Round-2 non-blocking findings, both fixed. ⚠️ THE WINDOW FIGURE WAS ARITHMETIC NOBODY HAD RUN. `min_w * (w_A + w_B) / w_B` = 6500 W is correct about `_fill()`'s PROPORTIONAL regime and is not a reachable steady state: the healthy pack's own 5000 W rating binds first. SWEPT on part 8b's own fixture, reproduced rather than transcribed: load equal OPT-09 site target A B 1000 199/200 0/200 1080 997 83 2000 199/200 0/200 2170 2003 167 3000 199/200 0/200 3250 3000 250 4000 199/200 4/200 4340 4006 334 4500 199/200 8/200 4890 4514 376 4900 199/200 41/200 5320 4911 409 <- largest suppressed 5000 199/200 195/200 8000 5000 3000 <- A at its rating 6000 199/200 195/200 8000 5000 3000 So the alarm returns BELOW the formula bound, not above it, and the largest site target reached with the wedged unit still under the 500 W threshold is 5320 W - not 6500. The equal-weights "suppressed below 1000 W" bound is unreachable for the same reason: the equal arm names the wedged unit 199/200 at EVERY load swept, 1000 W included. The formula and its check are kept, because the mechanism they state is right and it is the mechanism that generalises to other ratings. What was wrong was the sentence around them, in four places, implying the site passes through the bound. Each now carries the sweep and says the rating binds first. ⚠️ THIS NUMBER CAME FROM THE REVIEW, NOT FROM THE BRANCH, and was adopted in good faith by the implementer. The reviewer found it in round 2 and said so. That is worth recording: a figure arriving from a trusted reviewer got less scrutiny than one written by the author, and PROC-01's eight fabricated numbers in two days is now nine. The rule that catches it is the same either way - run it before you ship it. Also: the DECISIONS header's base sha, stale for the third time (464d398->3368231->3d29993, moved by two rebases and caught by review each time). It now records that history, and the header is why `test_translations.py`'s counts are computed rather than typed. SAFETY-43 is now named by id where the follow-up is referenced, so a reader can follow the thread from the disclosure to its closure. Suite: 25 files, all pass. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
307 lines
18 KiB
Markdown
307 lines
18 KiB
Markdown
# OPT-09 - the weights parameter, and what it is honestly for
|
|
|
|
**Status:** implemented. **Branch:** `OPT-09`. **Base:** `release/1.0` @ `3d29993` (rebased onto the UX-02 merge; it read `3368231`, and before that `464d398` - each rebase moved it and review caught it each time, which is why the counts in `test_translations.py` are now computed rather than typed)
|
|
(`git merge-base HEAD 3368231`; the branch was rebased and this line used to name
|
|
the pre-rebase base, `464d398`).
|
|
|
|
## 0. What was actually wrong
|
|
|
|
`allocator.plan()` has taken a `weights` argument since ALLOC-01, `_fill()`
|
|
consumes it in two passes, and **nothing had ever passed one**. Confirmed on the
|
|
base commit:
|
|
|
|
arbiter.py:535 def resolve(claims, *, units=None, weights=None, live=None, ...)
|
|
main.py:2422 resolve(claims, units=self.units, live=self.live_units(), ...)
|
|
|
|
So `weights` was None on every tick of every install, `plan()` turned that into
|
|
1.0 per unit, and the site target was split **50/50 regardless of what either
|
|
pack could do**. The card was filed as "per-pack arbitrage sizing"; the architect
|
|
pass found the sharper content, and it is the sharper content that this branch is
|
|
mostly about.
|
|
|
|
## 1. Two instruments, and they are not interchangeable
|
|
|
|
`allocator.py` states the rule this card is built on, and it is mechanical rather
|
|
than advisory:
|
|
|
|
> WEIGHTS EXPRESS PREFERENCE. ENVELOPES EXPRESS PERMISSION. A weight of 0 is
|
|
> "please do not use this unit", and it is honoured while any other unit has
|
|
> headroom - but it is NOT a constraint.
|
|
|
|
`_fill()` runs a deliberate **last-resort pass** over the zero-weight units when
|
|
the preferred ones saturate, so that a preference can never manufacture a
|
|
standing error at the meter. A pack at its own cut-out that is only *weighted*
|
|
to zero is therefore still commanded to discharge the moment its sibling fills
|
|
up. So this branch ships both:
|
|
|
|
| | question | mechanism |
|
|
|---|---|---|
|
|
| `packshare.envelope()` | MAY this pack be asked, at all, in this direction? | a `pack` UNIT claim at `P_SAFETY`, `hi = 0` at the cut-out, `lo = 0` at 100 % |
|
|
| `packshare.weights()` | GIVEN that both may, which should carry more? | energy headroom in kWh, handed to `resolve()` |
|
|
|
|
## 2. ⚠️ What the weights CANNOT do
|
|
|
|
ARCH-01's convex-combination argument - the gain at the meter is
|
|
`sum(a_i * g_i)`, so it lies in `[min g_i, max g_i]` for **any** split -
|
|
guarantees that a bad split cannot **destabilise** the site. It says nothing
|
|
about whether the site can **regulate**. A unit at its energy limit has
|
|
`g_i = 0`; the combination is still inside the interval and the load it was
|
|
asked to carry simply does not move.
|
|
|
|
Measured, `test_packshare.py` part 8, two units rated 2000 W each, B sitting on
|
|
its own floor and therefore answering 0 W to any discharge command. The plant is
|
|
modelled in that file (`lag_s = 0`, obeys within one cycle, bounded by its
|
|
rating) and the loop is the real `compute()`:
|
|
|
|
| load | arm | site target | shares | grid | unmet |
|
|
|---|---|---|---|---|---|
|
|
| 1500 W | shipped | +3000 W | A +1500, B +1500 | 0 W | 0 W |
|
|
| 1500 W | weights | +1500 W | A +1500, B +0 | 0 W | 0 W |
|
|
| 1500 W | envelope | +1500 W | A +1500, B +0 | 0 W | 0 W |
|
|
| 3000 W | shipped | +4000 W | A +2000, B +2000 | +1000 W | 0 W |
|
|
| 3000 W | weights | +4000 W | A +2000, B +2000 | +1000 W | 0 W |
|
|
| 3000 W | envelope | +4000 W | A +2000, B **+0** | +1000 W | **+2000 W** |
|
|
|
|
Three things are worth reading off that table, and the second and third are the
|
|
uncomfortable ones:
|
|
|
|
1. At a load the healthy pack can cover, the weights alone deliver the whole
|
|
improvement. The shipped arm reaches the same meter reading only by winding
|
|
the site target to **twice the load** and standing a +1500 W command on a
|
|
battery that answers nothing, permanently saturation-frozen. That is not a
|
|
working site, it is a site with no headroom left for the next load step.
|
|
2. At a load it cannot cover, **the weights stop working entirely**. The
|
|
weighted arm and the shipped arm command the identical +2000 W into the empty
|
|
pack, because `_fill()`'s last-resort pass hands the remainder to the
|
|
zero-weighted unit. Same shares, same watts, same error.
|
|
3. **And the envelope does not rescue the delivery either - it names the
|
|
shortfall.** Same 2000 W delivered, same 1000 W standing at the meter. What
|
|
changes is that the empty pack is commanded 0 W instead of 2000 W, and 2000 W
|
|
of site target is *reported* as unplaceable instead of appearing to have been
|
|
placed.
|
|
|
|
> **Weights are a comfort choice for STABILITY and NOT for DELIVERY.** Nothing in
|
|
> this add-on shifts a unit's load to its sibling once the sibling is at its
|
|
> rating, and weighting a failing unit down is not a remedy for it.
|
|
|
|
## 2b. ⚠️ The card's own premise is only half true
|
|
|
|
The card opens with *"a unit that stops delivering its share (empty, full,
|
|
curtailed, wedged) parks the site with a standing grid error and no alarm."*
|
|
After this branch: the **ask** stops, and while the sibling has headroom the site
|
|
regulates to zero error instead of winding to twice the load. The **standing grid
|
|
error does not stop** once the sibling is at its rating - §2's table measures
|
|
1000 W standing in all three arms - and there is **still no alarm** for it, only
|
|
a report. SAFETY-42 will not alarm on a pack at its own floor; that is one of its
|
|
acceptance criteria and its evidence is that the benign and the wedged case are
|
|
indistinguishable in the power domain.
|
|
|
|
So the two cards together mean: an empty pack limiting the site is now REPORTED
|
|
(`unmet_w`, an action-log line) and still, deliberately, NOT ALARMED. Whether it
|
|
should be alarmed is a decision - and the alarm it would need is about a site's
|
|
stored ENERGY, not about an inverter's delivery, so it is not this card's and not
|
|
SAFETY-42's. Recorded rather than quietly closed against a premise this card only
|
|
half meets.
|
|
|
|
## 3. Which floor, and which ceiling - the two places this could have become policy
|
|
|
|
**The floor is `bms_soc_floor` alone, never `peakguard.pack_floor_pct()`.** That
|
|
function's conjunction with `peak_soc_floor` is right for the peak guard and
|
|
wrong here: SAFETY-25 decided (2026-09-02, Option A) that `peak_soc_floor` bounds
|
|
the peak guard **only**, ordinary self-consumption discharges straight past it,
|
|
and closing an envelope at it would turn an operator preference into a hard stop
|
|
on the grid-following loop - the memo's **deferred Option B**, built by accident.
|
|
`delivery.py`'s `account()` made the same choice one step out, for the same
|
|
reason. Graded: a pack at 15 % with a 10 % cut-out is not closed, though a 20 %
|
|
EMS floor would have closed it.
|
|
|
|
**The ceiling is 100 %, and the coarseness is the honest answer.** There is no
|
|
per-pack charge ceiling anywhere in this add-on - `delivery.py` says so at length
|
|
and calls it a card, and it is why SAFETY-42 is armed on discharge shares only.
|
|
The only other number available is `arbitrage_soc_ceiling`, which is one
|
|
site-wide **trade policy**; filing it as a `P_SAFETY` envelope on the loop would
|
|
be the mistake above in the charge direction. So the envelope closes only where
|
|
the ask is physically impossible, and everything between is left to the weights -
|
|
which is the right instrument for a graded preference and is honest about being
|
|
only a preference.
|
|
|
|
## 4. N=1, and the tripwire this had to argue past
|
|
|
|
`actuator_for()` routes **every** source to the site at one inverter, so a `pack`
|
|
interval filed there would bound the SITE TARGET rather than a share. `main.py`
|
|
therefore does not file it at all below a roster of two - the same guard, for the
|
|
same reason, that SAFETY-30's `sign_site` carries. AC 4 ("at N=1 allocation is
|
|
byte-identical") is that `if`.
|
|
|
|
`test_peakguard.py` part 10f pins the claim-source set against `main.py`'s own
|
|
AST precisely so that a state-of-charge-conditioned claim cannot arrive quietly.
|
|
`pack` is state-of-charge-conditioned, so the argument is written at that set
|
|
rather than the count edited: the number is not an option, the claim is
|
|
unit-scoped so it cannot bound the site target, it is not filed at N=1, and part
|
|
10f's own note names this as the revisit trigger - *"under ALLOC-01 the reserve
|
|
becomes a PER-INVERTER INTERVAL AT THE ALLOCATOR rather than a ninth claim
|
|
here"*. Stage 1 is how an interval reaches the allocator and stage 1's input is
|
|
claims, so a unit-scoped claim is the shape that sentence asks for.
|
|
|
|
**What N=1 still does not get, said plainly:** nothing stops the loop discharging
|
|
into the BMS cut-out at one inverter. That is unchanged, it is SAFETY-25's
|
|
deferred option, and the BMS is what stops it.
|
|
|
|
## 5. SAFETY-42 - the same hazard from the opposite side
|
|
|
|
The seam is **the state of charge** - and they overlap in one direction, which
|
|
is what the rest of this section is about:
|
|
|
|
* **OPT-09 stops the site ASKING** a pack whose own SoC says it cannot deliver.
|
|
* **SAFETY-42 alarms** when a pack that said it could does not.
|
|
|
|
A wedged unit reads a healthy SoC, so **no envelope closes** - that half is
|
|
absolute, and it is why this card cannot stop the ask on a wedged box. A pack at
|
|
its floor is `account()`'s explained case, so SAFETY-42 stays silent - and after
|
|
this card that ask does not arrive in the first place, which removes the benign
|
|
arm from the detector's input rather than teaching it a new discriminator.
|
|
|
|
⚠️ **BUT THE WEIGHT DOES MOVE, AND IT NARROWS SAFETY-42's DETECTION WINDOW. THIS
|
|
IS A DETECTION REGRESSION AT N=2 AND IT IS NOT FIXED HERE.** An earlier draft of
|
|
this section said "no envelope closes and no weight moves - OPT-09 cannot see it
|
|
at all". The second clause was **false**, and it was load-bearing for the claim
|
|
that the two cards do not overlap. A weight is a function of the pack's ENERGY
|
|
HEADROOM, not of what the pack delivers, so a wedged unit's weight moves whenever
|
|
its headroom differs from its sibling's - which is the ordinary case this card
|
|
exists to exploit. And `delivery.delinquent()` (`app/delivery.py:484`)
|
|
names a unit only while its `short_by()` gap exceeds `min_w =
|
|
Tuning.saturation_w` - the comparison is `app/delivery.py:531`, and it is
|
|
**500 W in absolute watts**. Shrinking a unit's share shrinks its gap. Shrink the
|
|
share far enough and the gap drops below 500 W while the unit is still delivering
|
|
nothing, and the alarm stops firing.
|
|
|
|
Measured on the closed loop - real `compute()`, real `plan()`, real
|
|
`delinquent()`, modelled plant, B wedged at 15 % against its own 10 % floor so
|
|
nothing closes and `account()` explains nothing, i.e. a SAFETY-42 **true
|
|
positive** by that card's own definition:
|
|
|
|
load 1500 W equal weights (shipped) named on 199/200 cycles
|
|
shares {a:1500, b:1500} grid +0 W named=['inverter-b']
|
|
load 1500 W OPT-09 weights named on 0/200 cycles
|
|
shares {a:1505, b: 125} grid -5 W named=(nobody)
|
|
|
|
⚠️ That plant is modelled in `test_packshare.py`, and **inverter B does not
|
|
exist** (expected ~2026-09-12): it is two copies of A driven with different
|
|
numbers, and B's 4600 W / 20.48 kWh / 10 % floor are from the datasheet and the
|
|
serial. The claim is about the arithmetic of the split and the threshold, which
|
|
needs no hardware, and not about a GW5000S-BP.
|
|
|
|
At a load the healthy pack can cover - the regime where nothing else tells the
|
|
operator anything, `unmet_w` is 0, the meter is satisfied and no action-log line
|
|
fires - a wedged inverter goes from named on essentially every cycle to **never
|
|
named**. The suppression window widens from `site target < 2 * min_w` = 1000 W to
|
|
`site target < min_w * (w_A + w_B) / w_B`, which on that fixture is **6500 W** of
|
|
a 9600 W site; above it - once the healthy pack is at its own rating and
|
|
`_fill()`'s last-resort pass hands the wedged unit a big share again - the alarm
|
|
returns. ⚠️ BOTH BOUNDS ARE ARITHMETIC ABOUT `_fill()`'s PROPORTIONAL REGIME AND NEITHER IS A REACHABLE STEADY STATE. Swept on this fixture, the healthy pack's own 5000 W rating binds FIRST: suppressed 0/200 up to a 3000 W load, 4/200 at 4000 W, 41/200 at 4900 W (site target 5320 W, the largest reached with the wedged unit still under 500 W), then 195/200 at 5000 W once `_fill()` pins A at its cap and hands B 3000 W. So the alarm returns BELOW the 6500 W formula bound, not above it. The equal-weights 1000 W bound is unreachable for the same reason - the equal arm names the wedged unit 199/200 at every load swept, 1000 W included.
|
|
|
|
`test_packshare.py` part 8b grades all of it and **pins the current,
|
|
unflattering behaviour**, so that the day it changes a named check moves. The
|
|
closure - `delinquent()` measured against the ask rather than a flat 500 W - is
|
|
card **SAFETY-43**.
|
|
|
|
So the seam, stated accurately: **OPT-09 stops the ask AND narrows SAFETY-42's
|
|
detection window for a low-headroom unit.** The two cards do not merely meet from
|
|
opposite sides; this one takes something away from the other one. Closing the gap
|
|
means making `delinquent()` relative to the ask rather than absolute, which is
|
|
SAFETY-42's code and a design change - it is filed as its own card, deliberately
|
|
not done here, and this paragraph is its input. Until then this is a **disclosed
|
|
residual**, in the same voice as SAFETY-13's "2 of 272" and SAFETY-42's own "the
|
|
discriminator does not exist": at two inverters, a wedged unit with materially
|
|
less energy headroom than its sibling can go unreported at ordinary house loads.
|
|
|
|
⚠️ **And OPT-09 supplies the mechanism SAFETY-42 said was missing, without
|
|
connecting it.** That module's rejection of re-allocation rests on *"the only
|
|
re-allocation this add-on can express is ALL OR NOTHING [...] a partial
|
|
re-allocation is what would make acting safe, and the allocator has no way to
|
|
express it today"*. Passing weights **is** that expression. Wiring delinquency
|
|
into them is deliberately **not** done here: it would be acting on the alarm,
|
|
which SAFETY-42 refused with rig evidence (a unit derated to 50 % is 400 W worse
|
|
dropped than kept, and no instrument this add-on has can tell it from a wedged
|
|
one), and - see §2 - a weight cannot stop a unit being commanded anyway. That is
|
|
a card, and this paragraph is its input.
|
|
|
|
## 6. Per-pack arbitrage sizing, and the half that is deliberately not moved
|
|
|
|
`arbitrage.decide()` was handed `site_max_w` on **both** sides, so a two-pack
|
|
site would buy at the sum of the ratings whatever either pack's state of charge
|
|
was. It is now sized to the packs whose own SoC permits that direction
|
|
(`Controller.trade_power_w()`), using **arbitrage's own** bounds rather than the
|
|
BMS cut-out - sizing a trade is the trade's business; permitting a command is the
|
|
pack's.
|
|
|
|
Two honest limits:
|
|
|
|
* **The sell side is a no-op on every roster today.** `decide()` is handed
|
|
`pack_floor_soc` - the emptiest pack - so a sell is refused outright whenever
|
|
*any* pack is at or under the floor, i.e. in exactly the states where the sum
|
|
could be smaller than the site rating. The arithmetic is graded directly
|
|
(`test_packshare.py` part 9); it becomes reachable the day that gate is
|
|
per-pack.
|
|
* **Moving that gate is not this card's.** Sizing a sell off the *fullest* pack
|
|
would let the trade proceed while the emptiest pack was below
|
|
`arbitrage_soc_floor`, and the only per-pack instrument that could keep it out
|
|
of that pack is the weights - which are a preference, and `_fill()` will hand
|
|
it watts anyway. Doing it safely needs an envelope that depends on WHICH CLAIM
|
|
WON the tick, which the arbiter's partition does not express. §2 is why that is
|
|
a real objection and not a hedge.
|
|
|
|
`arbitrage.decide()` also now refuses a **0 W sizing** by name (`IDLE_NO_SIZE`),
|
|
because a `Claim.set(..., 0.0)` at `P_ARBITRAGE` is a park order that outranks
|
|
the loop - the failure the note on `claim()` is already written against. The
|
|
sizing can never be zero on a tick that trades today; that is a coincidence of
|
|
the existing gate, and this makes it structural instead.
|
|
|
|
## 7. The fixture, which is the hard part
|
|
|
|
Two packs that differ in only ONE of SoC and capacity cannot separate a
|
|
SoC-aware weighting from a capacity-aware one; two identical packs cannot
|
|
separate ANY weighting from any other. `test_packshare.py` part 1 grades the
|
|
fixture itself before anything is asserted with it - four candidate schemes
|
|
(equal, power rating, SoC only, energy), four distinct splits of the same
|
|
1000 W:
|
|
|
|
equal A +500, B +500
|
|
power A +521, B +479
|
|
soc only A +125, B +875
|
|
energy A +97, B +903
|
|
|
|
and the counterfactuals: on two identical packs all four collapse to one answer;
|
|
at the same SoC, `soc only` collapses onto `equal`; at the same capacity,
|
|
`energy` collapses onto `soc only`.
|
|
|
|
## 8. Provenance of every number
|
|
|
|
* A: **5000 W, 15.36 kWh, 10 % floor** - measured (GW5000S-BP, register 0x0560).
|
|
* B: **4600 W, 20.48 kWh, 10 % floor** - **FROM DATASHEET AND SERIAL**
|
|
(`goodwe/NOTES.md` §1.1b, GW5048D-ES `55048ESU22AW0992`). ⚠️ **Inverter B does
|
|
not exist** (expected ~2026-09-12).
|
|
* Every two-unit run in `test_packshare.py` is arithmetic over intervals and
|
|
weights, or a plant modelled in that file. `sim/plantsim.py:216`'s `INVERTER_B`
|
|
is **inverter A copied** with `measured=False`, so any two-inverter simulation
|
|
result anywhere in this project is **two copies of A**.
|
|
* No rig was taken, no hardware was touched, and nothing here is evidence about
|
|
a second GoodWe inverter.
|
|
|
|
## 9. Config
|
|
|
|
`capacity_kwh` joins the `inverters` roster as an **optional** per-entry key
|
|
(`float(0.1,200)?`) - the opposite choice to SAFETY-32's required
|
|
`bms_soc_floor`, and for that card's own reason: a missing cut-out would have to
|
|
be *defaulted*, and one default for two batteries protects the shallower pack
|
|
with the deeper pack's number, whereas a missing capacity has an honest answer -
|
|
no opinion about the split, every unit weighs 1.0, which is exactly what shipped.
|
|
|
|
It is **all or nothing across the roster** and rule 9 refuses a partial one: a
|
|
pack measured in kWh beside a sibling weighing a dimensionless 1.0 is not a
|
|
comparison, `weights()` answers "no opinion" for the whole roster in that case,
|
|
and a key that silently changes nothing is worse than one that refuses to load.
|
|
|
|
There is deliberately **no flat `capacity_kwh`**: at one inverter there is no
|
|
split to weight, so it would be an option an operator can set and nothing reads.
|