The durability claim this PR shipped was FALSE, and the reviewer of #31 disproved it by building the fix. Part 10 said, in four committed places, that it "goes RED the day a loop-side floor is built, so the exposure cannot change size under a green suite". The reviewer implemented the memo's own recommended Option B in main.py - a `Claim.limit("reserve", P_LOOP, hi=0.0)` filed under a `loop_soc_floor` - and the ENTIRE SUITE STAYED GREEN. Part 10 green. Mutation 13 went on printing "NOTHING PREVENTS IT, ON PURPOSE" and the same 21 % -> 10.0 %, on a tree where something DID prevent it. Pushed to an absurd always-binding 95 % reserve it was caught only by SAFETY-24's pre-existing part 7 wiring checks; part 10 was still green. THE CAUSE IS STRUCTURAL, not a missing assertion. `replay_loop()` hand-builds main.py's claim list as a literal `[supervised, loop, peakguard.claim(...)]`, so it is blind to any claim main.py ADDS - which is exactly where AC 2 would be built. That is this repository's named failure mode: a check that observed something other than what it claimed to observe, shipped as a guarantee inside the document that recommends the change. THE FIX IS 10f: THE CLAIM-SOURCE SET, PINNED, two ways because the two fail differently. * STATICALLY, over `Controller.cycle()`'s own AST. Every `claims.append(...)` in it must be one the scan can read - an unreadable append FAILS rather than counting as nothing, which is how a scan like this goes quietly vacuous - and the sources it can file must be exactly {device, supervised, failsafe, safety, peak, arbitrage, maintenance, loop}. A ninth takes part 10 red on the line it is written, in every configuration, whether or not any fixture here reaches the state that files it. * DYNAMICALLY, through REAL `Controller.cycle()`s with main.py's OWN `resolve` spied - not a list this file built and hoped matched - swept over the WHOLE 0..100 % SoC range in the two states 10a-10c replay. Idle: exactly {device, supervised, loop}. Floor-limited: exactly {device, supervised, loop, peak}. A claim conditioned on a low pack, which is the shape a loop-side floor has, cannot hide from a sweep that visits 0 %. And the fold is checked rather than assumed: main.py's two P_SAFETY rating limits are both symmetric LIMITs, so replay_loop() modelling them as one `supervised` claim at the tighter bound is exact. MEASURED AGAINST THE COUNTEREXAMPLE. Reproduced first on the unfixed tree (green, as reported). On this tree the reviewer's Option B at its recommended default takes part 10 RED on 3 checks, and the 95 % variant on 6. Nine mutations were run in all, each against a freshly copied tree with no `__pycache__` present, mounted `:ro`; all nine red, no survivors, no `+0 B` delta. MUTATION.md records why a second round was needed: the first round's mutations were all aimed at DISARMING the guard, while the claim part 10 actually made was about the guard being FIXED. The four false sentences are replaced with what is now true, and each says WHICH half catches WHICH shape - 10f for an arbiter claim (Options B and C), 10a-10c for a clamp inside control.compute() or the guard (Option D), which the replay drives directly. AC 2 IS STILL OPEN AND NOTHING HERE BUILDS IT. The loop-side floor was a test mutant, reverted before commit. The memo still says "Status: OPEN. This is a memo, not a decision." Also, non-blocking, from the same review: the NOT READY banner had inherited the new scope sentence and become a ~550-character paragraph that the row three lines below repeated verbatim. A checks() row may now carry an optional short `banner` form; the floor-limited row does, and `status_payload()` prefers it. THE ROW IS UNCHANGED - shortening that would have been weakening AC 3 - and rows without the key are unaffected. Graded, and mutated: dropping the short form goes red. Merged origin/release/1.0 first (CI-02), keeping both tickets' CHANGELOG entries. Full suite green: 17/17 in goodwe-addon-ci (test_ci_gate.py needs `git`, which CI-02 added to .gitea/ci/Dockerfile but the local image lacks; run with it installed and it passes). Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
GoodWe RS485 Controller — Home Assistant add-on repository
Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.
repository.yaml add-on repository metadata
goodwe_controller/ the add-on
config.yaml manifest + options schema (the per-site config form)
app/ the controller
control.py the control law — pure functions, no I/O
maintenance.py the monthly cycle state machine
hass.py Supervisor/Core API access
store.py persistent state in /data
mqtt.py optional status entities
web.py ingress UI
main.py orchestration, heartbeat, failsafe behaviour
test_control.py runnable checks — no framework needed
test_maintenance.py runnable checks — walks a full cycle in fake time
DOCS.md the add-on's documentation tab
MUTATION.md how to run a mutation so the result means something
tools/mutation_run.sh the mutation harness - purges bytecode, then grades
firmware/goodwe-master.yaml ESPHome config for the T-CAN485
estop/rs485_log.py optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf the guide techs carry (10pp, A4)
docs/build_guide.py its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md how to edit and rebuild the guide
Picking this up after a break? Read HANDOVER.md first — current state,
what is known broken, and what to do next.
Install
Settings → Add-ons → Add-on store → ⋮ → Repositories → add
https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
then install GoodWe RS485 Controller.
⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it
anonymously; against a private repo the store shows nothing and gives no useful
error. If it must stay private, install locally instead: copy
goodwe_controller/ into the machine's /addons/ folder, then
ha store reload — it appears as a Local add-on.
⚠️ Bump version: in goodwe_controller/config.yaml for every change.
Supervisor keys the built image by that version, so without a bump it silently
reuses the old image and your fix appears not to work — on your bench and on
every client's machine.
Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.
Read this first
The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.
Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:
- ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
- Wind-down before firmware updates — 0 W written before the update starts.
- RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.
Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md
§10 signed.
Development
The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:
cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py
Both must pass before shipping any change. To prove a check bites - the way
almost every claim in this repository was established - mutate the module and
run tools/mutation_run.sh, which clears __pycache__ first. It is not
optional: a same-size edit reverted inside one second leaves CPython reusing the
old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md
has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre —
each assertion corresponds to a rule whose absence produced an observed failure
on real hardware, and the comments in control.py say which.
Compatibility
Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:
| tag | platform | verdict |
|---|---|---|
ESU EMU ESA BPS BPU EMJ IJL |
105 — ES/EM/BP, AA55-era meter bus | supported |
SPB SPN |
745 — SBP G2 (GW…-SBP-20) |
no |
ESN ESC |
745 — ES G2 (GW…-ES-20) |
no |
ETU EHU BTU … |
205/745/753 — ET/EH/BT hybrids | no |
SDT DST MSU NSU … |
PV-only inverters — no battery to control | no |
A "-20" or "G2" suffix means a different platform with a different meter
protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which
is also what Home Assistant's own integration uses to pick a protocol.
- GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
- The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.