SAFETY-12: the loop thinks on a clock, not only when the number moves
run_control() ran cycle() only when the meter value differed from the previous poll. A meter that repeats a value therefore ran no control cycles at all - while the heartbeat kept re-emitting the last command and the firmware kept putting it on the wire every 2 s. Layer 1 stayed fed and every indicator read healthy, so a command computed from an old reading went on being executed through whatever the load did next. TEL-05 measured it: 70 s at a literally constant 350.0 W, 14 arrivals, zero cycles. cycle_floor_s (default 15 s) is a deadline on the GAP between cycles, reset by every cycle whichever trigger fired - not a second scheduler. On a healthy meter it never elapses, so the cycle rate and the commanded sequence are unchanged; test_loop.py asserts that by driving the real loop twice on one binary (a huge cycle_floor_s reproduces the old behaviour) and diffing the writes. 15 s is bracketed: above the ~11 s worst gap on a merely-unlucky healthy meter (~5 s arrivals, 1 s detection, one dropped poll retried on the next tick), below meter_max_age_s and the firmware's 30 s ingest veto, and equal to stale_input_s. A floor cycle runs the full law. Freshness is already decided upstream - past meter_max_age_s the reading is None, which is a P_SAFETY 0 W claim - and the integrator advances per cycle, not per second, so bounding the gap bounds the accumulation. Not a freeze detector: nothing here decides whether a repeated reading is true. DOCS.md's "accepted deviation" passage is qualified rather than deleted - the window is now bounded at 3 x cycle_floor_s instead of open-ended, and its "nothing accumulates while it is stalled" argument is called out as having covered windup and not staleness. Same correction in control.py's comment. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
This commit is contained in:
co-authored by
Claude Opus 5
parent
e2e331ea54
commit
88cd97cc7a
@@ -67,6 +67,62 @@ A refusal is legible as a refusal: a banner that says in words that this is a
|
||||
configuration problem and nothing is broken, the numbered problems, no traceback,
|
||||
and exit status 78 (`EX_CONFIG`).
|
||||
|
||||
**SAFETY-12.** The control loop now evaluates on a clock as well as on a change.
|
||||
`run_control()` ran `cycle()` only when the meter value differed from the
|
||||
previous poll, so a meter that repeated a value ran **no control cycles at
|
||||
all** - while the heartbeat went on re-emitting the last command and the
|
||||
firmware went on putting it on the wire every 2 s. Layer 1 stayed fed, every
|
||||
indicator read healthy, and a command computed from an old reading kept being
|
||||
executed through whatever the load did next. Measured on the rig during TEL-05:
|
||||
70 s at a literally constant 350.0 W with 14 arrivals and zero cycles.
|
||||
|
||||
`cycle_floor_s` (default **15 s**) is a deadline on the gap between cycles, not
|
||||
a second scheduler: every cycle resets it, whichever trigger fired. On a healthy
|
||||
meter it never elapses, so the cycle rate, the write sequence and therefore the
|
||||
per-cycle gain the tuning was measured against are unchanged - asserted in
|
||||
`test_loop.py` by driving the real loop twice on one binary (a huge
|
||||
`cycle_floor_s` reproduces the old behaviour exactly) and comparing the
|
||||
commanded values.
|
||||
|
||||
15 s is bracketed, not round. Below it: arrivals are ~5 s (NOTES.md measures
|
||||
4.97 s), detected up to 1 s late by the 1 s poll, and one dropped poll is
|
||||
retried on the next tick - about 11 s worst case on a meter that is merely
|
||||
unlucky, which the floor must not fire on. Above it: `meter_max_age_s` is 30 s,
|
||||
past which there is no reading to evaluate, and the firmware's ingest veto is
|
||||
also 30 s - so the loop is guaranteed to have re-decided at least twice inside
|
||||
any window in which layer 1 might otherwise be the only thing deciding. It is
|
||||
also exactly `stale_input_s`, this system's existing answer to "how long may we
|
||||
hold without re-deciding".
|
||||
|
||||
A floor cycle runs the **full** law on the same inputs, integrator included. The
|
||||
freshness question is already answered upstream and answered harder - past
|
||||
`meter_max_age_s` the reading is None, which is "inputs missing", which is a
|
||||
`P_SAFETY` 0 W claim - so a floor cycle can only ever run on a reading this
|
||||
system already calls fresh. The integrator advances per *cycle*, not per second,
|
||||
so bounding the gap bounds the accumulation; `integrator_max_w` bounds it after
|
||||
that. A gentler second law for floor cycles would be a second set of dynamics
|
||||
nobody can test on this hardware.
|
||||
|
||||
⚠️ **This is not a freeze detector**, and TEL-05 established one cannot be built
|
||||
here: at the converged -10 W target a 1 Wh register needs ~6 minutes to move
|
||||
while the power figure legitimately repeats, so any threshold on `unchanged_s`
|
||||
false-trips at the exact operating point we run at. Nothing in this change
|
||||
decides whether a repeated reading is *true*. It stops "the number is the same"
|
||||
from meaning "do not think". The consequence, stated plainly: against a meter
|
||||
genuinely frozen at a wrong value the loop will now correct toward that wrong
|
||||
value rather than hold a stale command, bounded by `max_w`, the arbiter and the
|
||||
device rating. That was already what happened to a lying meter whose value
|
||||
merely jittered; bit-exact repetition was never a safety property.
|
||||
|
||||
`DOCS.md`'s "Saturation is counted in cycles, not seconds" section documented
|
||||
the old behaviour as an accepted deviation. It is **qualified, not deleted**:
|
||||
the deviation survives (the window is still counted in cycles, and 3 x 15 s is
|
||||
still not the specification's 10 s) but it is now bounded at 45 s instead of
|
||||
open-ended, and the passage's second justification - "nothing accumulates while
|
||||
it is stalled" - is called out as having covered integrator windup and not
|
||||
staleness, which was the actual hazard. The same wrong argument in
|
||||
`control.py`'s saturation comment is corrected too.
|
||||
|
||||
**TEL-04.** `meter_source: ha_signed` reads a single *signed* power entity, which
|
||||
is the shape a HomeWizard P1 publishes. Both transports 0.3.0 shipped require two
|
||||
unsigned registers and refuse negatives, so neither fits the meter installed here.
|
||||
|
||||
Reference in New Issue
Block a user