FRAC, FreezeWatchdog, FreezeWatchdogConfig, looks_frozen, rail_w,
|
||||
)
|
||||
from app.main import Controller
|
||||
from app.p1 import HomeWizardLocalSource, P1Ingest
|
||||
|
||||
fails = []
|
||||
T0 = datetime(2026, 8, 26, 7, 0, 0, tzinfo=timezone.utc)
|
||||
HERE = Path(__file__).resolve().parent
|
||||
|
||||
# The live install's numbers, which are the ones the exposure is written at.
|
||||
LIVE_MAX_W = 5000.0
|
||||
|
||||
|
||||
def check(name, cond):
|
||||
print(f" {'ok ' if cond else 'FAIL'} {name}")
|
||||
if not cond:
|
||||
fails.append(name)
|
||||
|
||||
|
||||
def tuning(max_w=LIVE_MAX_W):
|
||||
"""The shipped defaults from config.yaml, at the live install's max_w."""
|
||||
return Tuning(gain=0.6, max_w=max_w, slew_w=1000, deadband_w=15,
|
||||
target_grid_w=-10, step_w=10, saturation_w=500,
|
||||
saturation_cycles=3)
|
||||
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
# 1. the predicate and the edge
|
||||
# --------------------------------------------------------------------------- #
|
||||
print("predicate")
|
||||
cfg = FreezeWatchdogConfig(hold_s=300)
|
||||
|
||||
check("both terms true -> frozen", looks_frozen(300, 5000, 5000, cfg))
|
||||
check("unchanged long, command NOT railed -> silent (TEL-05's case)",
|
||||
not looks_frozen(3600, -40, 5000, cfg))
|
||||
check("command railed, meter still moving -> silent (a real 8 kW load)",
|
||||
not looks_frozen(4, -5000, 5000, cfg))
|
||||
check("neither -> silent", not looks_frozen(4, -40, 5000, cfg))
|
||||
check("one second under the hold is still silent",
|
||||
not looks_frozen(299.9, 5000, 5000, cfg))
|
||||
check("just under the rail fraction is still silent",
|
||||
not looks_frozen(3600, 5000 * RAIL_FRAC - 1, 5000, cfg))
|
||||
check("at the rail fraction exactly, it fires",
|
||||
looks_frozen(3600, 5000 * RAIL_FRAC, 5000, cfg))
|
||||
check("the rail scales with max_w, not with a fixed watt figure",
|
||||
looks_frozen(3600, 2000, 2000, cfg) and not looks_frozen(3600, 2000, 5000, cfg))
|
||||
check("a charge rail counts too - the runaway can be either sign",
|
||||
looks_frozen(3600, -5000, 5000, cfg))
|
||||
check("no transport signal (unchanged_s None) -> silent, never assumed frozen",
|
||||
not looks_frozen(None, 5000, 5000, cfg))
|
||||
check("no command yet -> silent", not looks_frozen(3600, None, 5000, cfg))
|
||||
check("rail_w tracks RAIL_FRAC", rail_w(5000) == 5000 * RAIL_FRAC)
|
||||
|
||||
print("the edge")
|
||||
wd = FreezeWatchdog(cfg)
|
||||
edges = [wd.evaluate(u, c, 5000, T0 + timedelta(seconds=i))
|
||||
for i, (u, c) in enumerate(
|
||||
[(10, 5000), (300, 5000), (305, 5000), (310, 5000),
|
||||
(2, 5000), (300, 5000)])]
|
||||
check("rises exactly once per episode", edges == [False, True, False, False,
|
||||
False, True])
|
||||
check("two episodes counted", wd.episodes == 2)
|
||||
check("clearing the condition clears the alarm state",
|
||||
not FreezeWatchdog(cfg).evaluate(2, 5000, 5000, T0))
|
||||
check("the reason names both terms",
|
||||
"unchanged over 300" in wd.reason and "command over 4750" in wd.reason)
|
||||
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
# 2. silent on 40 minutes of real converged behaviour
|
||||
# --------------------------------------------------------------------------- #
|
||||
print("converged replay - scenarios/p1-age-2026-08-26.jsonl.gz")
|
||||
rows = [json.loads(line) for line in
|
||||
gzip.open(HERE / "scenarios" / "p1-age-2026-08-26.jsonl.gz", "rt")]
|
||||
check("the capture loaded", len(rows) > 1000)
|
||||
|
||||
# ⚠️ The capture records the POWER figure only. The shipped fingerprint also
|
||||
# covers both kWh registers, so a real `unchanged_s` on this data can only be
|
||||
# SHORTER than what is reconstructed here - this replay is the pessimistic
|
||||
# version of the converged case, not a flattering one.
|
||||
def replay(hold_s, max_w, cycle_floor_s=15.0):
|
||||
"""Drive the real control law and the real detector over the capture."""
|
||||
wd = FreezeWatchdog(FreezeWatchdogConfig(hold_s=hold_s))
|
||||
t = tuning(max_w)
|
||||
target, i_w, sat = 0.0, 0.0, 0
|
||||
prev_pwr, changed_at = None, rows[0]["t"]
|
||||
last_cycle = None
|
||||
peak_cmd, peak_unchanged, fired_at = 0.0, 0.0, None
|
||||
for r in rows:
|
||||
now, pwr = r["t"], float(r["pwr"])
|
||||
if prev_pwr is None or pwr != prev_pwr:
|
||||
changed_at = now
|
||||
arrival = (prev_pwr is None or pwr != prev_pwr)
|
||||
prev_pwr = pwr
|
||||
# main.run_control()'s rule: a cycle per changed reading, or the floor.
|
||||
if arrival or last_cycle is None or now - last_cycle >= cycle_floor_s:
|
||||
last_cycle = now
|
||||
d = compute(prev_w=target, grid_w=pwr, actual_w=target, tuning=t,
|
||||
sat_count=sat, i_w=i_w)
|
||||
target, i_w, sat = d.target_w, d.i_w, d.sat_count
|
||||
# ⚠️ The detector is evaluated on EVERY poll, not only on cycles, and
|
||||
# that is deliberately harsher than the shipped wiring (which evaluates
|
||||
# it inside cycle()). On an arrival-triggered cycle `unchanged_s` is 0
|
||||
# by construction, so grading only there would be grading the detector
|
||||
# on the one sample it cannot possibly fire on.
|
||||
unchanged = now - changed_at
|
||||
peak_cmd = max(peak_cmd, abs(target))
|
||||
peak_unchanged = max(peak_unchanged, unchanged)
|
||||
if wd.evaluate(unchanged, target, max_w,
|
||||
T0 + timedelta(seconds=now - rows[0]["t"])) \
|
||||
and fired_at is None:
|
||||
fired_at = now - rows[0]["t"]
|
||||
return wd, peak_cmd, peak_unchanged, fired_at
|
||||
|
||||
|
||||
for mw in (2000.0, LIVE_MAX_W):
|
||||
wd_r, peak_cmd, peak_unchanged, fired = replay(300.0, mw)
|
||||
print(f" max_w {mw:.0f}: worst |command| {peak_cmd:.0f} W (rail "
|
||||
f"{rail_w(mw):.0f} W), worst unchanged {peak_unchanged:.1f} s "
|
||||
f"(hold 300 s), episodes {wd_r.episodes}")
|
||||
check(f"max_w {mw:.0f}: never alarms on the converged capture", fired is None)
|
||||
check(f"max_w {mw:.0f}: and the rail term had margin to spare",
|
||||
peak_cmd < rail_w(mw))
|
||||
|
||||
# The margin on the OTHER term, as numbers rather than as trust. Both figures
|
||||
# are quoted in config.yaml and freeze.py, so they are re-measured every run and
|
||||
# a capture swapped underneath them cannot leave the prose saying the old thing.
|
||||
_, _, worst_unchanged, _ = replay(300.0, LIVE_MAX_W)
|
||||
gaps, last, prev = [], rows[0]["t"], None
|
||||
for r in rows:
|
||||
if prev is None or r["pwr"] != prev:
|
||||
gaps.append(r["t"] - last)
|
||||
last = r["t"]
|
||||
prev = r["pwr"]
|
||||
print(f" longest unchanged_s any sample would observe: {worst_unchanged:.1f} s")
|
||||
print(f" longest interval serving no distinct reading: {max(gaps):.1f} s "
|
||||
f"(spans an 11.4 s hole in the capture's own polling)")
|
||||
check("worst observed unchanged_s is the 8 s the docs quote",
|
||||
7.5 < worst_unchanged < 8.5)
|
||||
check("longest distinct-reading interval is the 15.4 s the docs quote",
|
||||
15.0 < max(gaps) < 16.0)
|
||||
check("300 s is at least 15x the worst of the two", 300.0 >= 15 * max(gaps))
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
# 2b. TEL-05's case, reconstructed, because the capture cannot contain it
|
||||
# --------------------------------------------------------------------------- #
|
||||
# ⚠️ BE HONEST ABOUT WHAT THE CAPTURE ABOVE PROVES AND WHAT IT DOES NOT. On this
|
||||
# house's meter the power figure jitters at 1 W, so the worst `unchanged_s` any
|
||||
# sample sees is 8 s - which means the capture alone does NOT refute a bare
|
||||
# `unchanged_s > 300` threshold, and reporting it as though it did would be the
|
||||
# confident explanation nobody checked. The case that refutes the bare threshold
|
||||
# is the one p1.py describes and no capture of THIS meter contains: a converged
|
||||
# meter whose power figure simply repeats, where the 1 Wh export register needs
|
||||
# 360 s to advance at -10 W and the fingerprint therefore stands still.
|
||||
#
|
||||
# So it is constructed, from the operating point the capture measures (mean grid
|
||||
# -14.2 W) rather than invented: one hour of a perfectly healthy converged meter
|
||||
# that happens not to move.
|
||||
print("TEL-05's low-power case - a converged meter that legitimately repeats")
|
||||
tel05 = FreezeWatchdog(FreezeWatchdogConfig(hold_s=300))
|
||||
t5 = tuning(LIVE_MAX_W)
|
||||
tgt, iw, sc = 0.0, 0.0, 0
|
||||
bare_would_fire = False
|
||||
tel05_cmd = 0.0
|
||||
for k in range(3600):
|
||||
if k % 15 == 0: # cycle_floor_s, the only trigger left
|
||||
d = compute(prev_w=tgt, grid_w=-14.2, actual_w=tgt, tuning=t5,
|
||||
sat_count=sc, i_w=iw)
|
||||
tgt, iw, sc = d.target_w, d.i_w, d.sat_count
|
||||
tel05_cmd = max(tel05_cmd, abs(tgt))
|
||||
# The REJECTED design, written out so the case can be shown to be real.
|
||||
bare_would_fire = bare_would_fire or float(k) >= 300
|
||||
tel05.evaluate(float(k), tgt, LIVE_MAX_W, T0 + timedelta(seconds=k))
|
||||
print(f" an hour at -14.2 W: worst |command| {tel05_cmd:.0f} W, "
|
||||
f"unchanged_s reaches 3599 s, episodes {tel05.episodes}")
|
||||
check("the bare unchanged_s threshold TEL-05 rejected WOULD fire here",
|
||||
bare_would_fire)
|
||||
check("the conjunction does not - this is what the rail term buys",
|
||||
tel05.episodes == 0)
|
||||
check("...and the command stayed nowhere near the rail",
|
||||
tel05_cmd < rail_w(LIVE_MAX_W))
|
||||
|
||||
# The structural version of the same point, re-derived rather than asserted in
|
||||
# prose: the slowest register a HEALTHY meter can have while still being seen as
|
||||
# unchanged for hold_s is 3600/hold_s watts, and at the shipped defaults that
|
||||
# figure is inside the deadband, so the command there is parked at 0 W. If
|
||||
# someone lowers meter_freeze_s or narrows the deadband, this is the check that
|
||||
# should stop them.
|
||||
DEADBAND_W = 15.0
|
||||
slowest_healthy_w = 3600.0 / 300.0
|
||||
check("a healthy meter slow enough to look unchanged is inside the deadband",
|
||||
slowest_healthy_w < DEADBAND_W)
|
||||
_park = compute(prev_w=0.0, grid_w=-slowest_healthy_w, actual_w=0.0,
|
||||
tuning=tuning(LIVE_MAX_W), sat_count=0, i_w=0.0)
|
||||
check("...and the shipped law really does park the command there",
|
||||
_park.target_w == 0.0)
|
||||
|
||||
# ⚠️ THE PROOF THAT THE REPLAY IS CAPABLE OF FIRING AT ALL. Without this, "the
|
||||
# converged capture is silent" is satisfied by a detector that is wired to
|
||||
# nothing. Drop the hold to 1 s and the rail to nothing, and the SAME replay
|
||||
# must alarm - so the silence above is the data's doing, not the harness's.
|
||||
wd_hot, _, _, fired_hot = replay(1.0, 20.0)
|
||||
check("...and the same replay DOES alarm once both terms are made reachable",
|
||||
fired_hot is not None and wd_hot.episodes > 0)
|
||||
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
# 3. a genuinely frozen meter, over real HTTP, through the real transport
|
||||
# --------------------------------------------------------------------------- #
|
||||
def find_hwsim():
|
||||
"""The rig's own fake meter, if the infra repo is reachable."""
|
||||
cands = []
|
||||
if os.environ.get("GOODWE_SIM"):
|
||||
cands.append(Path(os.environ["GOODWE_SIM"]) / "hwsim.py")
|
||||
cands.append(HERE.parents[1] / "goodwe" / "sim" / "hwsim.py")
|
||||
for c in cands:
|
||||
if c.exists():
|
||||
return c
|
||||
return None
|
||||
|
||||
|
||||
STUB = r'''
|
||||
import http.server, json, sys, threading, time
|
||||
FROZEN = {"active_power_w": 700.0, "active_power_l1_w": 700.0,
|
||||
"total_power_import_kwh": 1234.567, "total_power_export_kwh": 890.123}
|
||||
moving = len(sys.argv) > 2 and sys.argv[2] == "moving"
|
||||
t0 = time.monotonic()
|
||||
class H(http.server.BaseHTTPRequestHandler):
|
||||
def do_GET(self):
|
||||
d = dict(FROZEN)
|
||||
if moving:
|
||||
# A REAL railed condition: a big steady import, so the power figure
|
||||
# jitters and the 1 Wh registers advance the way physics makes them.
|
||||
el = time.monotonic() - t0
|
||||
d["active_power_w"] = 7000.0 + (int(el * 10) % 7)
|
||||
d["active_power_l1_w"] = d["active_power_w"]
|
||||
d["total_power_import_kwh"] = round(1234.567 + 7000 * el / 3.6e6, 3)
|
||||
raw = json.dumps(d).encode()
|
||||
self.send_response(200)
|
||||
self.send_header("Content-Type", "application/json")
|
||||
self.send_header("Content-Length", str(len(raw)))
|
||||
self.end_headers()
|
||||
self.wfile.write(raw)
|
||||
def log_message(self, *a): pass
|
||||
http.server.ThreadingHTTPServer(("127.0.0.1", int(sys.argv[1])), H).serve_forever()
|
||||
'''
|
||||
|
||||
HWSIM_DRIVER = r'''
|
||||
import sys, threading, time
|
||||
sys.path.insert(0, sys.argv[3])
|
||||
import hwsim
|
||||
hwsim.serve(int(sys.argv[1]))
|
||||
mode = sys.argv[2]
|
||||
hwsim.set_grid(7000.0)
|
||||
if mode == "freeze":
|
||||
hwsim.fault = "freeze" # exactly `hwsim.py --fault freeze`
|
||||
while True:
|
||||
# The plant keeps moving underneath either way. Under `freeze` hwsim's own
|
||||
# set_grid() returns early, which is the whole point of that fault.
|
||||
hwsim.set_grid(7000.0 + (int(time.monotonic() * 10) % 7))
|
||||
time.sleep(0.2)
|
||||
'''
|
||||
|
||||
|
||||
async def live_run(port, mode, hold_s=10.0, seconds=16.0, max_w=LIVE_MAX_W):
|
||||
"""Poll a real HTTP meter through the real transport and drive the detector."""
|
||||
ingest = P1Ingest(phases=1, max_age_s=30)
|
||||
wd = FreezeWatchdog(FreezeWatchdogConfig(hold_s=hold_s))
|
||||
t = tuning(max_w)
|
||||
target, i_w, sat = 0.0, 0.0, 0
|
||||
fired_at, polls, worst_unchanged, worst_cmd = None, 0, 0.0, 0.0
|
||||
async with aiohttp.ClientSession() as session:
|
||||
src = HomeWizardLocalSource(session, ingest, "127.0.0.1", port=port,
|
||||
poll_s=1.0)
|
||||
start = time.monotonic()
|
||||
while time.monotonic() - start < seconds:
|
||||
if await src.poll_once():
|
||||
polls += 1
|
||||
grid = ingest.net_w
|
||||
d = compute(prev_w=target, grid_w=grid, actual_w=target,
|
||||
tuning=t, sat_count=sat, i_w=i_w)
|
||||
target, i_w, sat = d.target_w, d.i_w, d.sat_count
|
||||
worst_unchanged = max(worst_unchanged, src.unchanged_s or 0.0)
|
||||
worst_cmd = max(worst_cmd, abs(target))
|
||||
if wd.evaluate(src.unchanged_s, target, max_w,
|
||||
datetime.now(timezone.utc)) and fired_at is None:
|
||||
fired_at = time.monotonic() - start
|
||||
await asyncio.sleep(1.0)
|
||||
return fired_at, polls, worst_unchanged, worst_cmd
|
||||
|
||||
|
||||
def with_server(argv, port, fn):
|
||||
proc = subprocess.Popen([sys.executable, "-c"] + argv,
|
||||
stdout=subprocess.DEVNULL, stderr=subprocess.PIPE)
|
||||
try:
|
||||
deadline = time.monotonic() + 10
|
||||
while time.monotonic() < deadline:
|
||||
try:
|
||||
import socket
|
||||
with socket.create_connection(("127.0.0.1", port), 0.3):
|
||||
break
|
||||
except OSError:
|
||||
time.sleep(0.1)
|
||||
else:
|
||||
raise RuntimeError("the fake meter never came up")
|
||||
return fn()
|
||||
finally:
|
||||
proc.kill()
|
||||
proc.wait()
|
||||
|
||||
|
||||
hw = find_hwsim()
|
||||
print(f"frozen meter over HTTP - using {'the rig hwsim at ' + str(hw) if hw else 'the local stub'}")
|
||||
if hw:
|
||||
def argv_for(mode):
|
||||
return [HWSIM_DRIVER, "8791" if mode == "freeze" else "8792", mode,
|
||||
str(hw.parent)]
|
||||
else:
|
||||
def argv_for(mode):
|
||||
return [STUB, "8791" if mode == "freeze" else "8792",
|
||||
"frozen" if mode == "freeze" else "moving"]
|
||||
|
||||
fired, polls, unch, cmd = with_server(
|
||||
argv_for("freeze"), 8791,
|
||||
lambda: asyncio.run(live_run(8791, "freeze")))
|
||||
print(f" freeze: {polls} polls, worst unchanged {unch:.1f} s, "
|
||||
f"worst |command| {cmd:.0f} W, alarm at "
|
||||
f"{'never' if fired is None else f'{fired:.1f} s'}")
|
||||
check("the transport really polled a live server", polls >= 10)
|
||||
check("a frozen meter raises the alarm", fired is not None)
|
||||
check("...and only after the hold, not on the first railed poll",
|
||||
fired is None or fired >= 10.0)
|
||||
|
||||
fired2, polls2, unch2, cmd2 = with_server(
|
||||
argv_for("moving"), 8792,
|
||||
lambda: asyncio.run(live_run(8792, "moving")))
|
||||
print(f" moving: {polls2} polls, worst unchanged {unch2:.1f} s, "
|
||||
f"worst |command| {cmd2:.0f} W, alarm at "
|
||||
f"{'never' if fired2 is None else f'{fired2:.1f} s'}")
|
||||
check("the moving meter also drove the command to the rail", cmd2 >= rail_w(LIVE_MAX_W))
|
||||
check("a REAL railed condition against a live meter stays silent", fired2 is None)
|
||||
check("...because the meter kept moving", unch2 < 10.0)
|
||||
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
# 4. the wiring, because a correct detector nobody calls is not a detector
|
||||
# --------------------------------------------------------------------------- #
|
||||
# ⚠️ EVERYTHING ABOVE PASSES WITH `app/freeze.py` IMPORTED BY NOTHING. That is
|
||||
# the shape of defect this project keeps finding: the mechanism is right, the
|
||||
# suite is green, and the shipped path never reaches it. So the real
|
||||
# `Controller.cycle()` is driven here, against the real arbiter and the real
|
||||
# control law, with a stand-in transport that reports `unchanged_s` the way
|
||||
# HomeWizardLocalSource does - and the assertion is on the SERVICE CALL that
|
||||
# leaves the process, not on the watchdog's own flag.
|
||||
print("the wiring - Controller.cycle() actually raises the notification")
|
||||
|
||||
|
||||
class _Store:
|
||||
data: dict = {}
|
||||
|
||||
def set(self, *a):
|
||||
pass
|
||||
|
||||
def get_time(self, *a):
|
||||
return None
|
||||
|
||||
|
||||
class _Pub:
|
||||
enabled = False
|
||||
|
||||
def publish(self, *a, **k):
|
||||
pass
|
||||
|
||||
def close(self):
|
||||
pass
|
||||
|
||||
|
||||
class _Hass:
|
||||
def __init__(self, grid):
|
||||
self.grid = grid
|
||||
self.calls = []
|
||||
self.writes = []
|
||||
# The plant tracks the command instantly, as in test_loop.py. Without
|
||||
# it the saturation freeze pins the command short of the rail and the
|
||||
# runaway under test never happens - which would have made this a check
|
||||
# that passes for the wrong reason.
|
||||
self.batt = 0.0
|
||||
|
||||
async def limits(self, entity):
|
||||
return (-5000.0, 5000.0, 1.0)
|
||||
|
||||
async def number(self, entity, invert=False):
|
||||
return {"sensor.grid": self.grid, "sensor.soc": 50.0,
|
||||
"sensor.batt": self.batt}.get(entity)
|
||||
|
||||
async def set_number(self, entity, value):
|
||||
self.writes.append(float(value))
|
||||
self.batt = float(value)
|
||||
return True
|
||||
|
||||
async def call(self, domain, service, data):
|
||||
self.calls.append((domain, service, data))
|
||||
return True
|
||||
|
||||
|
||||
class _Source:
|
||||
"""Only the attribute the controller reads. Duck-typed like the real one."""
|
||||
|
||||
def __init__(self, unchanged_s):
|
||||
self.unchanged_s = unchanged_s
|
||||
|
||||
|
||||
def wired(unchanged_s, grid, cycles=60, **over):
|
||||
async def go():
|
||||
hass = _Hass(grid)
|
||||
c = Controller(dict(
|
||||
{"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
|
||||
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
|
||||
"meter_source": "off", "max_w": LIVE_MAX_W, "gain": 0.6,
|
||||
"slew_w": 1000, "deadband_w": 15, "target_grid_w": -10,
|
||||
"step_w": 10, "heartbeat_s": 10, "stale_input_s": 15},
|
||||
**over), hass, _Store(), _Pub(), stop=asyncio.Event())
|
||||
c.auto = True
|
||||
c.dev_min, c.dev_max = -5000.0, 5000.0
|
||||
c.p1_source = _Source(unchanged_s)
|
||||
for _ in range(cycles):
|
||||
await c.read_inputs()
|
||||
await c.cycle()
|
||||
return hass, c
|
||||
return asyncio.run(go())
|
||||
|
||||
|
||||
hass_f, ctl_f = wired(3600.0, 4000.0)
|
||||
notes = [d for dom, svc, d in hass_f.calls
|
||||
if (dom, svc) == ("persistent_notification", "create")]
|
||||
# The status row lives behind `p1_enabled`, which is what a homewizard_local
|
||||
# install has. Flipped here rather than plumbing a whole P1 transport in - the
|
||||
# row's own content is what is under test.
|
||||
ctl_f.p1_enabled = True
|
||||
rows = [c for c in ctl_f.checks() if "METER MAY BE FROZEN" in c["text"]]
|
||||
print(f" frozen at +4000 W: command ran to {ctl_f.target:.0f} W, "
|
||||
f"{len(notes)} notification(s), {len(rows)} red status row(s)")
|
||||
check("the shipped cycle() raises exactly one HA notification", len(notes) == 1)
|
||||
check("...with a fixed notification_id so repeats replace, not stack",
|
||||
notes and notes[0].get("notification_id") == "goodwe_meter_frozen")
|
||||
check("...and it says the controller is still running",
|
||||
bool(notes) and "STILL RUNNING" in notes[0]["message"])
|
||||
check("the status page carries a failed row saying so",
|
||||
len(rows) == 1 and not rows[0]["ok"] and not rows[0]["warn"])
|
||||
check("the event log names it", any("METER FROZEN" in e for e in ctl_f.events))
|
||||
# ⚠️ NOTIFY, NOT TRIP. If a later cut turns this into a trip it must come here
|
||||
# and change this expectation deliberately, not discover it in the field.
|
||||
check("and it does NOT command 0 W - this cut is an alarm only",
|
||||
abs(ctl_f.target) >= rail_w(LIVE_MAX_W))
|
||||
|
||||
hass_n, ctl_n = wired(3600.0, -14.2)
|
||||
check("wired up, TEL-05's converged case still raises nothing",
|
||||
not [1 for dom, svc, _ in hass_n.calls if svc == "create"])
|
||||
hass_m, ctl_m = wired(2.0, 8000.0)
|
||||
check("wired up, a real railed load against a moving meter raises nothing",
|
||||
not [1 for dom, svc, _ in hass_m.calls if svc == "create"]
|
||||
and abs(ctl_m.target) >= rail_w(LIVE_MAX_W))
|
||||
check("an uncovered transport (no unchanged_s) raises nothing, and says so",
|
||||
not [1 for dom, svc, _ in wired(None, 4000.0)[0].calls if svc == "create"])
|
||||
|
||||
print()
|
||||
if fails:
|
||||
print(f"{len(fails)} FAILED: {', '.join(fails)}")
|
||||
sys.exit(1)
|
||||
print("all checks passed")
|
||||