adminandClaude Opus 5.5 6918e154c8 SAFETY-97: "gives nothing" is graded against each battery's idle reading
checks / unit (pull_request) Failing after 29m7s
infra-pin / fresh (pull_request) Failing after 2s
B's power reading shows -95 to -118 W at idle (standby draw), so the
|reading| < 100 W refusal band never held a refusing B: never at N=2,
and since SAFETY-94's shared rule not at N=1 either (review F1).

Each unit now learns its idle reading (app/idle.py): only while control
runs, the unit is not refused/stale/tripped and its command has stayed
within 50 W for 120 s; first value a 120 s mean, then a 30 min follow;
samples beyond 250 W dropped, value clamped to 250 W; saved per unit and
restored. The shared refusal evidence, compute()'s N=1 engage and end,
the unit refusal ends, the stale-path refusal and SAFETY-42's "parked"
test are centred on it. Until learned it is 0 W, the rule as it was.

Refusing B caught at N=1 28/28/65 s and N=2 24/24/60 s (1/2/5 s
meters), before never; refusing A unchanged. Healthy B with its offset,
SAFETY-94's scenarios, 96 runs: 0 stale, 0 refused. Live replay: 0.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
2026-10-04 12:21:24 +02:00
adminandClaude Opus 5.5 6759d21ea5 SAFETY-94: a healthy battery that lags or reverses is not flagged as frozen or refusing
checks / unit (pull_request) Successful in 28m10s
infra-pin / fresh (pull_request) Failing after 2s
The stale-reading gate counted its 35 s from the register's last change, so
after a rest the first read after a new command tripped it (SAFETY-58; live
2026-10-03, four trips 1 s after the command). It now counts only the time
the command asked the register to move.

At N=1 the refusal engaged after 12 frozen cycles if the reading was under
100 W at that moment, which a battery reversing through its lag passes at a
1 s meter. The refusal now needs the N>1 evidence at every roster size: under
100 W, one way, for 12 cycles spanning 22 s, restarting when the reading
moves 50 W towards the ask.

DECISIONS/SAFETY-94-lagging-battery.md; test_safety94.py.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-04 00:15:42 +02:00
adminandClaude Opus 5.5 214051d1a8 SAFETY-93 review: a charge that ends by a stale link or a refusal hands back smoothly too
checks / unit (pull_request) Successful in 27m5s
infra-pin / fresh (pull_request) Failing after 1s
A battery still in CHARGE but dropped by the allocator (stale link, or a
SAFETY-73 refusal contradicting its charge) left its -2000 W in the loop's
start point, and B went 0 -> -1600 W in one cycle. The end is now noted
after the unit claims are filed: in CHARGE, live and not contradicted.
Tests: part 6 (stale link, refusal) and a spy on the guard suspension.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-03 00:10:21 +02:00
adminandClaude Opus 5.5 05eb93f139 SAFETY-93: the maintenance charge end hands back smoothly, with no grid charging at a high house
checks / unit (pull_request) Successful in 26m55s
infra-pin / fresh (pull_request) Failing after 1s
At N>=2, when a battery's maintenance charge ended, its watts stayed in the
loop's start point and landed on the other battery (B 0 -> -1600 W in one
cycle, charging from the grid at a 6000 W house). On the cycle a charge
ends, the loop now starts from what the others stood at plus that
battery's new command. N=1 and all identity digests unchanged.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-02 22:38:42 +02:00
adminandClaude Opus 5.5 4cd604afcb SAFETY-91 review: a held-back battery is released 1 point above its reserve
checks / unit (pull_request) Successful in 26m26s
infra-pin / fresh (pull_request) Successful in 1s
A SoC reading flipping across the reserve swapped ~1000 W between the
batteries on each flip (grid +-500 W with unequal lags). Also grades
next_quarter()'s staleness boundary (29.5 / 30.5 s).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-02 14:54:20 +02:00
adminandClaude Opus 5.5 6872353e2e SAFETY-91: a held battery is drawn only after the others are full
checks / unit (pull_request) Successful in 26m19s
infra-pin / fresh (pull_request) Successful in 1s
At N>=2 a battery at or under its own peak reserve now weighs 0 whenever
the site gives (not only for the peak), a draining battery's pin becomes
a floor at its drain rate so it rises before the held one gives, and a
quarter's edge is graded on the next quarter when its first telegram is
late. SAFETY-25 option A stays: the held battery is still drawn once the
others are full. N=1 unchanged.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-02 14:03:54 +02:00
adminandClaude Opus 5.5 7b723a6cd5 SAFETY-85 review: grade discharge only, over the plant's settle time
checks / unit (pull_request) Successful in 25m47s
infra-pin / fresh (pull_request) Successful in 2s
Rule 2 graded each battery against last cycle's command and graded charges
too. On plantsim's battery (10 s lag) at the 2 s meter it warned at every
drain or charge start and 15 times an hour under the peak guard at N=2; a
charge tapering near full warned 11 times in 50 min (SAFETY-42 section 7).
Now a discharge is graded against the least it stood at over SHORT_CYCLES /
SHORT_SPAN_S. DOCS lists `mode-bound` under Loop reason. test_safety85 part 7:
peak guard with a dead battery, lagging plant, taper; part 3: the bound ends
with maintenance.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-01 20:25:41 +02:00
glenn schrooyenandClaude Opus 5.5 4b81387908 SAFETY-85: no false 'not keeping up' while maintenance or the peak guard sets the battery
checks / unit (pull_request) Successful in 25m35s
infra-pin / fresh (pull_request) Successful in 2s
The loop's integrator bound counts only on a cycle the loop decided. A battery
another owner set (maintenance, the peak guard, a safety limit) alarms only
when it gives more than saturation_w less than told for saturation_cycles
cycles. At N>=2 the loop is bounded while maintenance holds a battery, so it
does not wind and control comes back one slew step a cycle. The status row
counts episodes, not cycles. Digests re-pinned where behaviour changed on
purpose; DECISIONS/SAFETY-85-no-false-not-keeping-up.md has the list.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
2026-10-01 19:05:27 +02:00
Claude aa501ffec7 SAFETY-87 review: maintenance pins beside a held battery
checks / unit (pull_request) Successful in 26m5s
infra-pin / fresh (pull_request) Successful in 1s
A draining battery that may still give is raised from its drain rate
towards its rating for the peak floor while another battery is held
(peak > drain); before, the floor's rest landed on the held battery. In a
HOLD, a held battery's own pin counts among the others: a held drain no
longer over-places the site, and a held charge probe no longer parks it.

Tests: test_safety87.py part 10 (drain beside a held battery, N=3 HOLD,
unknown cut-out and unread level at N=3, a stopping row outranks the
running peak alarm). DECISIONS entry updated, incl. the modes-on exception.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
2026-10-01 10:50:01 +02:00
Claude d0db5b8c39 SAFETY-87: peak guard uses every battery that can still give
checks / unit (pull_request) Successful in 25m45s
infra-pin / fresh (pull_request) Successful in 1s
At N>=2 a battery at or under its own peak reserve is held: it gives
nothing for the peak (weight 0 while the site gives) and the guard's need
is placed on the live, non-refusing batteries above theirs. The guard is
floor-limited, and alarms, only when those cannot hold the limit at full
power for ALARM_HOLD_S. The peak alarms no longer read "Not ready" or hold
the Home page at 0 W, because control keeps running. N=1 is byte-identical.

DECISIONS/SAFETY-87-guard-uses-able-batteries.md.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
2026-10-01 09:29:30 +02:00
glenn schrooyenandClaude Opus 5.5 1c41a1e412 SAFETY-86 review: hold the site at the peak floor while a HOLD gives
checks / unit (pull_request) Successful in 24m23s
infra-pin / fresh (pull_request) Successful in 1s
At N>=2 the holding pack's pin follows the guard's floor while the loop
still asks for +5000 W, so the ALLOCATOR "could not be placed" row was
re-logged on every 1 W change and filled the 40-row action log. While the
pin is raised, cycle() now files a site `hold` ceiling at the floor
(P_MAINTENANCE), as SAFETY-84 does for a charge. Filed only when the
holding pack gives; hi == the floor, so it never clashes with it.

Tests: a noisy N=2 house logs no ALLOCATOR row and at most one clamp
row (20 and 20 without the ceiling); the ceiling is the floor itself;
a CHARGE is not refiled at N=1. The DECISIONS entry records the owner's
2026-10-01 decision: the HOLD ends on its clock, no top-up.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-01 02:00:20 +02:00
glenn schrooyenandClaude Opus 5.5 ba31e7c8b1 SAFETY-86: peak guard outranks the maintenance hold
checks / unit (pull_request) Successful in 24m17s
infra-pin / fresh (pull_request) Successful in 1s
During a HOLD the holding battery gives what keeps the quarter at the peak
aim. N=1: the peak floor is refiled at P_MAINTENANCE, as for a drain
(SAFETY-83). N>=2: the hold's pin is raised to the floor minus what the
other live batteries may place, so they give first. A site stop still
decides alone. The hold ends on its clock even if the level dipped.
Below the aim nothing changes (rows identical).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-01 00:56:34 +02:00
glenn schrooyenandClaude Opus 5.5 43a52e7f60 SAFETY-84: maintenance charge at N=2 no longer stalls
checks / unit (pull_request) Successful in 23m57s
infra-pin / fresh (pull_request) Successful in 2s
At N>=2 a cheap-window maintenance charge files a site `hi` (`charge`,
P_MAINT_SHAPE) equal to what the charging pack's own `hi` places, so the
other pack never has to give against it. The charge is sized to the
quarter's headroom under the peak aim so it yields to the peak guard, and
to 0 W under a site safety stop. N=1 byte-identical (safety84_identity).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-30 19:47:15 +02:00
glenn schrooyenandClaude Opus 5.5 79b94024cb Merge release/1.0 (OPT-11 P4, #156) into safety-83-peak-over-drain
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-30 13:35:28 +02:00
adminandClaude Opus 5.5 d77f1b1fdf SAFETY-83: peak guard outranks the maintenance drain at N=1
checks / unit (pull_request) Successful in 16m54s
infra-pin / fresh (pull_request) Successful in 1s
At N=1 the drain is the site SET at P_MAINTENANCE (60), so the peak floor
(P_PEAK, 50) was not applied and the house imported what the drain left.
Where the floor asks for more than the drain rate, main.py now refiles the
peak claim at P_MAINTENANCE, so it wins; safety SETs still park everything.
Nothing else changes: safety78_identity --diff against 35cdffe changes only
cycles where the guard wanted more than the drain; N=2 is byte-identical.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 22:40:14 +02:00
glenn schrooyenandClaude Opus 5.5 b171ada894 Merge release/1.0 (SAFETY-78, #154) into opt11-p4-solar-forecast
checks / unit (pull_request) Successful in 23m54s
infra-pin / fresh (pull_request) Successful in 1s
Conflicts: modetrade.decide() takes both the day plan (targets) and
SAFETY-78's draining flag; the Why line keeps SAFETY-78's other_cycle
ahead of the plan's word (test added).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 22:37:09 +02:00
glenn schrooyenandClaude Opus 5.5 a692560960 Merge release/1.0 (SAFETY-81, #155) into opt11-p4-solar-forecast
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 22:08:52 +02:00
goodwe-review 516bc8b4ec Merge release/1.0 into safety-78-drain-at-two
checks / unit (pull_request) Successful in 18m49s
infra-pin / fresh (pull_request) Successful in 2s
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 21:53:47 +02:00
adminandClaude Opus 5.5 f967073cfe SAFETY-81 review: 10 s hold, ERROR line per episode, more scenarios
checks / unit (pull_request) Successful in 20m31s
infra-pin / fresh (pull_request) Successful in 2s
- The alarm must hold for peakguard.ALARM_HOLD_S (10 s) on the projection's
  clock. A load that tops cap + battery for ~5 s every 30 s alarmed at every
  quarter start while the quarter landed under the aim (sine4500_fast).
- A cycle with no battery reading leaves the hold alone.
- Notified once per quarter, but the ERROR line is written per episode.
- New sim scenarios (sine4500_fast, twice7000, step6500_gap) with 5a4cdc2
  digests; control still byte-identical. Unit checks for export and the
  hold across a missing reading. test_peakguard's saturated fixture moves
  the hold start back instead of waiting it out.
- DECISIONS and DOCS updated: costs of the hold, tolerance reasoning, the
  double count in control left to a follow-up.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 20:58:37 +02:00
goodwe-agent 6eb67c0f9c SAFETY-81: no false 'Load too high' alarms
checks / unit (pull_request) Successful in 16m11s
infra-pin / fresh (pull_request) Successful in 1s
The alarm now also needs peakguard.load_too_high(): with the battery at
full power, the quarter still ends more than 10 W over the real limit.
The battery reading is the lower of this cycle's and the last, so a meter
sample from before the battery's last increase is not counted twice.
At most one alarm per quarter. Control outputs unchanged.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 19:55:38 +02:00
Claude 5d27f8496f SAFETY-78: maintenance drain at N=2 no longer stalls
checks / unit (pull_request) Failing after 17m13s
infra-pin / fresh (pull_request) Successful in 2s
At two inverters the drain pins its pack and the site target is split
around the pin. Below the pin the other pack had to charge, the allocator
refused the opposite directions, and the site sat at 0 W with an ARBITER
line every cycle (house below or above the drain rate, or a grid charge).

main.py now files a site limit `drain` (lo = what the pin places, at
P_MAINTENANCE) at N>=2 while a pack drains, so the other pack only adds
power in the same direction. A drain that cannot give power waits with
one log line. With battery modes on, no grid charge while a pack drains,
and the other battery's card says why. N=1 is byte-identical.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 19:52:51 +02:00
Claude eb10537aee OPT-11 P4: solar forecast and day plan
A Home Assistant solar forecast (Forecast.Solar, Solcast or Open-Meteo
shapes) and the add-on's own hourly house use decide, before each cheap
run, whether the sun will fill each battery before the expensive hours.
Leftover solar then buys from the grid only the shortfall; Cheap hours only
skips the part the sun covers; Solar first never grid-charges. No, stale or
failed forecast: P3 option A exactly (12 digests pinned from 5a4cdc2).

Replay (16 recorded days, forecast errors from Elia's day-ahead BE solar):
year-earlier prices P4 19.15 vs P2 19.33 / option A 19.44 / old trade 18.14;
real 2026 prices P4 29.19 vs 32.26 / 32.01 / 31.40 EUR net.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 19:29:32 +02:00
Claude dev agent 6dab4ec16b OPT-11 P3, owner option A: selling off, Leftover solar takes solar only
checks / unit (pull_request) Successful in 15m12s
infra-pin / fresh (pull_request) Successful in 1s
Owner decision 2026-09-29. Selling is off until it can be judged on the price
the grid pays: packmode.SELLING_ENABLED = False makes read() answer
sell=False whatever the store holds, pack_sell is refused ("Selling is off
for now."), and the page has no selling switch; the sell code stays. Until
the P4 forecast, only Cheap hours only charges from the grid
(packmode.GRID_CHARGE_MODES); Leftover solar holds and gives in the
expensive runs. Help, Today and plan lines, DOCS and DECISIONS follow.
Replay, 16 days: Solar first + Leftover solar 19.44 EUR net (P2 19.33).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 10:42:58 +02:00
Claude dev agent 902524ae5e OPT-11 P3: price runs per battery
checks / unit (pull_request) Successful in 13m45s
infra-pin / fresh (pull_request) Successful in 1s
Cheap and expensive hours as runs of consecutive firm price slots
(priceruns.py); each battery's role per tick from its mode (modetrade.py):
grid charging for Leftover solar / Cheap hours only, never Solar first;
holding for the expensive runs; selling per battery (pack_sell) above the
spread and the floor. The site trade is sized inside the modes (loop bound)
and the peak guard's headroom; a run edge reseeds the loop. Cheap hours only
and selling are enabled on the Batteries screen and in the HA select
(appended). The site Why row no longer says "held back" when the peak limit
pushes power up (F2). Modes off: byte-identical to 7a00f12 on the trade path.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 02:37:44 +02:00
Review AgentandClaude Opus 5.5 e6096d3e17 Merge release/1.0 (7337b79, OPT-11 P2) into safety-79-peak-margin
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 00:23:14 +02:00
adminandClaude Opus 5.5 c664e38ef4 OPT-11 P2 review: refusals stay counted, removals survive a start with no broker
- A refusal past the log-once set or the 32 cap is counted in the log at
  1, 10, 100 and so on, so a repeated attack stays visible.
- The logged topic is printable only (no forged log lines).
- mode_announcement(): the start-up store logic, now tested with a real
  Store. A removed config topic stays stored, so a start with no broker
  cannot forget it (rename case tested).
- A test ties each HA mode option to the page's English name.
- packmode.enabled() is tested for "true", 1 and "false".
- Retained-command text, DOCS and DECISIONS updated to match.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 23:58:34 +02:00
adminandClaude Opus 5.5 b310282729 OPT-11 P2: HA entities for battery modes
checks / unit (pull_request) Successful in 11m12s
infra-pin / fresh (pull_request) Successful in 2s
Each battery gets an MQTT-discovered Mode select and Use switch, only while
battery_modes_enabled is true. Commands go through handle_action(), the
/action path; refusals are logged once. Retained commands are never applied.
Turning modes off removes exactly the configs announced (kept in the store).
With modes off the announcement is byte-identical to ed739d4.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 23:12:04 +02:00
glenn schrooyenandClaude Opus 5.5 7c4c8f5c66 SAFETY-79: peak guard keeps a margin below the limit
checks / unit (pull_request) Failing after 11m34s
infra-pin / fresh (pull_request) Successful in 1s
New option peak_margin_w (default 50 W, 0-500 W). The peak guard, the
forecast checks and the maintenance charge sizing aim at
peak_cap_w - peak_margin_w; the month peak, the bill, headroom, warnings
and every notice keep the real cap. Owner decision 2026-09-28.

peak_margin_w 0 is byte-identical to ed739d4 (tools/safety79_identity.py,
test_peak_margin.py part 1). validate.py rule 12 refuses a value outside
0-500, not whole, or not below the peak limit.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01UBtqPrG1mDLXzTEBnhEkkV
2026-09-28 23:09:39 +02:00
glenn schrooyenandClaude Opus 5.5 ffc9a4d721 OPT-11 P1 review: a mode never beats the peak floor; SAFETY-03 kept at the rail
checks / unit (pull_request) Successful in 11m4s
infra-pin / fresh (pull_request) Successful in 2s
- arbiter: a mode now gives way only as far as a site limit above P_MODE
  needs (_unit_modes at N>1, _site_mode at N=1). Before, the modes were
  released only when the peak floor bound S, so a trade won above the floor
  kept them and placed less than the floor (an Off battery at N=1 went to 0 W
  under a 2000 W floor), and a capped grid charge released an Off battery.
  While released, held batteries weigh 0 and carry only the shortfall.
- control: a side of the loop bound that reaches the rail is left to the
  rail, so SAFETY-03's i_clamped still fires with every battery on.
- opt11_identity: add maintenance scenarios and a 6000-case arbiter digest
  (peak floor, trades, maintenance, refusals); a5dddad digests pinned.
- tests: test_arbiter part 11, test_control (g), test_modes (0/1 refused,
  loop bound counts live units only). DOCS and DECISIONS say the new rule.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01UBtqPrG1mDLXzTEBnhEkkV
2026-09-28 19:41:36 +02:00
Claude dev agent d69fd8fbfd OPT-11 P1: per-battery mode limits, on/off, solar order
checks / unit (pull_request) Successful in 10m59s
infra-pin / fresh (pull_request) Successful in 1s
A battery's mode is a soft unit limit (source `mode`, P_MODE 35) kept
apart from the hard limits in pre_resolve(). The allocator applies it
only while the site target is decided at or below 35 (new
Resolution.deciding_priority), so the peak floor releases it and a mode
`hi` never meets the site `lo`. At N=1 resolve() applies the same rule
to the site target after stage 2. A mode range without 0 W is dropped
as a software fault, so REFUSE_SIGN stays unreachable from a mode.

compute() gets the loop bound (sum over live units of hard limits with
modes applied), so the loop never asks for watts no battery may give
and the saturation freeze never parks on them. While charging, Leftover
solar weighs 0 so Solar first fills first. Store keys pack_use and
pack_mode per battery, set by two new /action values; Off stops and
skips maintenance with a log line. Minimal Batteries cards (EN/NL).

Off by default (battery_modes_enabled); off, commands are byte-identical
to a5dddad at N=1 and N=2 (test_modes.py part 1).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 18:51:29 +02:00
Claude dev agent 667b8e9145 UX-13 P5: Dutch text, STYLE check, DOCS screenshots, period editor
checks / unit (pull_request) Successful in 10m45s
infra-pin / fresh (pull_request) Successful in 1s
- app/ui_text/nl.json and app/uitext.py: every page word in Dutch, English
  fallback per key; the page picks by browser language. Home's sentences
  move into ui_text `home_words`, so /status?lang=nl builds them in Dutch.
- test_ui_text.py: EN/NL key and placeholder parity, STYLE limits, jargon
  lists for both languages, no inline details, untranslated Dutch caught.
  Shared rules moved unchanged to tools/style_rules.py.
- tools/ux13_screenshots.sh/.py: DOCS screenshots from the demo fixtures in
  headless Chromium; docs/img/ux13/. Battery modes (P3): no screenshot.
- "Other time windows": a list editor (ui.periods) that builds
  static_profile and names bad times, empty prices, overlaps and gaps.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 16:33:32 +02:00
adminandClaude Opus 5.5 159d7461d8 UX-15: setup-only mode, and the wizard fixes F1, F2, meter, step 1
A new install names no inverter. When that is the startup gate's only
refusal, the add-on now serves the setup wizard in setup-only mode instead
of exiting 78. It builds no controller, MQTT client or meter task, its
HomeAssistant is read-only (every service call refuses before sending),
Controller refuses a read-only HomeAssistant, and /action answers 409.
Any other refusal still exits 78. DECISIONS/UX-15-setup-only-mode.md.

Wizard fixes from the UX-13 P4 test:
- F1: /config/validate converts what it can, so a conversion error blocks
  its own step and the live checks still run; save 422 carries steps.
- F2: saves send the model the page opened (base); only keys this page
  changed are written onto the blob stored now.
- A meter entity missing from Home Assistant is red on the last step.
- Step 1 says the reading went down after a skip that followed a fall.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 08:48:21 +02:00
glenn schrooyenandClaude Opus 5.5 06aa09e28c SAFETY-73 review: a refusal needs 22 s of evidence, and the cut-out warning is for giving only
infra-pin / fresh (pull_request) Successful in 1s
checks / unit (pull_request) Successful in 10m11s
- REFUSED_SPAN_S: the 12 cycles of evidence must also span (SETTLE_CYCLES-1) *
  LOOP_TICK_S = 22 s. At a 1 s meter, lagged healthy readings refused both
  units 10-16 times an hour after load steps (site held 0 W). 2 s and slower
  ticks are unchanged.
- REFUSES_ABOVE_CUT_OUT only for a refusal to give power: a full battery that
  stops taking charge is always above its cut-out level.
- test_delivery: its wedged fixture (0.2 s cycles) no longer reaches a refusal;
  the release/1.0 checks are restored and a span check added.
- test_refusal_units: lagged-reading and full-battery plants, two new checks,
  U14/U15 in the mutation table. Stale "> 500 W" wording fixed. DOCS/DECISIONS.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 02:16:24 +02:00
glenn schrooyenandClaude Opus 5.5 1a9c7523c9 Merge release/1.0 (a36dca6) into SAFETY-73-per-unit-refusal
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 01:41:54 +02:00
Claude f8d63cc614 UX-13 P1: page shell and Home screen on a structured /status
checks / unit (pull_request) Successful in 9m37s
infra-pin / fresh (pull_request) Successful in 2s
- app/static/{index.html,app.css,app.js}: tabs (Home, Batteries, Settings,
  Setup), hash routes, phone bottom tabs, light/dark. Served inlined at "/";
  the route list is unchanged, and every URL is relative.
- app/homeview.py: /status gains state, now, batteries, plan, attention,
  month_peak and control beside the old fields. The plan is what the add-on
  does today: the arbitrage verdict (the same plan.arbitrage() call as the
  cycle), the monthly cycle, the peak limit, "follows the house".
- The Home plan chart has hover, tap and keyboard-focus tooltips: price bar =
  hour and price; block = what, when, why, kWh and EUR.
- Region preset and year: in config/model (for P2) and on the Home price line.
- test_home.py; test_messages part 8 scans every Home sentence; STYLE plan line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
2026-09-28 00:45:01 +02:00
glenn schrooyenandClaude Opus 5.5 016ed5a5a3 SAFETY-73: a battery that refuses, per inverter, with two or more
checks / unit (pull_request) Successful in 10m1s
infra-pin / fresh (pull_request) Successful in 1s
SAFETY-52's hold applied per unit at N>1 (owner, 2026-09-27, option R).
A unit that gives < 100 W for 12 cycles in one direction while asked
> 200 W, or trips its stale-reading gate on a ~0 W reading, gets a
P_SAFETY `refused` unit limit closing that direction, so the allocator
hands its share to the others within their own limits. Probe: a +-200 W
pin every 15 min, one unit at a time, only while the site asks 200 W that
way. All units refusing: the site law holds 0 W. Exits reseed the site
target from the wire. INFO plus one WARNING (REFUSES_ABOVE_CUT_OUT) above
the configured cut-out; SAFETY-42/43 no longer report a refusing unit.
N=1 unchanged.

test_refusal_units.py: cases a/b/c on flat and jitter registers against
the old behaviour, probes, recovery, exits; mutations U1-U13 all red.
TEST-19 no-fault campaign: 0 engagements in 5280 runs.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 00:13:26 +02:00
adminandClaude Opus 5.5 3c0f2b9669 SAFETY-52 review: a refusal is under 100 W, and any delivery ends it
checks / unit (pull_request) Successful in 9m22s
infra-pin / fresh (pull_request) Successful in 1s
- Engage (and seed from a stale stop) below REFUSED_BELOW_W, the probe's
  own 100 W answer, not below saturation_w: a battery derated to 100-499 W
  was held at 0 W ~93 % of the time.
- A reading of 100 W or more in the held direction ends the refusal, probe
  or not: at a 1 s meter SETTLE_CYCLES is 12 s, shorter than a healthy
  reading's lag, and that held a healthy step at 0 W until the next probe.
- test_refusal part 5b and a seed test; DOCS states the N>1 limit; the
  DECISIONS record carries the traced cause of the replay's extra trips.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 18:11:42 +02:00
glenn schrooyenandClaude Opus 5.5 1f97c7652f SAFETY-52: a battery that refuses is asked for 0 W, with a 200 W probe every 15 min
infra-pin / fresh (pull_request) Successful in 1s
checks / unit (pull_request) Failing after 9m32s
At the BMS cut-out the saturation freeze held the last request for hours
(+5000 W for 11.87 h on 09-06, +1940 W for 3 h 55 m on 09-19) until the grid
error changed sign. compute() now carries a refused direction: after
SETTLE_CYCLES of a ~0 W reading against a larger ask it holds that direction
at 0 W, probes 200 W (below the gate's 250 W) every 15 minutes, and lets go
on charge, an answered probe, stop/start or another writer. A stale-reading
trip on a frozen ~0 W reading seeds the same hold, which ends SAFETY-59's
~70 s cycle. One inverter only; no SoC in the loop (SAFETY-25 Option A).

test_refusal.py drives the real Controller and gate; tools/replay_refusal.py
replays the 16-day capture. test_clamp.py and test_delivery.py re-baselined
where they asserted the old hold. DECISIONS/SAFETY-52 has the record and what
SAFETY-58/59 must take into account.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 16:43:27 +02:00
adminandClaude Opus 5.5 3c298af3d8 UX-11 review: restored stops log their figures to events, the quiet-meter WARNING is rate-limited
checks / unit (pull_request) Successful in 9m7s
infra-pin / fresh (pull_request) Successful in 1s
- After a restart, each restored stop (direction per inverter and site,
  delivery, circulation) also writes its saved reason to the action log.
  log_level defaults to info and events starts empty, so the DEBUG
  evidence alone left the figures only in state.json.
- A flapping meter (ha_signed under a flat load, 42-97 s between changes)
  logs at most one WARNING/INFO pair per 10 minutes, with the episodes in
  between at DEBUG.
- LONG_LINE_OK refuses any key whose text is a safety reason.
- test_watchdog keeps the byte pin beside the meaning pin, since the text
  did not change.
- DOCS says the DEBUG line needs log_level debug.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 14:21:05 +02:00
glenn schrooyenandClaude Opus 5.5 c628099e69 UX-11: the meter WARNING names the limit only, as 'over 30 seconds'
checks / unit (pull_request) Successful in 9m4s
infra-pin / fresh (pull_request) Successful in 2s
TEST-23 showed 'No meter reading for 30 seconds, over the limit of 30
seconds': the age is 30.4 s, which rounds to the limit. The limit alone is
always true at the moment the line is logged.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
2026-09-27 13:49:17 +02:00
glenn schrooyenandClaude Opus 5.5 29837dfaa7 UX-11: safety log lines give one plain sentence and the code, the figures go to DEBUG
checks / unit (pull_request) Successful in 9m3s
infra-pin / fresh (pull_request) Successful in 2s
- Every WARNING/ERROR line that reported a safety reason (direction, delivery,
  stuck meter, stale reading, peak guard, circulation, over-rating) now ends in
  the reason's code (messages.reason_code()). The reason itself, figures and
  limits included, is on a DEBUG line right after it and in the action log.
- The reasons and state.json are unchanged, so an old state file loads and
  shows the same way: every saved reason opens with its code.
- test_messages part 6 checks every WARNING+ line at 25 words as logged; nine
  non-safety families are listed with a reason and capped. The byte pin in
  test_watchdog now pins the meaning, in order.
- The meter logs one WARNING per quiet episode, and INFO when back, so the red
  row's "the add-on log shows why" holds. The Why line past the hold names
  the missing reading. Action log: "25 engagements", "Shadow mode off: ...".

No trigger, latch, threshold, log level, notification id, cadence, row colour
or banner order changed.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
2026-09-27 13:34:30 +02:00
adminandClaude Opus 5.5 e0b578756f UX-10 review: the line as logged gets the red-alarm shape, clamp lines at 30 words, plain HA 400
checks / unit (pull_request) Successful in 9m3s
infra-pin / fresh (pull_request) Successful in 2s
Part 6 checked the quoted reason alone, so title + reason + tails logged
as 4+ sentences. It now also checks the whole line (at most 3 sentences,
none over 30 words); 25 lines failed and are rewritten (one-sentence
wrappers, two-sentence circulation and peak reasons, STALE_READING's
fixed limits on a DEBUG line). The clamp lines for one inverter are
pinned at 30 words with OUTPUT_CLAMP and the numbers kept. Home
Assistant's bare '400: Bad Request' while it loads becomes one plain
line; still WARNING, throttled, a failed write.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 12:08:38 +02:00
glenn schrooyenandClaude Opus 5.5 23a3a3f5b5 UX-10: the last plain-language leftovers: log lines, two table rows, 'Why: Other', red at 0 s
checks / unit (pull_request) Successful in 9m3s
infra-pin / fresh (pull_request) Successful in 2s
- test_messages.py part 6: every dynamic part of a WARNING+ line is classified
  as data or as a built text, and every built text is produced by the real
  code and checked. This is the gap the 2d scan had: it counted `%s` as one
  word, so reasons built by loop_clamp_note() and friends were never seen.
- Quoted reasons rewritten to STYLE.md (red-alarm shape, codes kept):
  OUTPUT_CLAMP, METER_FROZEN, CIRCULATING_POWER, STALE_READING, the peak
  guard (codes now PEAK_GUARD*), the migration report, price feed, price
  history and gate reasons. Plurals via messages.times()/count().
- Top table: Price history "96 prices over 24 hours for 26 Sep", Tariff
  "one every 15 minutes or every hour", "not final yet" dropped.
- Levels and noise: per-cycle shadow line DEBUG, shadow on/off INFO,
  aiohttp access log only at log level debug, settings warnings once per
  start, one plain line per Home Assistant outage (hass.Outage).
- INFO jargon and error texts: no "§8.3", ISO times, "banked", "keys ARE",
  "NOT_OBSERVED", "did NOT land", "AND".
- Display bugs: WHY_WINNER covers every winner and safety reason
  (main.why_key(), part 7 finds them in the code); the meter row is amber
  "waiting for the first reading" inside its limit after a start; the
  missing-reading age is counted when the page asks.
- STYLE.md and DECISIONS/UX-08-short-notifications.md (UX-10 section).

No change to safety behaviour, alarm levels, notification ids, triggers,
cadence or the banner cascade. One row colour changes (meter at start),
justified in DECISIONS.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 10:58:43 +02:00
Claude review 569f16aa91 UX-08 2d review: action log reachable in status JSON, engaged peak row pinned, imported keys expanded
infra-pin / fresh (pull_request) Successful in 1s
checks / unit (pull_request) Successful in 8m54s
- status_payload() also returns the action log as `events`. The page
  does not render it. Some entries (a dropped inverter's reason, the peak
  guard's projection, unplaced watts) are written nowhere else, and DOCS
  still points installers at the action log.
- test_peakguard pins the engaged row's ordered pair (the battery's share,
  then the limit).
- test_messages expands setting keys named by constants imported from
  another app module, so the shown-text 30-word scan counts them.
- p1.py: 'A meter message could not be read'. DOCS glossary: control
  board in plain words, with the hardware in an installer note.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 08:29:14 +02:00
adminandClaude Opus 5.5 6a95447248 UX-08 2d: plain log lines, the rest of the status page, and DOCS
infra-pin / fresh (pull_request) Successful in 1s
checks / unit (pull_request) Successful in 8m55s
Every WARNING and ERROR line is one plain line of at most 25 words, with
no card ids, capitals or semicolons; the reasoning of the ten longest is
on a DEBUG line. The ux08 allowlist is empty and its cap is 0 (43 -> 0).

The status page: the month-peak and peak-guard rows, the stale-reading
row, the top table (Why, Tariff, Arbitrage, Shadow mode, labels), the
Stopped banner and the line under the buttons, which now shows the plain
hint of each event instead of the raw action log. The Supervisor question
at start logs one line with a real reason.

Refusals are counted as shown (labels expanded, long cases driven), seven
were shortened, the card and parse errors lost their internals, a blank
value reads "empty", and the panel no longer files inverters.max_w under
the flat max_w. Option names lose "(JSON)", the NL texts are checked too.

DOCS gets a glossary (control board, isolator, Developer Tools) and card
ids move from headings to a "For installers" line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
2026-09-27 08:01:16 +02:00
adminandClaude Opus 5.5 63dee6db1e UX-09 review: short start-up timeout, latch rows pinned in shadow, plainer rows
checks / unit (pull_request) Successful in 8m50s
infra-pin / fresh (pull_request) Successful in 1s
The Supervisor questions for the Details link are asked together with a
3 s budget instead of one after the other at 10 s each, so a hung
Supervisor cannot hold control start for 20 s. In shadow mode the
circulating and site-direction latches are pinned to keep their own red
row that says how they clear. Plainer inverter and battery wording.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 04:45:06 +02:00
adminandClaude Opus 5.5 00e3ee9de8 UX-09: Details link for current HA, "would" in shadow mode, plain terms
infra-pin / fresh (pull_request) Successful in 2s
checks / unit (pull_request) Successful in 8m50s
- Details link: /config/app/<slug>/documentation on HA 2026.2+ (the old
  /hassio/addon path is a 404 from 2026.5), /hassio/addon on 2026.1 and
  older. Slug from GET /addons/self/info, version from GET /info, hostname
  as fallback.
- Shadow mode: the over-rating alarm and row say what would have been sent,
  the peak alarm no longer says the battery is giving all it can.
- "controller" -> "the add-on" / "control". Settings named by their labels;
  four labels changed to match (Peak reserve, Battery level entity, Solar
  production ..., Reversed-sign solar entities).
- Shadow banner and inverter link notes moved to messages.py and checked.
- DOCS Notifications and Status page rewritten for home owners, with a
  "For installers" part each. Allowlist 168 -> 167.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
2026-09-27 04:10:39 +02:00
glenn schrooyenandClaude Opus 5.5 571b884315 UX-08 phase 2b review: keep over-rating evidence, pin latch clearing, plainer rows
checks / unit (pull_request) Successful in 8m48s
infra-pin / fresh (pull_request) Successful in 1s
- During a bound episode an earlier over-rating count stays on the page (amber,
  under its own title); test_clamp pins it.
- test_messages pins that every latch row says how it clears.
- pv_entities description no longer claims the page names the entity (en, nl);
  allowlist hash updated for that option-desc line.
- Plainer texts: multi-inverter direction banner, "fine now" after an episode,
  and the e-stop, peak-forecast and peak-guard-waiting rows move to messages.py.
- TEL-12 DECISIONS points to UX-08 item 3 for the retired row rule.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 03:10:25 +02:00
adminandClaude Opus 5.5 d017fc67bf UX-08 phase 2b: short, plain status rows and page banners
checks / unit (pull_request) Successful in 8m47s
infra-pin / fresh (pull_request) Failing after 1s
Every Commissioning row and every page banner is now worded in
app/messages.py (row_*, banner_*): one sentence of at most 15 words, a red
row up to three sentences so a latch still says how it clears, banners at
most 12 words. No row names a Home Assistant entity: sensors by their
setting, solar sources by their place in the list. Reason codes and limits
stay on the log line and event list; rows keep the numbers a reader acts on.

UX-07 item 1: ClampWatchdog counts over-rating and integrator-bound
engagements separately, and after an episode each count shows under its own
alarm's title instead of both under "output clamp".

No row colour, visibility or banner order changed. Rows carry an "id" so the
tests pin meaning rather than wording. The row and banner kinds leave the
allowlist (200 -> 168, cap equal). DOCS.md gains "Status page"; choices are in
DECISIONS/UX-08-short-notifications.md.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
2026-09-27 02:12:10 +02:00
adminandClaude Opus 5.5 7b65a3e69a UX-08 review: tighter notification texts, and two meaning fixes
infra-pin / fresh (pull_request) Successful in 1s
checks / unit (pull_request) Successful in 8m48s
- not delivering: the body said control keeps running and then "start
  control"; clearing it takes stop then start, and it now says so.
- peak reserve: the "reserve not set" branch is really soc_floor None,
  i.e. an inverter's cut-out level missing; it now names that. The title
  is true on all three branches ("Battery stopped limiting the peak").
- no semicolon run-ons in bodies (STYLE.md + test); loop-bound, circulating,
  meter-frozen and multi-unit over-rating bodies rewritten to match.
- allowlist cap is now exact, so a shrink cannot leave room to regrow.
- DOCS names the settings behind "peak reserve" and "cut-out level";
  DECISIONS no longer states the HA anchor behaviour as fact.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 01:18:55 +02:00