Files
goodwe-addon/goodwe_controller/config.yaml
T
glenn schrooyenandClaude Opus 5 7cde5d862a Merge release/1.0 into SAFETY-18 - CHANGELOG only
MAINT-04 (#10) landed on release/1.0 mid-review, so both branches had
prepended a stanza. config.yaml and DOCS.md auto-merged clean; only the
CHANGELOG needed a hand. Both stanzas are kept verbatim, MAINT-04's
Unreleased above the new 0.5.2 - no text from either author edited.
MAINT-04 is unreleased and 0.5.2 is being cut here, so a release manager
may want to fold the two; that is an editorial call, not a reviewer's.

Full suite green on the merged tree: arbiter, control, loop, maintenance,
p1, validate, watchdog, freeze.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
2026-08-30 03:20:26 +02:00

244 lines
9.7 KiB
YAML

name: GoodWe RS485 Controller
version: "0.5.2"
slug: goodwe_controller
description: >-
Drives a GoodWe ES/BP battery inverter over RS485 by emulating its smart
meter, holding net grid exchange at zero and running a monthly battery
maintenance cycle.
url: https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
arch:
- aarch64
- amd64
- armv7
init: false
startup: application
boot: auto
# Needed to read the meter and to write the ESPHome setpoint number.
homeassistant_api: true
hassio_api: true
# Own diagnostics/operations UI inside HA. This is what a field tech and a
# remote supporter both look at, so it is not optional.
ingress: true
ingress_port: 8099
panel_icon: mdi:battery-sync
panel_title: GoodWe
# Optional: publish status entities by MQTT discovery. `want` rather than
# `need` - the add-on runs fine with no broker, it just publishes nothing.
services:
- mqtt:want
options:
# --- sources (required) ---------------------------------------------------
meter_entity: sensor.p1_meter_active_power
meter_invert: false
soc_entity: ""
batt_entity: ""
batt_invert: false
setpoint_entity: ""
# --- P1 meter ingestion (specs §5.2 / §14 `meter:`) -------------------------
# `off` keeps the original single meter_entity path above, so an existing
# install is untouched until it opts in. ha_dsmr subscribes to the DSMR
# integration's entities over the HA WebSocket; mqtt_p1 reads the topic below;
# ha_signed reads ONE signed HA entity (+ import / - export), which is what a
# HomeWizard P1 publishes and what ha_dsmr cannot consume.
# homewizard_local skips Home Assistant entirely and polls the meter's own
# local API. ⚠️ It is the ONLY mode whose sensor.p1_sample_age_s measures when
# the meter REPORTED rather than when the value last CHANGED - HA emits
# nothing at all for a repeated reading - so it is the only mode a firmware
# watchdog may threshold. See DOCS.md.
meter_source: "off"
meter_phases: 1
meter_max_age_s: 30
meter_mqtt_topic: ""
# homewizard_local only. The meter's own address, `host` or `host:port`.
p1_host: ""
# homewizard_local only. Seconds between polls. Must be well under
# meter_max_age_s - the age is never fresher than this interval - and there is
# nothing to gain below the meter's own ~5.0 s update rate (NOTES.md:640).
meter_poll_s: 5
# The two UNSIGNED Belgian registers. The EMS derives net power from them
# (import - export); do NOT point these at a signed template sensor.
p1_import_entity: ""
p1_export_entity: ""
# Optional, in L1..L3 order. Required for the capacity-tariff peak on a
# three-phase connection; the list length must equal meter_phases.
p1_phase_import_entities: []
p1_phase_export_entities: []
# ha_signed only. ONE signed net-power sensor: positive = import from the
# grid, negative = export to it. Do NOT split it into two template sensors -
# the split is done in the add-on (p1.split_signed) precisely so the sign
# convention is tested rather than living in unreviewed YAML.
p1_net_entity: ""
# Optional, in L1..L3 order, each one signed the same way. Same role as
# p1_phase_import_entities: the capacity-tariff peak on a three-phase
# connection. The list length must equal meter_phases.
p1_phase_net_entities: []
# --- control ---------------------------------------------------------------
max_w: 2000
gain: 0.6
slew_w: 1000
deadband_w: 15
target_grid_w: -10
step_w: 10
saturation_w: 500
saturation_cycles: 3
integrator_max_w: 0
heartbeat_s: 10
stale_input_s: 15
cycle_floor_s: 15
auto_start: false
# --- SAFETY-02 sign-disagreement watchdog ----------------------------------
# Trips when the emitted setpoint and the P1 net figure point OPPOSITE ways,
# both over sign_disagree_w, continuously for sign_disagree_s. Action: 0 W and
# a failsafe that latches until an operator starts control again.
#
# Both defaults are measured, not chosen. On the captured healthy day
# (2026-08-23) the longest legitimate opposed run - a load step the loop has
# not caught up with - is 30 s, and sign agreement over the gated samples is
# 93.4 %. On the captured fault day (2026-08-20) the clusters run 0.0-10.5 %
# agreement with opposed runs up to 1752 s. 300 W / 180 s sits in the middle of
# a very wide gap: at 60 s the healthy day still trips nothing, at 300 s the
# fault day still trips 13 times. There is no reason to move either number
# without a capture that says so. They are options because the AC says
# thresholds are defaults rather than constants - not because they are knobs
# anyone is expected to turn.
#
# ⚠️ sign_disagree_w must stay BELOW max_w or the watchdog can never fire (the
# arbiter bounds the command to +-max_w). validate.py refuses that config.
sign_disagree_w: 300
sign_disagree_s: 180
# --- SAFETY-18 frozen-but-fresh meter detector -----------------------------
# Seconds the meter may keep answering with an UNCHANGED measurement while the
# command stands at the rail before the add-on raises an alarm. Both halves
# are required: neither one alone is safe, and app/freeze.py carries why.
#
# ALARM ONLY. It does not command 0 W and does not latch. A false trip parks
# the battery; a false notification costs an alert.
#
# ⚠️ Only `meter_source: homewizard_local` can see this at all - it is the
# only transport that reads the meter's own document. On every other source
# the status page says NOT COVERED rather than "armed".
#
# 300 s is measured, not chosen. Over 2399 s of the live house at the
# converged operating point (sim/scenarios/p1-age-2026-08-26.jsonl.gz, mean
# grid -14.2 W, 1194 polls, 735 of them repeating the previous reading) the
# LONGEST run without a distinct reading is 15.4 s (the largest unchanged_s any
# sample observes is 8.0 s). 300 s is 19.5x the pessimistic figure, and
# still inside the 900 s quarter that bills the capacity tariff.
meter_freeze_s: 300
# --- maintenance -----------------------------------------------------------
maintenance_enabled: false
maintenance_interval_days: 28
maintenance_start_hour: 10
# ⚠️ BOTH MUST STAY AT OR BELOW max_w, and that is why they are 2000 rather
# than the 2500 they shipped as. The cheap-window charge shaping asks the
# arbiter for `hi = -maintenance_charge_w` against the supervised `lo =
# -max_w`: above the ceiling that is `lo > hi`, a contradiction resolved to
# 0 W, so maintenance would SILENTLY NEVER CHARGE in a cheap window on a
# default install. validate.py refuses that config (rule 6), so these
# defaults had to become self-consistent with the max_w above rather than
# ship a configuration the validator rejects.
#
# The discharge side is clamped rather than contradicted - it drains at max_w
# and the arbiter says so - so it is only warned about; it is 2000 here for
# symmetry and to keep the shipped config warning-free.
#
# Raising max_w (the live reference install runs 5000) is what unlocks a
# faster maintenance cycle. Raise max_w FIRST, then these.
maintenance_discharge_w: 2000
maintenance_charge_w: 2000
maintenance_soc_floor: 11
maintenance_soc_target: 99
maintenance_hold_min: 120
# --- tariff / capacity tariff (all optional) ------------------------------
peak_forecast_entity: ""
peak_cap_w: 3500
price_now_entity: ""
price_avg_entity: ""
# --- site ------------------------------------------------------------------
estop_fitted: false
log_level: info
schema:
meter_entity: str
meter_invert: bool
soc_entity: str
batt_entity: str
batt_invert: bool
setpoint_entity: str
meter_source: list(off|ha_dsmr|mqtt_p1|ha_signed|homewizard_local)
# ⚠️ 2 is accepted by this range but is not a real Belgian connection. A
# telegram whose phase count disagrees is rejected at ingest and logged, so a
# mis-set 2 shows up immediately as "0 telegrams accepted" rather than as a
# quietly wrong number.
meter_phases: int(1,3)
meter_max_age_s: int(5,300)
meter_poll_s: int(1,60)
meter_mqtt_topic: str?
p1_host: str?
p1_import_entity: str?
p1_export_entity: str?
p1_phase_import_entities:
- str
p1_phase_export_entities:
- str
p1_net_entity: str?
p1_phase_net_entities:
- str
max_w: int(100,5000)
gain: float(0.05,1.0)
slew_w: int(50,5000)
deadband_w: int(0,500)
target_grid_w: float(-200,200)
step_w: int(1,100)
saturation_w: int(100,2000)
saturation_cycles: int(1,10)
integrator_max_w: int(0,15000)
heartbeat_s: int(2,25)
stale_input_s: int(5,120)
cycle_floor_s: int(5,60)
auto_start: bool
# No "off" value, deliberately: this is a P0 safety check and the schema is
# not the place to make disarming it a supported configuration.
sign_disagree_w: int(50,5000)
sign_disagree_s: int(30,1800)
# No "off" value, for SAFETY-02's reason: disarming a safety alarm is not a
# supported configuration. ⚠️ THE FLOOR OF 60 IS NOT A RECOMMENDATION. At 300 s
# the slowest a HEALTHY meter's 1 Wh register can tick and still look unchanged
# is 12 W, which is inside the 15 W deadband, so the two terms of the
# conjunction are mutually exclusive rather than merely far apart. At 60 s that
# figure is 60 W and the argument is gone - only the margin is left. See
# app/freeze.py.
meter_freeze_s: int(60,3600)
maintenance_enabled: bool
maintenance_interval_days: int(1,90)
maintenance_start_hour: int(0,23)
maintenance_discharge_w: int(500,5000)
maintenance_charge_w: int(500,5000)
maintenance_soc_floor: int(5,30)
maintenance_soc_target: int(50,100)
maintenance_hold_min: int(5,480)
peak_forecast_entity: str?
peak_cap_w: int(500,15000)
price_now_entity: str?
price_avg_entity: str?
estop_fitted: bool
log_level: list(trace|debug|info|warning|error)