Merge pull request 'DOC-5: tell installers to turn on the Supervisor Watchdog' (#123) from DOC-5-watchdog into release/1.0

This commit was merged in pull request #123.
This commit is contained in:
2026-09-25 01:17:35 +02:00
2 changed files with 8 additions and 0 deletions
+3
View File
@@ -50,6 +50,9 @@ https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install **GoodWe RS485 Controller**.
Then turn on **Watchdog** on the add-on's Info tab — see
[Before you start](goodwe_controller/DOCS.md#before-you-start).
⚠️ **The repository must be PUBLIC for this to work.** Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
+5
View File
@@ -16,6 +16,11 @@ You need:
- A T-CAN485 (ESP32) flashed with `firmware/goodwe-master.yaml`
- A grid-power sensor already working in Home Assistant, updating every ~5–10 s
After installing, turn on **Watchdog** on the add-on's Info tab. A crashed
control loop stops the add-on at 0 W, and the Supervisor restarts it only when
Watchdog is on (it is off by default). See
`DECISIONS/SAFETY-61-control-task-death.md`.
## The safety model, in short
The inverter **holds its last command forever** — it has no meter-timeout. So: