MAINT-04 (#10) landed on release/1.0 mid-review, so both branches had prepended a stanza. config.yaml and DOCS.md auto-merged clean; only the CHANGELOG needed a hand. Both stanzas are kept verbatim, MAINT-04's Unreleased above the new 0.5.2 - no text from either author edited. MAINT-04 is unreleased and 0.5.2 is being cut here, so a release manager may want to fold the two; that is an editorial call, not a reviewer's. Full suite green on the merged tree: arbiter, control, loop, maintenance, p1, validate, watchdog, freeze. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
244 lines
9.7 KiB
YAML
244 lines
9.7 KiB
YAML
name: GoodWe RS485 Controller
|
|
version: "0.5.2"
|
|
slug: goodwe_controller
|
|
description: >-
|
|
Drives a GoodWe ES/BP battery inverter over RS485 by emulating its smart
|
|
meter, holding net grid exchange at zero and running a monthly battery
|
|
maintenance cycle.
|
|
url: https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
|
|
arch:
|
|
- aarch64
|
|
- amd64
|
|
- armv7
|
|
init: false
|
|
startup: application
|
|
boot: auto
|
|
|
|
# Needed to read the meter and to write the ESPHome setpoint number.
|
|
homeassistant_api: true
|
|
hassio_api: true
|
|
|
|
# Own diagnostics/operations UI inside HA. This is what a field tech and a
|
|
# remote supporter both look at, so it is not optional.
|
|
ingress: true
|
|
ingress_port: 8099
|
|
panel_icon: mdi:battery-sync
|
|
panel_title: GoodWe
|
|
|
|
# Optional: publish status entities by MQTT discovery. `want` rather than
|
|
# `need` - the add-on runs fine with no broker, it just publishes nothing.
|
|
services:
|
|
- mqtt:want
|
|
|
|
options:
|
|
# --- sources (required) ---------------------------------------------------
|
|
meter_entity: sensor.p1_meter_active_power
|
|
meter_invert: false
|
|
soc_entity: ""
|
|
batt_entity: ""
|
|
batt_invert: false
|
|
setpoint_entity: ""
|
|
|
|
# --- P1 meter ingestion (specs §5.2 / §14 `meter:`) -------------------------
|
|
# `off` keeps the original single meter_entity path above, so an existing
|
|
# install is untouched until it opts in. ha_dsmr subscribes to the DSMR
|
|
# integration's entities over the HA WebSocket; mqtt_p1 reads the topic below;
|
|
# ha_signed reads ONE signed HA entity (+ import / - export), which is what a
|
|
# HomeWizard P1 publishes and what ha_dsmr cannot consume.
|
|
# homewizard_local skips Home Assistant entirely and polls the meter's own
|
|
# local API. ⚠️ It is the ONLY mode whose sensor.p1_sample_age_s measures when
|
|
# the meter REPORTED rather than when the value last CHANGED - HA emits
|
|
# nothing at all for a repeated reading - so it is the only mode a firmware
|
|
# watchdog may threshold. See DOCS.md.
|
|
meter_source: "off"
|
|
meter_phases: 1
|
|
meter_max_age_s: 30
|
|
meter_mqtt_topic: ""
|
|
# homewizard_local only. The meter's own address, `host` or `host:port`.
|
|
p1_host: ""
|
|
# homewizard_local only. Seconds between polls. Must be well under
|
|
# meter_max_age_s - the age is never fresher than this interval - and there is
|
|
# nothing to gain below the meter's own ~5.0 s update rate (NOTES.md:640).
|
|
meter_poll_s: 5
|
|
# The two UNSIGNED Belgian registers. The EMS derives net power from them
|
|
# (import - export); do NOT point these at a signed template sensor.
|
|
p1_import_entity: ""
|
|
p1_export_entity: ""
|
|
# Optional, in L1..L3 order. Required for the capacity-tariff peak on a
|
|
# three-phase connection; the list length must equal meter_phases.
|
|
p1_phase_import_entities: []
|
|
p1_phase_export_entities: []
|
|
# ha_signed only. ONE signed net-power sensor: positive = import from the
|
|
# grid, negative = export to it. Do NOT split it into two template sensors -
|
|
# the split is done in the add-on (p1.split_signed) precisely so the sign
|
|
# convention is tested rather than living in unreviewed YAML.
|
|
p1_net_entity: ""
|
|
# Optional, in L1..L3 order, each one signed the same way. Same role as
|
|
# p1_phase_import_entities: the capacity-tariff peak on a three-phase
|
|
# connection. The list length must equal meter_phases.
|
|
p1_phase_net_entities: []
|
|
|
|
# --- control ---------------------------------------------------------------
|
|
max_w: 2000
|
|
gain: 0.6
|
|
slew_w: 1000
|
|
deadband_w: 15
|
|
target_grid_w: -10
|
|
step_w: 10
|
|
saturation_w: 500
|
|
saturation_cycles: 3
|
|
integrator_max_w: 0
|
|
heartbeat_s: 10
|
|
stale_input_s: 15
|
|
cycle_floor_s: 15
|
|
auto_start: false
|
|
|
|
# --- SAFETY-02 sign-disagreement watchdog ----------------------------------
|
|
# Trips when the emitted setpoint and the P1 net figure point OPPOSITE ways,
|
|
# both over sign_disagree_w, continuously for sign_disagree_s. Action: 0 W and
|
|
# a failsafe that latches until an operator starts control again.
|
|
#
|
|
# Both defaults are measured, not chosen. On the captured healthy day
|
|
# (2026-08-23) the longest legitimate opposed run - a load step the loop has
|
|
# not caught up with - is 30 s, and sign agreement over the gated samples is
|
|
# 93.4 %. On the captured fault day (2026-08-20) the clusters run 0.0-10.5 %
|
|
# agreement with opposed runs up to 1752 s. 300 W / 180 s sits in the middle of
|
|
# a very wide gap: at 60 s the healthy day still trips nothing, at 300 s the
|
|
# fault day still trips 13 times. There is no reason to move either number
|
|
# without a capture that says so. They are options because the AC says
|
|
# thresholds are defaults rather than constants - not because they are knobs
|
|
# anyone is expected to turn.
|
|
#
|
|
# ⚠️ sign_disagree_w must stay BELOW max_w or the watchdog can never fire (the
|
|
# arbiter bounds the command to +-max_w). validate.py refuses that config.
|
|
sign_disagree_w: 300
|
|
sign_disagree_s: 180
|
|
|
|
# --- SAFETY-18 frozen-but-fresh meter detector -----------------------------
|
|
# Seconds the meter may keep answering with an UNCHANGED measurement while the
|
|
# command stands at the rail before the add-on raises an alarm. Both halves
|
|
# are required: neither one alone is safe, and app/freeze.py carries why.
|
|
#
|
|
# ALARM ONLY. It does not command 0 W and does not latch. A false trip parks
|
|
# the battery; a false notification costs an alert.
|
|
#
|
|
# ⚠️ Only `meter_source: homewizard_local` can see this at all - it is the
|
|
# only transport that reads the meter's own document. On every other source
|
|
# the status page says NOT COVERED rather than "armed".
|
|
#
|
|
# 300 s is measured, not chosen. Over 2399 s of the live house at the
|
|
# converged operating point (sim/scenarios/p1-age-2026-08-26.jsonl.gz, mean
|
|
# grid -14.2 W, 1194 polls, 735 of them repeating the previous reading) the
|
|
# LONGEST run without a distinct reading is 15.4 s (the largest unchanged_s any
|
|
# sample observes is 8.0 s). 300 s is 19.5x the pessimistic figure, and
|
|
# still inside the 900 s quarter that bills the capacity tariff.
|
|
meter_freeze_s: 300
|
|
|
|
# --- maintenance -----------------------------------------------------------
|
|
maintenance_enabled: false
|
|
maintenance_interval_days: 28
|
|
maintenance_start_hour: 10
|
|
# ⚠️ BOTH MUST STAY AT OR BELOW max_w, and that is why they are 2000 rather
|
|
# than the 2500 they shipped as. The cheap-window charge shaping asks the
|
|
# arbiter for `hi = -maintenance_charge_w` against the supervised `lo =
|
|
# -max_w`: above the ceiling that is `lo > hi`, a contradiction resolved to
|
|
# 0 W, so maintenance would SILENTLY NEVER CHARGE in a cheap window on a
|
|
# default install. validate.py refuses that config (rule 6), so these
|
|
# defaults had to become self-consistent with the max_w above rather than
|
|
# ship a configuration the validator rejects.
|
|
#
|
|
# The discharge side is clamped rather than contradicted - it drains at max_w
|
|
# and the arbiter says so - so it is only warned about; it is 2000 here for
|
|
# symmetry and to keep the shipped config warning-free.
|
|
#
|
|
# Raising max_w (the live reference install runs 5000) is what unlocks a
|
|
# faster maintenance cycle. Raise max_w FIRST, then these.
|
|
maintenance_discharge_w: 2000
|
|
maintenance_charge_w: 2000
|
|
maintenance_soc_floor: 11
|
|
maintenance_soc_target: 99
|
|
maintenance_hold_min: 120
|
|
|
|
# --- tariff / capacity tariff (all optional) ------------------------------
|
|
peak_forecast_entity: ""
|
|
peak_cap_w: 3500
|
|
price_now_entity: ""
|
|
price_avg_entity: ""
|
|
|
|
# --- site ------------------------------------------------------------------
|
|
estop_fitted: false
|
|
log_level: info
|
|
|
|
schema:
|
|
meter_entity: str
|
|
meter_invert: bool
|
|
soc_entity: str
|
|
batt_entity: str
|
|
batt_invert: bool
|
|
setpoint_entity: str
|
|
|
|
meter_source: list(off|ha_dsmr|mqtt_p1|ha_signed|homewizard_local)
|
|
# ⚠️ 2 is accepted by this range but is not a real Belgian connection. A
|
|
# telegram whose phase count disagrees is rejected at ingest and logged, so a
|
|
# mis-set 2 shows up immediately as "0 telegrams accepted" rather than as a
|
|
# quietly wrong number.
|
|
meter_phases: int(1,3)
|
|
meter_max_age_s: int(5,300)
|
|
meter_poll_s: int(1,60)
|
|
meter_mqtt_topic: str?
|
|
p1_host: str?
|
|
p1_import_entity: str?
|
|
p1_export_entity: str?
|
|
p1_phase_import_entities:
|
|
- str
|
|
p1_phase_export_entities:
|
|
- str
|
|
p1_net_entity: str?
|
|
p1_phase_net_entities:
|
|
- str
|
|
|
|
max_w: int(100,5000)
|
|
gain: float(0.05,1.0)
|
|
slew_w: int(50,5000)
|
|
deadband_w: int(0,500)
|
|
target_grid_w: float(-200,200)
|
|
step_w: int(1,100)
|
|
saturation_w: int(100,2000)
|
|
saturation_cycles: int(1,10)
|
|
integrator_max_w: int(0,15000)
|
|
heartbeat_s: int(2,25)
|
|
stale_input_s: int(5,120)
|
|
cycle_floor_s: int(5,60)
|
|
auto_start: bool
|
|
|
|
# No "off" value, deliberately: this is a P0 safety check and the schema is
|
|
# not the place to make disarming it a supported configuration.
|
|
sign_disagree_w: int(50,5000)
|
|
sign_disagree_s: int(30,1800)
|
|
|
|
# No "off" value, for SAFETY-02's reason: disarming a safety alarm is not a
|
|
# supported configuration. ⚠️ THE FLOOR OF 60 IS NOT A RECOMMENDATION. At 300 s
|
|
# the slowest a HEALTHY meter's 1 Wh register can tick and still look unchanged
|
|
# is 12 W, which is inside the 15 W deadband, so the two terms of the
|
|
# conjunction are mutually exclusive rather than merely far apart. At 60 s that
|
|
# figure is 60 W and the argument is gone - only the margin is left. See
|
|
# app/freeze.py.
|
|
meter_freeze_s: int(60,3600)
|
|
|
|
maintenance_enabled: bool
|
|
maintenance_interval_days: int(1,90)
|
|
maintenance_start_hour: int(0,23)
|
|
maintenance_discharge_w: int(500,5000)
|
|
maintenance_charge_w: int(500,5000)
|
|
maintenance_soc_floor: int(5,30)
|
|
maintenance_soc_target: int(50,100)
|
|
maintenance_hold_min: int(5,480)
|
|
|
|
peak_forecast_entity: str?
|
|
peak_cap_w: int(500,15000)
|
|
price_now_entity: str?
|
|
price_avg_entity: str?
|
|
|
|
estop_fitted: bool
|
|
log_level: list(trace|debug|info|warning|error)
|