Commit Graph
153 Commits
Author SHA1 Message Date
glenn schrooyenandClaude Opus 5.5 88b9cd470a SAFETY-96: a battery the loop cannot move does not freeze it
checks / unit (pull_request) Successful in 31m44s
infra-pin / fresh (pull_request) Successful in 2s
At N>=2 a battery out of the split (stale link), with refused writes, or
settling after a step the loop did not make (a charge end, a rejoin) now
counts in the freeze test at its command, not its reading. Its real power
still reaches the loop through the meter. At a drop its share leaves the
loop's start point (the others take over one slew step a cycle); at a
rejoin it enters at its reading. No refusal is learned while a battery's
writes are refused. N=1 and the 46 identity digests are byte-identical.

test_safety78 part 2: the dropped-drain case now rests at B 1510 W (grid at
its -10 W aim) instead of 1500 W; the drop no longer sends B to 2500 W.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-06 04:02:03 +02:00
glenn schrooyenandClaude Opus 5.5 1d28daf8a0 MAINT-10 review: warn when HA did not answer and TZ is UTC; test the 3 s budget
checks / unit (pull_request) Successful in 31m18s
infra-pin / fresh (pull_request) Successful in 1s
HA can take minutes to start (2026-10-05, 502 from the proxy). Then TZ holds,
which the Supervisor sets from HA's zone, so the hour stays right; only a TZ
of UTC there now logs a WARNING asking for a restart. A test pins the 3 s
budget on the zone request (a mutant without it survived).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-05 23:24:02 +02:00
glenn schrooyenandClaude Opus 5.5 0b6b34f563 MAINT-10: every pack at N=2, the next DST days, plainer upgrade note
checks / unit (pull_request) Successful in 31m20s
infra-pin / fresh (pull_request) Successful in 1s
test_maint10.py part 10: at two inverters both packs get the site zone, the
real Controller is identical for 11 UTC and 13 Brussels, and two due packs
across 24/25 Oct 2026 and 27/28 Mar 2027 start at the local hour on
successive days; a pack freed in the repeated hour does not start there.
Part 3 adds 28 Mar 2027. DOCS: an existing install keeps its saved hour, now
read as local time; an hour set to make up for UTC goes back to 19.
DECISIONS: the SAFETY-83 gate is met; section on two inverters.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-05 21:51:15 +02:00
glenn schrooyenandClaude Opus 5.5 08fb1235fc Merge release/1.0 (0.15.0 + SAFETY-90) into maint-10-local-start-hour
Conflicts: main.py's maintenance import (base added CHARGE, HOLD; branch added
site_zone) - both kept. DOCS maintenance table: base's longer drain-rate row
kept, start hour row at 19 / local.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-05 21:51:04 +02:00
Claude (SAFETY-90 review) 8dfe91e1d2 SAFETY-90 review: count the start-up seconds like a gap
While the add-on is down the batteries are at 0 W (it sets 0 W when it
stops; the ESP32 watchdog after 30 s), so the import before its first
reading was the house, not the aim. Those seconds now count at
gap_w(limit, the import seen first), and after a restart the restored
reading's held 30 s is topped up the same way. Status row: "counted as
high use". Tests take the pre-start import as the house (batteries at
0 W) and add restarts of 10/60/150 s with a restored averager.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-05 12:24:33 +02:00
Claude (SAFETY-90 dev) 9d3fbe1be9 SAFETY-90: the peak guard goes on after a P1 meter gap
checks / unit (pull_request) Successful in 31m10s
infra-pin / fresh (pull_request) Successful in 1s
A meter gap past meter_max_age_s left seconds the quarter average never
counted, so the guard was blind for the rest of the quarter (rig case 7b:
3964.8 W against a 3450 W aim). Once readings are back, the missed seconds
now count at the higher of the limit and the import seen just before and
just after the gap with the batteries at 0 W (peakguard.gap_w/fill_gaps);
the gap's first meter_max_age_s is topped up to that too. Seconds before
the add-on's first reading count at the aim, and the page says part of the
period was not measured (EN/NL). The bill record is unchanged; no option.

DECISIONS/SAFETY-90-peak-guard-after-a-gap.md, test_safety90.py.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-05 11:46:58 +02:00
adminandClaude Opus 5.5 6918e154c8 SAFETY-97: "gives nothing" is graded against each battery's idle reading
checks / unit (pull_request) Failing after 29m7s
infra-pin / fresh (pull_request) Failing after 2s
B's power reading shows -95 to -118 W at idle (standby draw), so the
|reading| < 100 W refusal band never held a refusing B: never at N=2,
and since SAFETY-94's shared rule not at N=1 either (review F1).

Each unit now learns its idle reading (app/idle.py): only while control
runs, the unit is not refused/stale/tripped and its command has stayed
within 50 W for 120 s; first value a 120 s mean, then a 30 min follow;
samples beyond 250 W dropped, value clamped to 250 W; saved per unit and
restored. The shared refusal evidence, compute()'s N=1 engage and end,
the unit refusal ends, the stale-path refusal and SAFETY-42's "parked"
test are centred on it. Until learned it is 0 W, the rule as it was.

Refusing B caught at N=1 28/28/65 s and N=2 24/24/60 s (1/2/5 s
meters), before never; refusing A unchanged. Healthy B with its offset,
SAFETY-94's scenarios, 96 runs: 0 stale, 0 refused. Live replay: 0.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
2026-10-04 12:21:24 +02:00
adminandClaude Opus 5.5 6759d21ea5 SAFETY-94: a healthy battery that lags or reverses is not flagged as frozen or refusing
checks / unit (pull_request) Successful in 28m10s
infra-pin / fresh (pull_request) Failing after 2s
The stale-reading gate counted its 35 s from the register's last change, so
after a rest the first read after a new command tripped it (SAFETY-58; live
2026-10-03, four trips 1 s after the command). It now counts only the time
the command asked the register to move.

At N=1 the refusal engaged after 12 frozen cycles if the reading was under
100 W at that moment, which a battery reversing through its lag passes at a
1 s meter. The refusal now needs the N>1 evidence at every roster size: under
100 W, one way, for 12 cycles spanning 22 s, restarting when the reading
moves 50 W towards the ask.

DECISIONS/SAFETY-94-lagging-battery.md; test_safety94.py.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-04 00:15:42 +02:00
adminandClaude Opus 5.5 05eb93f139 SAFETY-93: the maintenance charge end hands back smoothly, with no grid charging at a high house
checks / unit (pull_request) Successful in 26m55s
infra-pin / fresh (pull_request) Failing after 1s
At N>=2, when a battery's maintenance charge ended, its watts stayed in the
loop's start point and landed on the other battery (B 0 -> -1600 W in one
cycle, charging from the grid at a 6000 W house). On the cycle a charge
ends, the loop now starts from what the others stood at plus that
battery's new command. N=1 and all identity digests unchanged.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-02 22:38:42 +02:00
adminandClaude Opus 5.5 6872353e2e SAFETY-91: a held battery is drawn only after the others are full
checks / unit (pull_request) Successful in 26m19s
infra-pin / fresh (pull_request) Successful in 1s
At N>=2 a battery at or under its own peak reserve now weighs 0 whenever
the site gives (not only for the peak), a draining battery's pin becomes
a floor at its drain rate so it rises before the held one gives, and a
quarter's edge is graded on the next quarter when its first telegram is
late. SAFETY-25 option A stays: the held battery is still drawn once the
others are full. N=1 unchanged.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-02 14:03:54 +02:00
adminandClaude Opus 5.5 7b723a6cd5 SAFETY-85 review: grade discharge only, over the plant's settle time
checks / unit (pull_request) Successful in 25m47s
infra-pin / fresh (pull_request) Successful in 2s
Rule 2 graded each battery against last cycle's command and graded charges
too. On plantsim's battery (10 s lag) at the 2 s meter it warned at every
drain or charge start and 15 times an hour under the peak guard at N=2; a
charge tapering near full warned 11 times in 50 min (SAFETY-42 section 7).
Now a discharge is graded against the least it stood at over SHORT_CYCLES /
SHORT_SPAN_S. DOCS lists `mode-bound` under Loop reason. test_safety85 part 7:
peak guard with a dead battery, lagging plant, taper; part 3: the bound ends
with maintenance.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-01 20:25:41 +02:00
glenn schrooyenandClaude Opus 5.5 4b81387908 SAFETY-85: no false 'not keeping up' while maintenance or the peak guard sets the battery
checks / unit (pull_request) Successful in 25m35s
infra-pin / fresh (pull_request) Successful in 2s
The loop's integrator bound counts only on a cycle the loop decided. A battery
another owner set (maintenance, the peak guard, a safety limit) alarms only
when it gives more than saturation_w less than told for saturation_cycles
cycles. At N>=2 the loop is bounded while maintenance holds a battery, so it
does not wind and control comes back one slew step a cycle. The status row
counts episodes, not cycles. Digests re-pinned where behaviour changed on
purpose; DECISIONS/SAFETY-85-no-false-not-keeping-up.md has the list.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
2026-10-01 19:05:27 +02:00
Claude b4d25dd485 SAFETY-87 review: DOCS, the drain rate may rise for the peak at N>=2
infra-pin / fresh (pull_request) Successful in 1s
checks / unit (pull_request) Successful in 24m53s
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
2026-10-01 11:08:42 +02:00
Claude d0db5b8c39 SAFETY-87: peak guard uses every battery that can still give
checks / unit (pull_request) Successful in 25m45s
infra-pin / fresh (pull_request) Successful in 1s
At N>=2 a battery at or under its own peak reserve is held: it gives
nothing for the peak (weight 0 while the site gives) and the guard's need
is placed on the live, non-refusing batteries above theirs. The guard is
floor-limited, and alarms, only when those cannot hold the limit at full
power for ALARM_HOLD_S. The peak alarms no longer read "Not ready" or hold
the Home page at 0 W, because control keeps running. N=1 is byte-identical.

DECISIONS/SAFETY-87-guard-uses-able-batteries.md.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
2026-10-01 09:29:30 +02:00
glenn schrooyenandClaude Opus 5.5 ba31e7c8b1 SAFETY-86: peak guard outranks the maintenance hold
checks / unit (pull_request) Successful in 24m17s
infra-pin / fresh (pull_request) Successful in 1s
During a HOLD the holding battery gives what keeps the quarter at the peak
aim. N=1: the peak floor is refiled at P_MAINTENANCE, as for a drain
(SAFETY-83). N>=2: the hold's pin is raised to the floor minus what the
other live batteries may place, so they give first. A site stop still
decides alone. The hold ends on its clock even if the level dipped.
Below the aim nothing changes (rows identical).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-01 00:56:34 +02:00
glenn schrooyenandClaude Opus 5.5 43a52e7f60 SAFETY-84: maintenance charge at N=2 no longer stalls
checks / unit (pull_request) Successful in 23m57s
infra-pin / fresh (pull_request) Successful in 2s
At N>=2 a cheap-window maintenance charge files a site `hi` (`charge`,
P_MAINT_SHAPE) equal to what the charging pack's own `hi` places, so the
other pack never has to give against it. The charge is sized to the
quarter's headroom under the peak aim so it yields to the peak guard, and
to 0 W under a site safety stop. N=1 byte-identical (safety84_identity).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-30 19:47:15 +02:00
glenn schrooyenandClaude Opus 5.5 79b94024cb Merge release/1.0 (OPT-11 P4, #156) into safety-83-peak-over-drain
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-30 13:35:28 +02:00
goodwe-agent 02c0a3dd7b MAINT-10: maintenance start hour in local time, default 19:00
The start hour was compared with the UTC hour, so the shipped 10 started at
12:00 in a Belgian summer. It is now read in Home Assistant's time zone
(fallback: the container's TZ, then UTC, one log line says which), and the
default moves to 19. DST: a missing hour starts at the first hour after the
jump; a repeated hour starts only in its first pass. Stored options are not
rewritten: a saved 10 now means 10:00 local (DOCS, CHANGELOG).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 22:52:05 +02:00
adminandClaude Opus 5.5 d77f1b1fdf SAFETY-83: peak guard outranks the maintenance drain at N=1
checks / unit (pull_request) Successful in 16m54s
infra-pin / fresh (pull_request) Successful in 1s
At N=1 the drain is the site SET at P_MAINTENANCE (60), so the peak floor
(P_PEAK, 50) was not applied and the house imported what the drain left.
Where the floor asks for more than the drain rate, main.py now refiles the
peak claim at P_MAINTENANCE, so it wins; safety SETs still park everything.
Nothing else changes: safety78_identity --diff against 35cdffe changes only
cycles where the guard wanted more than the drain; N=2 is byte-identical.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 22:40:14 +02:00
glenn schrooyenandClaude Opus 5.5 b171ada894 Merge release/1.0 (SAFETY-78, #154) into opt11-p4-solar-forecast
checks / unit (pull_request) Successful in 23m54s
infra-pin / fresh (pull_request) Successful in 1s
Conflicts: modetrade.decide() takes both the day plan (targets) and
SAFETY-78's draining flag; the Why line keeps SAFETY-78's other_cycle
ahead of the plan's word (test added).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 22:37:09 +02:00
glenn schrooyenandClaude Opus 5.5 0b96e3191c OPT-11 P4 review: records and text
checks / unit (pull_request) Failing after 4s
infra-pin / fresh (pull_request) Successful in 1s
- DECISIONS: the Cheap hours change and why; the no-sun replay (the gain is
  Leftover solar buying the evening's shortfall; the forecast added 0.14
  EUR); the reconstruction bias stated plainly.
- DOCS: Cheap hours ignores the forecast; a reading from before midnight
  is stale.
- The forecast line: "Solar still to come today: ..." (it is what is
  left, and it stays within the 12-word limit).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 22:29:00 +02:00
glenn schrooyenandClaude Opus 5.5 a692560960 Merge release/1.0 (SAFETY-81, #155) into opt11-p4-solar-forecast
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 22:08:52 +02:00
glenn schrooyenandClaude Opus 5.5 fbd884797d OPT-11 P4 review: Cheap hours ignores the plan; midnight-stale forecast; stricter ids
- Cheap hours only fills to the ceiling with or without a forecast, as the
  design (section 1) says. Skipping the sun's share cost 0.31 EUR on real
  2026 prices (29.72 against P3's 29.41) and saved nothing on the P3 set.
- A forecast reading from before local midnight is stale: until the
  integration refreshes, "left today" is still yesterday's 0 and
  "tomorrow" is really today.
- Forecast entity ids must be sensor.[a-z0-9_]+ (they go into the
  /api/states/<id> path).
- House profile: a stored day that is not a date, or is after today, is
  dropped instead of kept forever.
- Text: the forecast line says "for the rest of today"; the learning line
  no longer promises "tomorrow" (a plan needs one full day).
- Tests for four surviving review mutants (hour sample floor, the dear run
  after the cheap run, share by room, daytime use) and the fixes above.
- Replay tool: `--fc zero` (a forecast of no sun).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 22:08:47 +02:00
goodwe-review 516bc8b4ec Merge release/1.0 into safety-78-drain-at-two
checks / unit (pull_request) Successful in 18m49s
infra-pin / fresh (pull_request) Successful in 2s
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 21:53:47 +02:00
adminandClaude Opus 5.5 f967073cfe SAFETY-81 review: 10 s hold, ERROR line per episode, more scenarios
checks / unit (pull_request) Successful in 20m31s
infra-pin / fresh (pull_request) Successful in 2s
- The alarm must hold for peakguard.ALARM_HOLD_S (10 s) on the projection's
  clock. A load that tops cap + battery for ~5 s every 30 s alarmed at every
  quarter start while the quarter landed under the aim (sine4500_fast).
- A cycle with no battery reading leaves the hold alone.
- Notified once per quarter, but the ERROR line is written per episode.
- New sim scenarios (sine4500_fast, twice7000, step6500_gap) with 5a4cdc2
  digests; control still byte-identical. Unit checks for export and the
  hold across a missing reading. test_peakguard's saturated fixture moves
  the hold start back instead of waiting it out.
- DECISIONS and DOCS updated: costs of the hold, tolerance reasoning, the
  double count in control left to a follow-up.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 20:58:37 +02:00
goodwe-agent 6eb67c0f9c SAFETY-81: no false 'Load too high' alarms
checks / unit (pull_request) Successful in 16m11s
infra-pin / fresh (pull_request) Successful in 1s
The alarm now also needs peakguard.load_too_high(): with the battery at
full power, the quarter still ends more than 10 W over the real limit.
The battery reading is the lower of this cycle's and the last, so a meter
sample from before the battery's last increase is not counted twice.
At most one alarm per quarter. Control outputs unchanged.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 19:55:38 +02:00
Claude 5d27f8496f SAFETY-78: maintenance drain at N=2 no longer stalls
checks / unit (pull_request) Failing after 17m13s
infra-pin / fresh (pull_request) Successful in 2s
At two inverters the drain pins its pack and the site target is split
around the pin. Below the pin the other pack had to charge, the allocator
refused the opposite directions, and the site sat at 0 W with an ARBITER
line every cycle (house below or above the drain rate, or a grid charge).

main.py now files a site limit `drain` (lo = what the pin places, at
P_MAINTENANCE) at N>=2 while a pack drains, so the other pack only adds
power in the same direction. A drain that cannot give power waits with
one log line. With battery modes on, no grid charge while a pack drains,
and the other battery's card says why. N=1 is byte-identical.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 19:52:51 +02:00
Claude eb10537aee OPT-11 P4: solar forecast and day plan
A Home Assistant solar forecast (Forecast.Solar, Solcast or Open-Meteo
shapes) and the add-on's own hourly house use decide, before each cheap
run, whether the sun will fill each battery before the expensive hours.
Leftover solar then buys from the grid only the shortfall; Cheap hours only
skips the part the sun covers; Solar first never grid-charges. No, stale or
failed forecast: P3 option A exactly (12 digests pinned from 5a4cdc2).

Replay (16 recorded days, forecast errors from Elia's day-ahead BE solar):
year-earlier prices P4 19.15 vs P2 19.33 / option A 19.44 / old trade 18.14;
real 2026 prices P4 29.19 vs 32.26 / 32.01 / 31.40 EUR net.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 19:29:32 +02:00
Claude dev agent 6dab4ec16b OPT-11 P3, owner option A: selling off, Leftover solar takes solar only
checks / unit (pull_request) Successful in 15m12s
infra-pin / fresh (pull_request) Successful in 1s
Owner decision 2026-09-29. Selling is off until it can be judged on the price
the grid pays: packmode.SELLING_ENABLED = False makes read() answer
sell=False whatever the store holds, pack_sell is refused ("Selling is off
for now."), and the page has no selling switch; the sell code stays. Until
the P4 forecast, only Cheap hours only charges from the grid
(packmode.GRID_CHARGE_MODES); Leftover solar holds and gives in the
expensive runs. Help, Today and plan lines, DOCS and DECISIONS follow.
Replay, 16 days: Solar first + Leftover solar 19.44 EUR net (P2 19.33).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 10:42:58 +02:00
glenn schrooyenandClaude Opus 5.5 b014fd2e16 OPT-11 P3 review: sale shows no money, honest sell text, tests for four surviving mutants
checks / unit (pull_request) Successful in 14m5s
infra-pin / fresh (pull_request) Successful in 1s
- A sale block on the plan no longer says "Worth up to" at the import
  price: a sale earns the lower injection price.
- The selling switch help (EN/NL) and DOCS say the grid pays less than
  power costs; DECISIONS records why P3 loses on the replay.
- test_modes_p3 part 11: modes on ignore the site trade switch (R13), a
  battery in maintenance takes no part (R10), a headroom stop latches for
  the period (R8). All three mutants survived before and are red now.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 03:51:15 +02:00
Claude dev agent 902524ae5e OPT-11 P3: price runs per battery
checks / unit (pull_request) Successful in 13m45s
infra-pin / fresh (pull_request) Successful in 1s
Cheap and expensive hours as runs of consecutive firm price slots
(priceruns.py); each battery's role per tick from its mode (modetrade.py):
grid charging for Leftover solar / Cheap hours only, never Solar first;
holding for the expensive runs; selling per battery (pack_sell) above the
spread and the floor. The site trade is sized inside the modes (loop bound)
and the peak guard's headroom; a run edge reseeds the loop. Cheap hours only
and selling are enabled on the Batteries screen and in the HA select
(appended). The site Why row no longer says "held back" when the peak limit
pushes power up (F2). Modes off: byte-identical to 7a00f12 on the trade path.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 02:37:44 +02:00
Review AgentandClaude Opus 5.5 ce0aea30b6 SAFETY-79 review: margin under a banked month peak too; identity harness reaches headroom and maintenance
checks / unit (pull_request) Successful in 11m50s
infra-pin / fresh (pull_request) Successful in 1s
- quarter_target_w() is now the margin under quarter_ceiling_w(): a peak
  banked between cap - margin and the cap was aimed at exactly, so one
  overshoot crossed the cap; above the cap the same overshoot raised the bill.
- safety79_identity.py hashes charge_headroom_w() and the shaping suspension,
  and adds n1_maint/n2_maint (cheap window, forecast across cap - 50 .. cap).
  Digests re-printed on ed739d4 and pinned; margin 0 still identical.
- test_margin_under_banked_peak; DECISIONS and DOCS updated.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 00:49:16 +02:00
Review AgentandClaude Opus 5.5 e6096d3e17 Merge release/1.0 (7337b79, OPT-11 P2) into safety-79-peak-margin
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 00:23:14 +02:00
glenn schrooyenandClaude Opus 5.5 308adc9277 Merge release/1.0 (7995e4d, UX-13 P3) into opt11-p2-ha-entities
checks / unit (pull_request) Successful in 11m29s
infra-pin / fresh (pull_request) Successful in 2s
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 23:58:39 +02:00
adminandClaude Opus 5.5 c664e38ef4 OPT-11 P2 review: refusals stay counted, removals survive a start with no broker
- A refusal past the log-once set or the 32 cap is counted in the log at
  1, 10, 100 and so on, so a repeated attack stays visible.
- The logged topic is printable only (no forged log lines).
- mode_announcement(): the start-up store logic, now tested with a real
  Store. A removed config topic stays stored, so a start with no broker
  cannot forget it (rename case tested).
- A test ties each HA mode option to the page's English name.
- packmode.enabled() is tested for "true", 1 and "false".
- Retained-command text, DOCS and DECISIONS updated to match.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 23:58:34 +02:00
glenn schrooyen 0951cb227f Merge release/1.0 into safety-79-peak-margin
infra-pin / fresh (pull_request) Successful in 1s
checks / unit (pull_request) Successful in 11m36s
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

# Conflicts:
#	goodwe_controller/app/uilayout.py
2026-09-28 23:56:33 +02:00
goodwe-review-agent a9f7d78527 UX-13 P3 review: truthful peak lines, a clock-proof test, Simple stays default
checks / unit (pull_request) Successful in 11m10s
infra-pin / fresh (pull_request) Successful in 2s
- The peak limit's Why and plan block need a real power request (floor above
  0 W), not a blind or floor-limited guard. An Off battery gets the peak
  block only while it gives power. Why no longer says every battery gives.
- test_batteries_screen pins the fixture clock: unpinned it failed every
  morning. New checks cover the trade and cycle filters, the blind guard and
  an Off battery that A covers alone.
- Settings keeps only a picked view; a link to Installer is not remembered.
- Browser check: badges, unsaved change across views, locked value.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 23:20:33 +02:00
adminandClaude Opus 5.5 b310282729 OPT-11 P2: HA entities for battery modes
checks / unit (pull_request) Successful in 11m12s
infra-pin / fresh (pull_request) Successful in 2s
Each battery gets an MQTT-discovered Mode select and Use switch, only while
battery_modes_enabled is true. Commands go through handle_action(), the
/action path; refusals are logged once. Retained commands are never applied.
Turning modes off removes exactly the configs announced (kept in the store).
With modes off the announcement is byte-identical to ed739d4.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 23:12:04 +02:00
glenn schrooyenandClaude Opus 5.5 7c4c8f5c66 SAFETY-79: peak guard keeps a margin below the limit
checks / unit (pull_request) Failing after 11m34s
infra-pin / fresh (pull_request) Successful in 1s
New option peak_margin_w (default 50 W, 0-500 W). The peak guard, the
forecast checks and the maintenance charge sizing aim at
peak_cap_w - peak_margin_w; the month peak, the bill, headroom, warnings
and every notice keep the real cap. Owner decision 2026-09-28.

peak_margin_w 0 is byte-identical to ed739d4 (tools/safety79_identity.py,
test_peak_margin.py part 1). validate.py rule 12 refuses a value outside
0-500, not whole, or not below the peak limit.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01UBtqPrG1mDLXzTEBnhEkkV
2026-09-28 23:09:39 +02:00
Claude 2d2b6afb07 UX-13 P3: Simple view and Batteries screen
checks / unit (pull_request) Successful in 11m9s
infra-pin / fresh (pull_request) Successful in 2s
- Batteries: one card per battery with On/Off, the mode list (cheap hours
  and selling greyed out until OPT-11 P3), level, and Now / Today / Why
  lines built in homeview.py. Replaces the OPT-11 P1 minimal cards and uses
  the existing pack_use / pack_mode actions and store keys.
- An Off battery the peak limit still needs says so with its figure; no line
  shows 0 W beside moving power (OPT-11 P1 test F2). Today says "Not planned
  yet" until OPT-11 P3/P4.
- Home's plan leaves Off batteries out, except for the peak limit.
- Settings opens on Simple: the layout's simple fields with an applies chip
  and a note, plus the battery switches and modes. Installer is one tap.
- English and Dutch words in app/ui_text; test_batteries_screen.py; browser
  check tools/ux13_browser_check.py (CHECK=1 ux13_screenshots.sh); new and
  changed screenshots only.

No control, allocator, arbiter or command module changed.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01UBtqPrG1mDLXzTEBnhEkkV
2026-09-28 22:39:43 +02:00
glenn schrooyenandClaude Opus 5.5 ffc9a4d721 OPT-11 P1 review: a mode never beats the peak floor; SAFETY-03 kept at the rail
checks / unit (pull_request) Successful in 11m4s
infra-pin / fresh (pull_request) Successful in 2s
- arbiter: a mode now gives way only as far as a site limit above P_MODE
  needs (_unit_modes at N>1, _site_mode at N=1). Before, the modes were
  released only when the peak floor bound S, so a trade won above the floor
  kept them and placed less than the floor (an Off battery at N=1 went to 0 W
  under a 2000 W floor), and a capped grid charge released an Off battery.
  While released, held batteries weigh 0 and carry only the shortfall.
- control: a side of the loop bound that reaches the rail is left to the
  rail, so SAFETY-03's i_clamped still fires with every battery on.
- opt11_identity: add maintenance scenarios and a 6000-case arbiter digest
  (peak floor, trades, maintenance, refusals); a5dddad digests pinned.
- tests: test_arbiter part 11, test_control (g), test_modes (0/1 refused,
  loop bound counts live units only). DOCS and DECISIONS say the new rule.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01UBtqPrG1mDLXzTEBnhEkkV
2026-09-28 19:41:36 +02:00
Claude dev agent d69fd8fbfd OPT-11 P1: per-battery mode limits, on/off, solar order
checks / unit (pull_request) Successful in 10m59s
infra-pin / fresh (pull_request) Successful in 1s
A battery's mode is a soft unit limit (source `mode`, P_MODE 35) kept
apart from the hard limits in pre_resolve(). The allocator applies it
only while the site target is decided at or below 35 (new
Resolution.deciding_priority), so the peak floor releases it and a mode
`hi` never meets the site `lo`. At N=1 resolve() applies the same rule
to the site target after stage 2. A mode range without 0 W is dropped
as a software fault, so REFUSE_SIGN stays unreachable from a mode.

compute() gets the loop bound (sum over live units of hard limits with
modes applied), so the loop never asks for watts no battery may give
and the saturation freeze never parks on them. While charging, Leftover
solar weighs 0 so Solar first fills first. Store keys pack_use and
pack_mode per battery, set by two new /action values; Off stops and
skips maintenance with a log line. Minimal Batteries cards (EN/NL).

Off by default (battery_modes_enabled); off, commands are byte-identical
to a5dddad at N=1 and N=2 (test_modes.py part 1).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 18:51:29 +02:00
Claude dev agent 667b8e9145 UX-13 P5: Dutch text, STYLE check, DOCS screenshots, period editor
checks / unit (pull_request) Successful in 10m45s
infra-pin / fresh (pull_request) Successful in 1s
- app/ui_text/nl.json and app/uitext.py: every page word in Dutch, English
  fallback per key; the page picks by browser language. Home's sentences
  move into ui_text `home_words`, so /status?lang=nl builds them in Dutch.
- test_ui_text.py: EN/NL key and placeholder parity, STYLE limits, jargon
  lists for both languages, no inline details, untranslated Dutch caught.
  Shared rules moved unchanged to tools/style_rules.py.
- tools/ux13_screenshots.sh/.py: DOCS screenshots from the demo fixtures in
  headless Chromium; docs/img/ux13/. Battery modes (P3): no screenshot.
- "Other time windows": a list editor (ui.periods) that builds
  static_profile and names bad times, empty prices, overlaps and gaps.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 16:33:32 +02:00
Claude review agent 30cba1e58d UX-15 review: shorter setup banner (PR #147)
The Home banner title was ten words; UX-08 asks for about six.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 15:06:12 +02:00
adminandClaude Opus 5.5 159d7461d8 UX-15: setup-only mode, and the wizard fixes F1, F2, meter, step 1
A new install names no inverter. When that is the startup gate's only
refusal, the add-on now serves the setup wizard in setup-only mode instead
of exiting 78. It builds no controller, MQTT client or meter task, its
HomeAssistant is read-only (every service call refuses before sending),
Controller refuses a read-only HomeAssistant, and /action answers 409.
Any other refusal still exits 78. DECISIONS/UX-15-setup-only-mode.md.

Wizard fixes from the UX-13 P4 test:
- F1: /config/validate converts what it can, so a conversion error blocks
  its own step and the live checks still run; save 422 carries steps.
- F2: saves send the model the page opened (base); only keys this page
  changed are written onto the blob stored now.
- A meter entity missing from Home Assistant is red on the last step.
- Step 1 says the reading went down after a skip that followed a fall.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 08:48:21 +02:00
review-agent 3198f346fd UX-13 P4 review fixes (PR #146, comment 1887)
checks / unit (pull_request) Successful in 10m24s
infra-pin / fresh (pull_request) Successful in 1s
R1: first_start also needs a Store created at this boot (Store.fresh), so
    old never-started sites (both TEST-23 add-ons, one in shadow) stay on Home.
R2: a kettle skip after a fall says on the last step that the reading went down.
R3: the shadow switch goes only on the model the wizard posts, never into V.
R4: Home Assistant not answering is red on the last step.
R5: meter + solar + battery below -300 W flags a reversed battery sensor.
R6: the live checks say what to change and where.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 06:12:09 +02:00
adminandClaude Opus 5.5 be57b87c34 UX-13 P4: the setup wizard for installers
checks / unit (pull_request) Successful in 10m22s
infra-pin / fresh (pull_request) Successful in 1s
The Setup tab draws the Installer view's page model one step at a time,
from each field's `wizard` step in app/uilayout.py: meter (with the kettle
test), inverters and batteries, solar (optional), prices, peak limit
(battery modes: "comes in a later update", OPT-11), check and start.
It reuses P2's controls and saves through /config/validate and
/config/save. No route was added.

- First run: /config/model says `setup_needed` when the stored options name
  no power request entity, or on a new install (no `setup_done` and no
  `auto` in the Store, control not started). The page opens #setup only
  when opened with no route. The wizard's save writes `setup_done`.
- Kettle test: GET ha/entities?entity= reads one entity now, in W. The
  change decides: up keeps meter_invert off, down turns it on; a net or
  import/export meter that goes down blocks the step with what to check.
- Last step: validate.setup_checks() beside the refusals: the meter reads,
  each power request entity exists in HA (bad if not, SAFETY-77), battery
  levels and power with direction, solar sign, prices. Saves with
  shadow_mode on by default, then a confirmed restart naming the 0 W.
- P2 test finding (a): a stale save lists only the keys the other surface
  moved (the blob handed out on open, by fingerprint, against stored now).
- test_setup.py; tools/ux13_wizard_blobs.py makes the 88 blobs the wizard
  can save; all accepted by Supervisor 2026.08.0 AppOptions (offline).
- DECISIONS/UX-13-setup-wizard.md; DOCS "Setup, for a new install".

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
2026-09-28 05:31:18 +02:00
glenn schrooyenandClaude Opus 5.5 06aa09e28c SAFETY-73 review: a refusal needs 22 s of evidence, and the cut-out warning is for giving only
infra-pin / fresh (pull_request) Successful in 1s
checks / unit (pull_request) Successful in 10m11s
- REFUSED_SPAN_S: the 12 cycles of evidence must also span (SETTLE_CYCLES-1) *
  LOOP_TICK_S = 22 s. At a 1 s meter, lagged healthy readings refused both
  units 10-16 times an hour after load steps (site held 0 W). 2 s and slower
  ticks are unchanged.
- REFUSES_ABOVE_CUT_OUT only for a refusal to give power: a full battery that
  stops taking charge is always above its cut-out level.
- test_delivery: its wedged fixture (0.2 s cycles) no longer reaches a refusal;
  the release/1.0 checks are restored and a span check added.
- test_refusal_units: lagged-reading and full-battery plants, two new checks,
  U14/U15 in the mutation table. Stale "> 500 W" wording fixed. DOCS/DECISIONS.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 02:16:24 +02:00
glenn schrooyenandClaude Opus 5.5 016ed5a5a3 SAFETY-73: a battery that refuses, per inverter, with two or more
checks / unit (pull_request) Successful in 10m1s
infra-pin / fresh (pull_request) Successful in 1s
SAFETY-52's hold applied per unit at N>1 (owner, 2026-09-27, option R).
A unit that gives < 100 W for 12 cycles in one direction while asked
> 200 W, or trips its stale-reading gate on a ~0 W reading, gets a
P_SAFETY `refused` unit limit closing that direction, so the allocator
hands its share to the others within their own limits. Probe: a +-200 W
pin every 15 min, one unit at a time, only while the site asks 200 W that
way. All units refusing: the site law holds 0 W. Exits reseed the site
target from the wire. INFO plus one WARNING (REFUSES_ABOVE_CUT_OUT) above
the configured cut-out; SAFETY-42/43 no longer report a refusing unit.
N=1 unchanged.

test_refusal_units.py: cases a/b/c on flat and jitter registers against
the old behaviour, probes, recovery, exits; mutations U1-U13 all red.
TEST-19 no-fault campaign: 0 engagements in 5280 runs.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-28 00:13:26 +02:00
adminandClaude Opus 5.5 3c0f2b9669 SAFETY-52 review: a refusal is under 100 W, and any delivery ends it
checks / unit (pull_request) Successful in 9m22s
infra-pin / fresh (pull_request) Successful in 1s
- Engage (and seed from a stale stop) below REFUSED_BELOW_W, the probe's
  own 100 W answer, not below saturation_w: a battery derated to 100-499 W
  was held at 0 W ~93 % of the time.
- A reading of 100 W or more in the held direction ends the refusal, probe
  or not: at a 1 s meter SETTLE_CYCLES is 12 s, shorter than a healthy
  reading's lag, and that held a healthy step at 0 W until the next probe.
- test_refusal part 5b and a seed test; DOCS states the N>1 limit; the
  DECISIONS record carries the traced cause of the replay's extra trips.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 18:11:42 +02:00