| Author | SHA1 | Message | Date | |
|---|---|---|---|---|
|
|
04292c4a08 |
DATA-01: thirty days of the real meter, and what AC 3 actually measures
checks / unit (pull_request) Successful in 3m36s
TARIFF-01 and SAFETY-07 both merged with AC 3 - "monthly peak held under
the soft limit in >= 95 % of intervals over a 30-day simulation replay" -
honestly unmet, because two days of capture existed and it was believed
nothing longer could be produced. That belief was a true statement about
the past read as a claim about the future: HA's recorder still held the
whole month, and the reason nobody found out is that the 2026-08-25
export was a one-off script that left no artefact.
So the exporter is committed and runnable now.
scenarios/p1-net-30d-2026-08/ is 2026-08-01 to 2026-08-30, 485,841
samples, 30/30 days read, 0 failed, 4.13 MB gzipped, in the schema the
two committed days already fixed.
VERIFIED AGAINST THE DAYS THAT EXIST. `--verify` re-fetches 2026-08-20
and 2026-08-23 by this exact route and reproduces both committed files
BYTE FOR BYTE after decompression (865,024 B / 15,600 samples and
894,387 B / 16,351 samples). The gzip containers differ by design: this
exporter writes mtime 0 so its output is reproducible, where the one-off
wrote a wall clock.
A FAILED READ IS NOT AN OBSERVATION. A day whose read fails writes no
file, is recorded "read": "FAILED", and the run exits non-zero; the
entity is proved to exist through /api/states before any empty day is
believed, because a typo would otherwise answer 200 [] thirty times and
produce a consistent dataset of nothing. Nothing is interpolated, so the
month's 13 gaps (1291 s, 99.95 % covered) and its 3 `unavailable`
samples stay visible as holes.
SIZE: COMMITTED, DELIBERATELY, AND MEASURED. A git bundle of the whole
history goes from 1.58 MB (release/1.0 @
|
||
|
|
f4914a174a |
TARIFF-01: measure the month's billed peak, and make it survive a restart
checks / unit (pull_request) Successful in 2m38s
The 15-minute block average was already built and unwired. p1.QuarterAverager computes clock-aligned 900 s blocks, time-weighted over irregular telegram spacing, offtake-only and per-phase; P1Ingest.blocks was a 96-entry list in memory that a restart erased. So this is the persistence and the monthly reduction, not a second accumulator - a second one would be a second source of truth for the exact quantity the money depends on. BLOCKS, NOT A SLIDING WINDOW. The card says "rolling"; 9.1 bills "the highest 15-minute average offtake" and states its own worked case per QUARTER - one 4998 W quarter moving a monthly peak from 4832 to 5013 W. A trailing window reports a peak the meter never bills, and reports it HIGH: a burst straddling :15 fills the window completely while contributing to two block averages at partial weight. DELIVERED, NOT INTENDED. tariff.py only ever sees P1Sample - the meter's own reading - and never a setpoint. SAFETY-20's open question does not arise for a capacity tariff: the utility integrates the current that flowed. AN UNREADABLE STORE IS NOT A ZERO PEAK. peak() answers OBSERVED / NO_RECORD / NOT_OBSERVED with peak_w None unless observed, which is riglock.holder()'s fix applied to something that spends money. A peak read as 0 W hands SAFETY-07 maximum headroom and disarms the guard at the moment its own storage breaks. Restart mid-block resumes the accumulator through a new snapshot()/restore() pair, checkpointed every 15 s and cleared in the same breath as a block close. The held sample keeps its ORIGINAL timestamp, so an outage is integrated under the same max_hold_s rule a running process would apply. quarter_start is the primary key and a re-bank may only ever RAISE a figure. Calendar months are LOCAL: a quarter starting 22:15 UTC on 31 August bills in September. No new option (the limit is the existing peak_cap_w), so config.yaml and validate.py are untouched and CFG-03 is not widened. No second peak entity: peak_forecast_entity stays the input to maintenance_charge_floor(), because repointing that consumer changes what moves energy and belongs to SAFETY-07. AC 3 is NOT met. It asks for 30 days of replay; two days of this house's real meter exist and are committed here. test_tariff.py part 9 replays them, reports the percentage next to the sample size in days, and asserts nothing about 95 %. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC |