Thirty days of the house's own P1 meter, exported from HA's recorder with a committed exporter, closing the dataset gap that made TARIFF-01's and SAFETY-07's AC 3 unmeetable. 2879 closed quarters, 485841 samples, 99.950 % covered, 13 gaps over 30 s and nothing interpolated. Reviewed independently. The re-export is byte-for-byte identical after decompression on both previously committed days (865024 B / 15600 samples and 894387 B / 16351 samples), verified by decompressing and comparing rather than by reading --verify; the only difference is the gzip mtime field, and writing 0 rather than a wall clock makes this exporter reproducible where the 2026-08-25 one-off was not. The committed CRLF is reproduced rather than tidied because reproducing it IS the verification, and .gitattributes marks *.gz binary so git can never drift it - confirmed with git check-attr. All 30 manifest sha256s match. replay_ac3.py --expect 189/190 reproduces test_peakguard part 6 exactly: 5029.8 -> 3485.3 W, 189/190, 878 Wh, 110 graded + 5 blind - every one a figure the reviewer had already derived independently on a different harness while reviewing TARIFF-01 and SAFETY-07. AND THE RESULT IS A FINDING ABOUT THE CRITERION. Over the month the guard takes the peak from 5029.8 W to 4107.3 W (-18.3 %, still over the 3500 W soft limit) while moving the interval count from 98.89 % to 98.99 %. The UNCONTROLLED month already passes the 95 % bar, with 112 quarters of slack, and the guard contributes 3 - a signal-to-threshold ratio of 0.021. The criterion counts intervals while the capacity tariff bills the month's maximum, so it cannot separate a working guard from an absent one. AC 3 is met on the letter and uninformative on the substance; it should not be read as evidence the guard works, and if rewritten it should be on the monthly peak. The failed-read discipline was verified by producing all three states: a typo'd entity and an unreachable recorder both exit 1 having written nothing, and a day whose read fails is recorded FAILED with file null, no .gz, days_failed 2 and empty_days [] - so an empty response cannot look like a quiet hour. The 30 days sit in a subdirectory and are glob-invisible to both suites' non-recursive scenarios/p1-net-*.jsonl.gz; neither suite had a check added, removed or altered. Full suite green, 15 files.
GoodWe RS485 Controller — Home Assistant add-on repository
Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.
repository.yaml add-on repository metadata
goodwe_controller/ the add-on
config.yaml manifest + options schema (the per-site config form)
app/ the controller
control.py the control law — pure functions, no I/O
maintenance.py the monthly cycle state machine
hass.py Supervisor/Core API access
store.py persistent state in /data
mqtt.py optional status entities
web.py ingress UI
main.py orchestration, heartbeat, failsafe behaviour
test_control.py runnable checks — no framework needed
test_maintenance.py runnable checks — walks a full cycle in fake time
DOCS.md the add-on's documentation tab
firmware/goodwe-master.yaml ESPHome config for the T-CAN485
estop/rs485_log.py optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf the guide techs carry (10pp, A4)
docs/build_guide.py its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md how to edit and rebuild the guide
Picking this up after a break? Read HANDOVER.md first — current state,
what is known broken, and what to do next.
Install
Settings → Add-ons → Add-on store → ⋮ → Repositories → add
https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install GoodWe RS485 Controller.
⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
goodwe_controller/ into the machine's /addons/ folder, then
ha store reload — it appears as a Local add-on.
⚠️ Bump version: in goodwe_controller/config.yaml for every change.
Supervisor keys the built image by that version, so without a bump it silently
reuses the old image and your fix appears not to work — on your bench and on
every client's machine.
Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.
Read this first
The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.
Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:
- ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
- Wind-down before firmware updates — 0 W written before the update starts.
- RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.
Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md
§10 signed.
Development
The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:
cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py
Both must pass before shipping any change. They are not unit-test theatre —
each assertion corresponds to a rule whose absence produced an observed failure
on real hardware, and the comments in control.py say which.
Compatibility
Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:
| tag | platform | verdict |
|---|---|---|
ESU EMU ESA BPS BPU EMJ IJL |
105 — ES/EM/BP, AA55-era meter bus | supported |
SPB SPN |
745 — SBP G2 (GW…-SBP-20) |
no |
ESN ESC |
745 — ES G2 (GW…-ES-20) |
no |
ETU EHU BTU … |
205/745/753 — ET/EH/BT hybrids | no |
SDT DST MSU NSU … |
PV-only inverters — no battery to control | no |
A "-20" or "G2" suffix means a different platform with a different meter
protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which
is also what Home Assistant's own integration uses to pick a protocol.
- GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
- The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.