SAFETY-02: a loop can be fresh, tracking and inside its rating and still push the wrong way
The stale-input watchdog asks whether the meter is still talking. The saturation freeze asks whether the inverter can follow. The output clamp asks whether the number is too big. A loop can pass all three while charging the battery out of the grid, because the only thing wrong is the sign. On 2026-08-20 a commercial controller did exactly that four times in one day, for up to 77 minutes at a stretch, reaching a commanded -14 768 W against a ±5000 W inverter. app/watchdog.py compares the emitted setpoint against the authoritative P1 figure and, when they oppose each other with both over 300 W for 180 s continuously, files a failsafe SET claim at P_SAFETY, commands 0 W and latches there until an operator starts control again. Validated against that day rather than against an argument: sim/replay_sign.py in the infra repo drives this module over the committed captures of both 2026-08-20 and the healthy 2026-08-23 and reaches 18 trips on the fault day - every one inside a window NOTES.md §4.7 accounts for - and 0 on the healthy day. The four episodes do share one signature: 0.3 / 0.9 / 10.5 / 0.0 % sign agreement inside them against 92.9 % healthy. Three decisions the ticket could not make: - It is DISARMED whenever the grid-following loop is not what is driving. Sign agreement is a property of a loop that follows the meter, and a maintenance grid charge opposes the meter by design - 2500 W of charge into a house drawing 500 W is +3000 W on the meter against a -2500 W command, for hours. The gate tests the emitted number, not the winning claim's name, because a limit claim can let the loop "win" and still replace its value. - The trip LATCHES. Commanding 0 W removes the command side of the comparison, so the disagreement always clears the moment the trip works. - sign_disagree_w at or above max_w is refused at startup. The arbiter never lets a command exceed max_w, so such a threshold leaves the watchdog incapable of firing while the status page still reports it armed. What it does not catch, said out loud: an inverter that ACTS opposite to its command moves the meter further the same way, leaving command and meter in agreement. That is the saturation freeze's job. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
This commit is contained in:
co-authored by
Claude Opus 5
parent
35856a73ae
commit
9aed43990b
@@ -41,6 +41,7 @@ from .maintenance import IDLE, MaintConfig, Maintenance
|
||||
from .mqtt import MqttPublisher
|
||||
from .p1 import P1Ingest, build_source, is_enabled
|
||||
from .validate import ConfigRefused, refuse, validate_startup_config
|
||||
from .watchdog import SignWatchdog, SignWatchdogConfig
|
||||
from . import web
|
||||
|
||||
OPTIONS_PATH = "/data/options.json"
|
||||
@@ -103,6 +104,12 @@ class Controller:
|
||||
store,
|
||||
)
|
||||
|
||||
# SAFETY-02. One instance, one actuator, one cadence - see watchdog.py.
|
||||
self.sign_wd = SignWatchdog(SignWatchdogConfig(
|
||||
min_w=float(opts.get("sign_disagree_w", 300)),
|
||||
hold_s=float(opts.get("sign_disagree_s", 180)),
|
||||
))
|
||||
|
||||
# P1 ingestion (TEL-01). `meter_source: off` keeps the original
|
||||
# single-entity meter_entity path, so an existing install is unchanged
|
||||
# until it opts in.
|
||||
@@ -120,6 +127,11 @@ class Controller:
|
||||
self.sat_count = 0
|
||||
self.i_w = 0.0 # the loop's integrator, carried between cycles
|
||||
self.loop_w = None # what the loop asked for last cycle, or None
|
||||
# Did the grid-following loop actually win the LAST arbitration? That is
|
||||
# the question SAFETY-02 has to ask about the command standing on the
|
||||
# wire right now, so it is recorded when the arbitration happens rather
|
||||
# than re-derived a cycle later. Starts False: nothing is on the wire.
|
||||
self.following = False
|
||||
self.reason = "starting"
|
||||
self.grid = self.soc = self.batt = None
|
||||
self.peak_fc = None
|
||||
@@ -214,8 +226,29 @@ class Controller:
|
||||
for msg in result.events:
|
||||
self.log_event(msg)
|
||||
|
||||
# --- SAFETY-02, and it runs BEFORE the early return below -------------
|
||||
# ⚠️ ORDER MATTERS HERE. If this were evaluated after the "inputs missing
|
||||
# but not yet stale" hold, a run of held cycles would leave
|
||||
# `disagree_since` untouched across the gap and the timer would resume
|
||||
# from a start time that predates it. It is evaluated every cycle,
|
||||
# unconditionally, so a missing meter CLEARS the window - see watchdog.py.
|
||||
#
|
||||
# The value compared is the command STANDING ON THE WIRE, which is what
|
||||
# this cycle's fresh meter reading is a response to. `last_write` is that
|
||||
# value after the device clamp and confirmed accepted; `target` covers
|
||||
# the case where nothing has been written yet (and, deliberately, the
|
||||
# case where the last write was REJECTED - the inverter is then still
|
||||
# latched on `last_write`, which is exactly what `last_write` holds).
|
||||
was_tripped = self.sign_wd.tripped
|
||||
standing = self.last_write if self.last_write is not None else self.target
|
||||
if self.sign_wd.evaluate(standing, self.grid, self.following, now) \
|
||||
and not was_tripped:
|
||||
self.log_event("FAILSAFE " + self.sign_wd.reason)
|
||||
_LOG.error("SAFETY-02 TRIPPED - %s. Commanding 0 W and holding it "
|
||||
"until control is started again.", self.sign_wd.reason)
|
||||
|
||||
stale_after = float(self.o.get("stale_input_s", 15))
|
||||
if not self.inputs_ok:
|
||||
if not self.inputs_ok and not self.sign_wd.tripped:
|
||||
bad_for = (now - self.inputs_bad_since).total_seconds() if self.inputs_bad_since else 0.0
|
||||
if bad_for < stale_after:
|
||||
# A single missed poll is not a fault. Hold, keep the heartbeat
|
||||
@@ -235,6 +268,16 @@ class Controller:
|
||||
claims.append(Claim.limit("supervised", P_SAFETY, -max_w, max_w, "max_w"))
|
||||
|
||||
# --- safety stops ----------------------------------------------------
|
||||
# ⚠️ SAFETY-02 is claimed FIRST and unconditionally while latched. It is
|
||||
# a SET at P_SAFETY, so it outranks maintenance, peak shaving and the
|
||||
# loop alike - a controller pushing power the wrong way is wrong
|
||||
# whatever it thinks it is doing. Re-filed EVERY cycle: claims are not
|
||||
# sticky, and one filed once would lapse the next cycle and hand the
|
||||
# actuator silently back to the loop that was driving the wrong way.
|
||||
if self.sign_wd.tripped:
|
||||
claims.append(Claim.set("failsafe", P_SAFETY, 0.0,
|
||||
"sign disagreement"))
|
||||
|
||||
if not self.auto:
|
||||
claims.append(Claim.set("safety", P_SAFETY, 0.0, "stopped"))
|
||||
elif not self.inputs_ok:
|
||||
@@ -306,6 +349,28 @@ class Controller:
|
||||
resolution = resolve(claims)
|
||||
if resolution.contradiction:
|
||||
self.log_event("ARBITER CONTRADICTION - commanding 0 W, see the log")
|
||||
# --- SAFETY-02's arming gate ------------------------------------------
|
||||
# Was the number about to go on the wire chosen by the grid-following
|
||||
# loop, or by a strategy that commands against the meter on purpose?
|
||||
# Only the former is expected to agree in sign with P1. See gate 1 in
|
||||
# watchdog.py - without this, every maintenance grid charge trips the
|
||||
# failsafe within three minutes of starting.
|
||||
#
|
||||
# ⚠️ "THE LOOP WON" IS NOT ENOUGH, and the difference is a whole class of
|
||||
# false trip. A LIMIT claim can survive the loop winning and still
|
||||
# replace its number: maintenance's charge-only shaping is
|
||||
# `hi = -charge_w`, so the loop can ask for +500 W of discharge, win the
|
||||
# arbitration, and have the emitted value come out at -2500 W of grid
|
||||
# charge. Winner says "loop"; the wire carries maintenance's intent. So
|
||||
# the test is on the NUMBER, not on the name: the loop is following only
|
||||
# while the emitted value points the way the loop asked and is no larger
|
||||
# than it asked - i.e. limits reduced it, they did not redirect it.
|
||||
# Zero on either side falls out as not-following, which costs nothing:
|
||||
# a 0 W command cannot be a wrong-direction command.
|
||||
asked = self.loop_w
|
||||
self.following = (resolution.winner == "loop" and asked is not None
|
||||
and resolution.target_w * asked > 0
|
||||
and abs(resolution.target_w) <= abs(asked))
|
||||
self.target = resolution.target_w
|
||||
self.reason = resolution.explain()
|
||||
await self.write_setpoint(self.target)
|
||||
@@ -439,7 +504,14 @@ class Controller:
|
||||
"battery": self.batt,
|
||||
"soc": self.soc,
|
||||
"phase": self.maint.phase,
|
||||
"status": "running" if self.auto else "stopped",
|
||||
# ⚠️ SAFETY-02's alarm surface, and it is deliberately an existing
|
||||
# one. IF-01/IF-02 own `ems/event/failsafe` and the `failsafe active`
|
||||
# binary sensor and neither is built yet; inventing a bespoke topic
|
||||
# here would be a surface to migrate later. This sensor is already
|
||||
# discovered, already on every dashboard, and "failsafe" is
|
||||
# additive to its vocabulary rather than a change to it.
|
||||
"status": ("failsafe" if self.sign_wd.tripped
|
||||
else "running" if self.auto else "stopped"),
|
||||
}
|
||||
# ⚠️ ONLY when P1 ingestion is actually running. The ESP32's stale-input
|
||||
# watchdog subscribes to sensor.goodwe_p1_sample_age - see the entity-id
|
||||
@@ -521,6 +593,22 @@ class Controller:
|
||||
out.append({"ok": False, "warn": False,
|
||||
"text": "last write to the inverter was REJECTED - check the log"})
|
||||
|
||||
# SAFETY-02. Reported in both states: a watchdog nobody can see is armed
|
||||
# is a watchdog nobody trusts when it fires.
|
||||
if self.sign_wd.tripped:
|
||||
out.append({"ok": False, "warn": False,
|
||||
"text": "SIGN-DISAGREEMENT FAILSAFE - " + self.sign_wd.reason
|
||||
+ ". The inverter is held at 0 W. Find out why the "
|
||||
"command opposed the meter before starting control "
|
||||
"again; starting clears this."})
|
||||
else:
|
||||
held = self.sign_wd.held_s
|
||||
out.append({"ok": True, "warn": False,
|
||||
"text": f"sign watchdog: armed (trips after "
|
||||
f"{self.sign_wd.cfg.hold_s:.0f} s opposed, both over "
|
||||
f"{self.sign_wd.cfg.min_w:.0f} W)"
|
||||
+ (f" - opposed for {held:.0f} s now" if held else "")})
|
||||
|
||||
if not o.get("estop_fitted", False):
|
||||
out.append({"ok": False, "warn": True,
|
||||
"text": "no e-stop fitted: if this host dies the battery stays "
|
||||
@@ -538,7 +626,11 @@ class Controller:
|
||||
def status_payload(self) -> dict:
|
||||
checks = self.checks()
|
||||
bad = [c for c in checks if not c["ok"] and not c["warn"]]
|
||||
if bad:
|
||||
if self.sign_wd.tripped:
|
||||
# Outranks "NOT READY": nothing is missing, something went wrong.
|
||||
level, banner = "bad", ("FAILSAFE — the command opposed the meter. "
|
||||
"Inverter held at 0 W.")
|
||||
elif bad:
|
||||
level, banner = "bad", f"NOT READY — {bad[0]['text']}"
|
||||
elif not self.auto:
|
||||
level, banner = "warn", "Stopped — inverter commanded to 0 W"
|
||||
@@ -572,6 +664,15 @@ class Controller:
|
||||
self.auto = not self.auto
|
||||
self.store.set("auto", self.auto)
|
||||
self.log_event("control started" if self.auto else "control stopped")
|
||||
if self.auto and self.sign_wd.tripped:
|
||||
# ⚠️ THE ONLY WAY OUT OF A SIGN-DISAGREEMENT TRIP, on purpose.
|
||||
# It clears on a deliberate human start, not on the condition
|
||||
# going away - the condition ALWAYS goes away, because the trip
|
||||
# commands 0 W and a 0 W command cannot disagree with anything.
|
||||
# An operator pressing start has, at minimum, looked at the
|
||||
# banner that says why.
|
||||
self.sign_wd.reset()
|
||||
self.log_event("sign-disagreement failsafe cleared by operator")
|
||||
if not self.auto:
|
||||
self.target = 0.0
|
||||
await self.write_setpoint(0.0, force=True)
|
||||
|
||||
@@ -74,6 +74,17 @@ NOT READY banner already names the problem, (b) does not apply.
|
||||
was overruled. That firmware file's own comment says a lower bound on this
|
||||
"belongs in CFG-01, not here" - so here it is.
|
||||
|
||||
5. `sign_disagree_w` at or above `max_w`. [(a)]
|
||||
The arbiter's `supervised` limit bounds every command to +-max_w, and
|
||||
SAFETY-02's predicate needs `abs(command) > sign_disagree_w`. Set the
|
||||
threshold at or above the ceiling and the command side of the comparison
|
||||
is unsatisfiable BY CONSTRUCTION: the watchdog can never fire, on any
|
||||
input, ever. Same shape as 1 and 4 - the operator set a number, a layer
|
||||
they cannot see makes it mean something else, and nothing says so. Worse
|
||||
here, because what the status page reports in that state is "sign
|
||||
watchdog: armed". A disarmed guard that advertises itself as armed is the
|
||||
one thing this project has decided repeatedly it will not ship.
|
||||
|
||||
WHAT IS DELIBERATELY *NOT* REFUSED, because it is untidy rather than unsafe:
|
||||
|
||||
- `integrator_max_w` above `max_w`. DOCS.md is right that the only thing the
|
||||
@@ -238,6 +249,26 @@ def validate_startup_config(opts: dict, dev_min=None, dev_max=None) -> list[str]
|
||||
"or rebuild the firmware with a matching max_age_s and update "
|
||||
"validate.FIRMWARE_INGEST_VETO_S.")
|
||||
|
||||
# --- 5. a sign watchdog that can actually fire ---------------------------
|
||||
# ⚠️ Strictly `>=`, matching the predicate exactly: watchdog.py tests
|
||||
# `abs(commanded_w) > min_w`, and the arbiter holds `abs(commanded_w)` at or
|
||||
# below max_w, so threshold == max_w is already unsatisfiable. Anything
|
||||
# BELOW max_w is reachable and therefore fine - this refuses the disarmed
|
||||
# case only, not "close to the rail".
|
||||
sign_w = _number(opts, "sign_disagree_w", 300.0)
|
||||
if sign_w is None:
|
||||
problems.append(f"sign_disagree_w {opts.get('sign_disagree_w')!r} is not a number")
|
||||
elif max_w is not None and max_w > 0 and sign_w >= max_w:
|
||||
problems.append(
|
||||
f"sign_disagree_w is {sign_w:.0f} W but max_w is {max_w:.0f} W, so "
|
||||
"the SAFETY-02 sign-disagreement watchdog can never fire: the "
|
||||
"arbiter never lets a command exceed max_w, and the watchdog needs "
|
||||
f"a command over {sign_w:.0f} W. It would sit there reporting "
|
||||
"'armed' on the status page while being incapable of tripping - the "
|
||||
f"one runaway failure mode this system has actually observed. Lower "
|
||||
f"sign_disagree_w below {max_w:.0f} W (300 W is the measured "
|
||||
"default), or raise max_w.")
|
||||
|
||||
# --- warnings: real, but not worth refusing over -------------------------
|
||||
integ = opts.get("integrator_max_w")
|
||||
integ_w = None if not integ else _number(opts, "integrator_max_w", None)
|
||||
|
||||
@@ -0,0 +1,220 @@
|
||||
"""SAFETY-02 - the sign-disagreement watchdog.
|
||||
|
||||
WHAT IT CATCHES, in one sentence: a grid-following loop that is pushing power in
|
||||
the wrong direction, which every other guard in this system is blind to.
|
||||
|
||||
The stale-input watchdog (SAFETY-01) asks "is the meter still talking?". The
|
||||
saturation freeze asks "can the inverter follow?". The output clamp asks "is the
|
||||
number too big?". A loop can pass all three and still be charging the battery
|
||||
out of the grid while the house imports - the meter is fresh, the inverter is
|
||||
tracking beautifully, and the magnitude is inside the rating. The only thing
|
||||
that separates that from healthy operation is the SIGN.
|
||||
|
||||
⚠️ THIS IS NOT A HYPOTHETICAL. On 2026-08-20 the vendor controller (Illusmart)
|
||||
did exactly this four times in one day (NOTES.md §4.7). Both captures of that
|
||||
bus are committed - `sim/scenarios/bus-2026-08-20.log.gz` and the healthy
|
||||
`bus-2026-08-23.log.gz` in the infra repo - and `sim/replay_sign.py` drives this
|
||||
module over both of them. Every number in this file was measured on those two
|
||||
days, not chosen:
|
||||
|
||||
day samples gated in sign agreement
|
||||
2026-08-23 4 127 / 16 349 92.9 % (healthy)
|
||||
2026-08-20 6 892 / 15 598 55.6 % (the whole fault day)
|
||||
episode A 15:26-16:43 0.3 %
|
||||
episode B 17:11-18:28 0.8 %
|
||||
episode C 20:01-20:31 11.0 %
|
||||
episode D 20:55-21:11 0.0 %
|
||||
|
||||
That is the signature, and it is the SAME signature in all four episodes: not a
|
||||
noisier version of healthy, a near-total inversion.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
WHY IT LIVES HERE AND NOT IN THE FIRMWARE OR THE WITNESS
|
||||
|
||||
Three vantage points see three different things. The firmware knows what it
|
||||
WROTE, the witness Pi knows what was ON THE WIRE and whether the inverter ACKed
|
||||
it, and the add-on knows what it INTENDED and holds the authoritative meter.
|
||||
|
||||
This check is not command-versus-wire; it is command-versus-physics. It needs
|
||||
the emitted setpoint and the P1 net figure in the same place, and it needs the
|
||||
authority to command zero when they fight:
|
||||
|
||||
- the witness is read-only by charter and cannot command anything, so it could
|
||||
raise the alarm but never take the trip action the AC requires;
|
||||
- the firmware has the wire but not the meter. §5.1 makes P1 the only
|
||||
authoritative grid figure and the board only ever receives its AGE
|
||||
(`sensor.goodwe_p1_sample_age`), never its value. Putting the check there
|
||||
would mean shipping the meter to the ESP32 for no other reason, and it would
|
||||
be C++ per install rather than one generic guard;
|
||||
- the add-on has both halves already, plus an arbiter that can outrank every
|
||||
strategy with a P_SAFETY claim.
|
||||
|
||||
The cost of standing here is real and worth stating: this watchdog compares what
|
||||
we MEANT to put on the wire against the meter. If the firmware or the driver
|
||||
inverts the sign on the way out, the add-on's own view still agrees with itself
|
||||
and this check stays silent. That gap is a wire-versus-intent problem and it
|
||||
belongs to the witness, not here.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
WHAT "DISAGREEMENT" MEANS, PRECISELY
|
||||
|
||||
disagree = following
|
||||
and commanded_w * grid_w < 0
|
||||
and abs(commanded_w) > min_w
|
||||
and abs(grid_w) > min_w
|
||||
|
||||
Four gates, and each one exists to exclude a specific thing that is NOT a fault:
|
||||
|
||||
1. `following`. ⚠️ THE GATE THAT IS EASIEST TO FORGET AND MOST EXPENSIVE TO
|
||||
OMIT. Sign agreement is a property of a GRID-FOLLOWING loop. It is not
|
||||
expected of a strategy that deliberately commands against the meter -
|
||||
maintenance is exactly that. A maintenance grid charge of 2500 W into a house
|
||||
drawing 500 W puts +3000 W on the meter against a -2500 W command: opposed,
|
||||
both far over any sane threshold, and sustained for HOURS. Armed
|
||||
unconditionally this watchdog would trip on every single maintenance cycle,
|
||||
which is not a tuning problem, it is the wrong question being asked. So the
|
||||
caller says whether the grid-following loop actually won the arbitration this
|
||||
cycle, and the timer only accumulates when it did.
|
||||
|
||||
2. The strict `< 0` product. "Opposed" and "neither side is zero" in one
|
||||
expression.
|
||||
|
||||
3. The 300 W magnitude gate ON BOTH SIDES. Near zero the sign is noise, and near
|
||||
zero is where a healthy loop LIVES - the deadband holds the command still
|
||||
while the meter wanders either side of `target_grid_w`. On the healthy day
|
||||
only 4 127 of 16 349 samples (25 %) are even gated in; the other 75 % are the
|
||||
converged band where sign carries no information. This is also why the
|
||||
deadband cannot produce a false trip: inside it the meter is by definition
|
||||
under 300 W.
|
||||
|
||||
4. The 180 s continuity requirement. This is what excludes the legitimate
|
||||
transient. A load step reverses the meter's sign instantly while the command
|
||||
is still where the last cycle left it; slew limiting then needs a few cycles
|
||||
to cross over. Measured on the healthy day, the LONGEST such crossing is 30 s
|
||||
- and that is with a vendor controller far cruder than ours. 180 s is six
|
||||
times that. It is not a fitted threshold: at 60 s the healthy day still
|
||||
produces zero trips, and at 300 s the fault day still produces 13.
|
||||
|
||||
⚠️ A BATTERY THAT REFUSES A COMMAND CANNOT TRIP THIS, and that is structural
|
||||
rather than lucky. At SoC 10 % in Standby, a 1350 W discharge command into a
|
||||
1350 W import is DECLINED: the battery does nothing, so the meter stays at
|
||||
+1350 W and the command stays at +1350 W. Same sign. Agreement. A refusal leaves
|
||||
the meter where it was; only the inverter ACTING moves it, and acting in the
|
||||
commanded direction moves it toward zero, not through it. The failure mode this
|
||||
check keys on is the opposite of a refusal - it is the inverter obediently doing
|
||||
a wrong thing.
|
||||
|
||||
⚠️ A FROZEN METER cannot trip it either, for the same reason read the other way:
|
||||
a stuck reading of +800 W makes the loop command discharge and keep commanding
|
||||
discharge. Command and meter converge on AGREEING. Freezes are SAFETY-12's and
|
||||
SAFETY-01's problem, and this watchdog neither helps nor hinders there.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
STATE, TRIP AND LATCH
|
||||
|
||||
One timestamp, not a sample counter. The cycle rate is not fixed - a meter
|
||||
arrival, or `cycle_floor_s` elapsing, whichever comes first - so N samples is a
|
||||
different wall-clock window on every path, and the AC is written in minutes.
|
||||
|
||||
The latch is not optional and not a nicety. Commanding 0 W removes the command
|
||||
side of the comparison (|0| is not > 300), so the disagreement disappears the
|
||||
instant the trip works. Un-latched, this watchdog would trip, clear itself, and
|
||||
hand the actuator straight back to the loop that was driving the wrong way -
|
||||
three minutes later, forever. `tripped` therefore stays true until an operator
|
||||
`reset()`s it by starting control again, which is a deliberate human act after
|
||||
looking at why.
|
||||
"""
|
||||
|
||||
from dataclasses import dataclass
|
||||
from datetime import datetime
|
||||
|
||||
|
||||
@dataclass(frozen=True)
|
||||
class SignWatchdogConfig:
|
||||
"""Defaults, not constants - config.yaml carries both (SAFETY-02 AC 5)."""
|
||||
|
||||
min_w: float = 300.0
|
||||
hold_s: float = 180.0
|
||||
|
||||
|
||||
class SignWatchdog:
|
||||
"""One instance per actuator, evaluated once per control cycle.
|
||||
|
||||
⚠️ NOT SHARED ACROSS CADENCES. `disagree_since` is a wall-clock start time,
|
||||
so driving one instance from two loops at two rates would have each one
|
||||
resetting the other's window. If a fast on-device path ever wants this
|
||||
check, it gets its own instance - the same exactly-one-writer discipline the
|
||||
arbiter applies to the actuator, applied to the detector's own state.
|
||||
"""
|
||||
|
||||
def __init__(self, cfg: SignWatchdogConfig | None = None):
|
||||
self.cfg = cfg or SignWatchdogConfig()
|
||||
self.disagree_since: datetime | None = None
|
||||
self.tripped = False
|
||||
self.reason = ""
|
||||
|
||||
# -- the whole check, and it is a pure function of its arguments ----------
|
||||
def evaluate(self, commanded_w, grid_w, following: bool,
|
||||
now: datetime) -> bool:
|
||||
"""Advance the detector one cycle. Returns True while tripped.
|
||||
|
||||
`commanded_w` the EMITTED setpoint - what is standing on the wire now,
|
||||
after deadband, slew, quantisation and the arbiter. Not
|
||||
the optimizer's raw wish: the wire carries the emitted
|
||||
value, so anything else can disagree with the meter for a
|
||||
reason that is not a fault.
|
||||
`grid_w` net P1, + = importing. None when the meter is stale or
|
||||
missing, which CLEARS the timer rather than accumulating
|
||||
- a frozen figure held against a moving command would
|
||||
otherwise manufacture a disagreement in about three
|
||||
minutes, on top of SAFETY-01 having already commanded
|
||||
zero for the same cause.
|
||||
`following` did the grid-following loop actually win this cycle? See
|
||||
gate 1 in the module docstring.
|
||||
`now` the caller's clock, so this stays testable and replayable.
|
||||
"""
|
||||
if self.tripped:
|
||||
# Latched. Do not re-evaluate: the trip removed the evidence.
|
||||
return True
|
||||
|
||||
cfg = self.cfg
|
||||
disagree = (
|
||||
following
|
||||
and commanded_w is not None and grid_w is not None
|
||||
and commanded_w * grid_w < 0
|
||||
and abs(commanded_w) > cfg.min_w
|
||||
and abs(grid_w) > cfg.min_w
|
||||
)
|
||||
|
||||
if not disagree:
|
||||
self.disagree_since = None
|
||||
return False
|
||||
|
||||
if self.disagree_since is None:
|
||||
self.disagree_since = now
|
||||
return False
|
||||
|
||||
held = (now - self.disagree_since).total_seconds()
|
||||
if held < cfg.hold_s:
|
||||
return False
|
||||
|
||||
self.tripped = True
|
||||
self.reason = (
|
||||
f"SIGN_DISAGREEMENT: commanded {commanded_w:+.0f} W against a meter "
|
||||
f"reading {grid_w:+.0f} W for {held:.0f} s continuously "
|
||||
f"(limits: both over {cfg.min_w:.0f} W, held over {cfg.hold_s:.0f} s)"
|
||||
)
|
||||
return True
|
||||
|
||||
@property
|
||||
def held_s(self) -> float:
|
||||
"""How long the current disagreement has been standing, for the UI."""
|
||||
if self.disagree_since is None:
|
||||
return 0.0
|
||||
return (datetime.now(self.disagree_since.tzinfo)
|
||||
- self.disagree_since).total_seconds()
|
||||
|
||||
def reset(self) -> None:
|
||||
self.disagree_since = None
|
||||
self.tripped = False
|
||||
self.reason = ""
|
||||