The first thing in this system that can STOP a runaway rather than alarm on one. Each cycle it projects the open 900 s block from P1 telegrams and, over the ceiling, files one arbiter claim: a lower bound at P_PEAK, sized as excess = 900*(projected-ceiling)/remaining added to the MEASURED battery power. No writes, no I/O, no clock, no state between calls. Replayed independently by the reviewer on a separate harness: 2026-08-20's billed quarter 5029.8 W -> 3485.3 W, both days 189/190 -> 190/190 under the 3500 W soft limit, 878 Wh modelled discharge on the failure day and 0 Wh with 0 engagements on the healthy one. Verified as properties rather than witnesses: the lo-limit claim cannot cap discharge or export (hi is inf; 0 of 54 loop/floor pairs lowered the target; no floor in 0..5000 W reduces a full-rate discharge; decide() emitted 0 negative floors over 630 input combinations), and the 900/remaining gain is exactly 1.0 at the top of the block, growing, bounded at the end by the achievable_w clamp so it can never file lo > hi. Round one held this PR on three wiring mutations that left all twelve suites green while a default install parked at 0 W in the billed quarter - including the suppression re-gated on the optional peak_forecast_entity, verbatim the historical defect this card's own comment described. All three are closed. The conjunction moved out of main.py into peakguard.shaping_suspended() so the check can assert on the shipped expression, and part 7 now executes the mutations against the real Controller.cycle(). The reviewer confirmed the harness cannot go vacuous: re-inlining the conjunction in main.py with behaviour-identical code turns B1 and B2 RED rather than green, because they assert the mutation takes effect. Eight further reviewer mutations this round, all red, no survivors. One note recorded, not blocking: the parsed-syntax grade on decide(batt_w=...) is defeated by a decoy .decide() call or by overwriting self.batt before the call, and it is the behavioural checks beside it that catch both. AC 3 remains TARIFF-01's and is NOT met - do not close the card as AC 3 met. SAFETY-24, the missing SoC backstop on the forced discharge, is named in peakguard.py with the 878 Wh figure and must land before this reaches a client install.
GoodWe RS485 Controller — Home Assistant add-on repository
Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.
repository.yaml add-on repository metadata
goodwe_controller/ the add-on
config.yaml manifest + options schema (the per-site config form)
app/ the controller
control.py the control law — pure functions, no I/O
maintenance.py the monthly cycle state machine
hass.py Supervisor/Core API access
store.py persistent state in /data
mqtt.py optional status entities
web.py ingress UI
main.py orchestration, heartbeat, failsafe behaviour
test_control.py runnable checks — no framework needed
test_maintenance.py runnable checks — walks a full cycle in fake time
DOCS.md the add-on's documentation tab
firmware/goodwe-master.yaml ESPHome config for the T-CAN485
estop/rs485_log.py optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf the guide techs carry (10pp, A4)
docs/build_guide.py its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md how to edit and rebuild the guide
Picking this up after a break? Read HANDOVER.md first — current state,
what is known broken, and what to do next.
Install
Settings → Add-ons → Add-on store → ⋮ → Repositories → add
https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install GoodWe RS485 Controller.
⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
goodwe_controller/ into the machine's /addons/ folder, then
ha store reload — it appears as a Local add-on.
⚠️ Bump version: in goodwe_controller/config.yaml for every change.
Supervisor keys the built image by that version, so without a bump it silently
reuses the old image and your fix appears not to work — on your bench and on
every client's machine.
Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.
Read this first
The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.
Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:
- ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
- Wind-down before firmware updates — 0 W written before the update starts.
- RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.
Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md
§10 signed.
Development
The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:
cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py
Both must pass before shipping any change. They are not unit-test theatre —
each assertion corresponds to a rule whose absence produced an observed failure
on real hardware, and the comments in control.py say which.
Compatibility
Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:
| tag | platform | verdict |
|---|---|---|
ESU EMU ESA BPS BPU EMJ IJL |
105 — ES/EM/BP, AA55-era meter bus | supported |
SPB SPN |
745 — SBP G2 (GW…-SBP-20) |
no |
ESN ESC |
745 — ES G2 (GW…-ES-20) |
no |
ETU EHU BTU … |
205/745/753 — ET/EH/BT hybrids | no |
SDT DST MSU NSU … |
PV-only inverters — no battery to control | no |
A "-20" or "G2" suffix means a different platform with a different meter
protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which
is also what Home Assistant's own integration uses to pick a protocol.
- GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
- The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.