glenn schrooyenandClaude Opus 5 547d796c5d CFG-01 review: widen the rule, refuse the firmware-veto case, fix the stop footgun
Review findings, all confirmed in code before changing anything.

THE RULE DID NOT AUTHORISE ITS OWN BEST REFUSAL. The stated test was
"makes a safety mechanism inoperative, or makes a stated limit untrue",
and a blank setpoint_entity does neither - layer 1 pinning the inverter
at 0 W is the failsafe WORKING, as validate.py's own text admitted. The
real justification is a second, separate category: the add-on is inert
and indistinguishable from healthy. Stated as (a) and (b), with each
refusal tagged, and with both halves explicitly bounded - (a) is not
"any two numbers that could disagree", (b) is not "anything degraded".
Left implicit, the gap is where trivia-creep comes back in.

meter_max_age_s ABOVE THE FIRMWARE'S VETO IS NOW REFUSED. The schema
allows int(5,300); the firmware's threshold is a compile-time
`max_age_s: "30"` and it trips layer 1 at `p1_age_s >= 30`. At 120 the
add-on believes a 119 s reading is fresh and keeps commanding while the
board has already vetoed and is holding at 0 W - healthy meter, running
controller, nothing moving. Structurally identical to the max_w case,
and unlike max_w it is settable on this install, so the headline
behaviour finally has a live demonstration. That firmware file's own
comment says a lower bound on this "belongs in CFG-01, not here".

Only ABOVE is refused: below the veto the add-on gives up first, which
is fail-safe and visible on its own status page. Scoped to P1 being
enabled, because meter_max_age_s governs nothing otherwise.
FIRMWARE_INGEST_VETO_S cannot be imported from a compile-time YAML
substitution, so it carries a note on the single direction in which it
can go stale - and a warning that TEL-06 is editing `ingest_stale`, so a
matching integer may stop meaning a matching rule.

stop= WAS A LIVE FOOTGUN. It defaulted to None, which made a Controller
that cannot stop itself the DEFAULT one. On the late-refusal path that
meant: log the banner, return, and leave the process alive forever with
no control loop and no exit - the exact "inert but looks healthy"
failure this module exists to refuse. Now required and keyword-only, so
the broken shape does not construct; test_p1.py's five call sites pass
an Event.

That whole path had no test and no live demo. It has one now: it drives
run_control() against a device that only reports a narrower range once
the loop starts, and asserts it refuses, signals, returns, and writes
NOTHING - plus the converse, that an agreeing device leads to real
writes. This also covers the max_w composition that cannot be reached
through the Supervisor on the live install.

max_w <= 0 is refused. Schema-blocked in production, but
validate_startup_config() is the simulation suite's entry point too, and
a non-positive max_w inverts the arbiter's supervised bounds into a
contradiction that reads as a safety trip rather than a typo.

Verified live 2026-08-28 (backup goodwe_controller-cfg01r2-1787940076):
meter_max_age_s 120 refused with a message naming 120, 30, and THE
FIRMWARE WINS; no traceback; add-on restored byte-exact and running.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-28 20:05:10 +02:00

309 lines
18 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Changelog
## 0.4.0
**CFG-01.** The add-on now refuses to start on a configuration it cannot honour,
instead of logging a line and carrying on. `validate_startup_config()` runs in
`amain()` before the broker, the web server or any task exists, so a refusal
cannot leave half a controller running behind a UI.
It refuses only where continuing produces one of two outcomes: **(a)** a stated
limit is untrue - the operator configured a bound and a lower layer silently
enforces a different one - or **(b)** the add-on is inert and indistinguishable
from healthy. (b) is not a special case of (a): with no `setpoint_entity`, layer
1 pinning the inverter at 0 W is the failsafe *working*. The system does not
become unsafe, it becomes a convincing impression of a working controller.
Four things qualify:
- **`max_w` above (or below) the setpoint device's own rating.** This is the one
that changed behaviour. It used to warn `the device wins` and run anyway, with
`write_setpoint()` silently clamping, so the configured ceiling was never the
real one and the only evidence had scrolled off the log. The refusal names the
configured value, the device's value, and which wins.
- **No `setpoint_entity`.** A controller with no actuator: every write is a
no-op, the device rating is never read, and the ESP32 heartbeat that holds off
the layer-1 failsafe never happens. It ran, looked healthy, and moved nothing.
- **A `meter_source` that can never produce a reading** - missing `p1_host`,
missing `p1_net_entity`, a blank MQTT topic, a phase list disagreeing with
`meter_phases`, an unknown source name, or a `meter_poll_s` at or past
`meter_max_age_s`. These were already caught, but they only *disabled
ingestion*, which leaves the grid reading None forever: permanent "inputs
missing", 0 W, and a status page indistinguishable from a healthy meter nobody
has sent anything to yet.
- **`meter_max_age_s` above the firmware's ingest veto.** The schema accepts
`int(5,300)`; the ESP32's threshold is a compile-time `max_age_s: "30"` and it
trips layer 1 at `p1_age_s >= 30`. Set 120 and the add-on treats a 119 s
reading as fresh and keeps commanding, while the firmware has already vetoed
and is holding the inverter at 0 W - healthy meter, running controller,
nothing moving, and no line anywhere saying the number you set was overruled.
Structurally the same fault as the `max_w` case. Only *above* the veto is
refused: below it the add-on gives up first, which is fail-safe and visible on
its own status page. Mirrored as `validate.FIRMWARE_INGEST_VETO_S` - it cannot
be imported from a compile-time YAML substitution, so it carries a note about
the one direction in which it can go stale.
`max_w` at or below zero is refused too. Schema-blocked on a real install, but
`validate_startup_config()` is now also the simulation suite's entry point, and
a non-positive `max_w` inverts the arbiter's `supervised` bounds into a
contradiction that resolves to 0 W - i.e. it would read as a safety trip rather
than as the typo it is.
The predicates for the meter group still live in `p1.validate_meter_options()`,
which `build_source()` also calls - one definition, two callers, not two
competing validators. Two transports gained a check they never had: `ha_dsmr`
with only one of its two entities, and `mqtt_p1` with a blank topic, both of
which previously built a transport that could never read.
Deliberately **not** refused, because it is untidy rather than unsafe:
`integrator_max_w` above `max_w` (the arbiter still bounds the wire to ±max_w,
so the cost is unwind latency, not amperage - warned), a missing `soc_entity` /
`batt_entity` (fail-safe, and already a red NOT READY banner naming it), a
`setpoint_entity` that has not appeared on the Core API yet (ESPHome is routinely
late; refusing would make a slow boot need a human - re-checked once the real
rating arrives), and a thin-but-nonzero `meter_poll_s` margin.
A refusal is legible as a refusal: a banner that says in words that this is a
configuration problem and nothing is broken, the numbered problems, no traceback,
and exit status 78 (`EX_CONFIG`).
**TEL-04.** `meter_source: ha_signed` reads a single *signed* power entity, which
is the shape a HomeWizard P1 publishes. Both transports 0.3.0 shipped require two
unsigned registers and refuse negatives, so neither fits the meter installed here.
**TEL-05.** `meter_source: homewizard_local` polls the meter's own local API
directly. This exists because of something the HA paths cannot do: Home Assistant
fires no state change for a repeated reading and exposes no arrival signal at
all, so `sensor.p1_sample_age_s` on those transports measures time since the
*value changed*, not since the meter *reported*. Real captured data has gaps of
42 s and 97 s between changes on a perfectly healthy meter - long enough for a
30 s staleness threshold to command 0 W for no reason. Every HTTP response to the
local API is a genuine arrival, so the age means what it says.
Verified on the rig against a literally constant 350.0 W for 70 s - the exact
state where the HA path recorded zero samples in 45 s - with 14 arrivals and the
age never exceeding the poll cadence.
Set `p1_host` to the meter's address and `meter_poll_s` (default 5 s, matching
the meter's own ~5 s update). Still defaults to `off`; nothing changes for an
install that does not opt in.
Freeze detection is separate and deliberately not thresholded: a meter answering
200 OK with a stale number *is* arriving, so no arrival stamp can flag it. The
energy registers carry that as `unchanged_s`, surfaced on the status line for a
human to read rather than alarmed on - at a converged -10 W a 1 Wh register needs
about six minutes to move, so any threshold would false-trip at the target
operating point.
## Unreleased
**TEL-05.** A fourth `meter_source`, `homewizard_local`, which polls a
HomeWizard P1's **own local API** (`GET /api/v1/data`) instead of watching a
Home Assistant entity. Set `p1_host` to the meter's address; `meter_poll_s`
(default 5 s, the meter's own update rate) sets the cadence.
✅ **This is the first transport whose `sensor.p1_sample_age_s` measures when
the meter *reported*, and therefore the first one a firmware watchdog may
threshold.** Every HTTP response is an arrival: the meter answered, now, with
its current reading, and whether the *number* moved is not consulted. Home
Assistant cannot express that at all — a repeated reading emits no
`state_changed`, advances `last_reported` on neither serialiser, and
`state_reported` is not subscribable ("Event filter is required"). On
`ha_signed` that made a healthy meter under a flat load indistinguishable from
a dead one, and our own capture of this house's meter goes 42.2 s and 97.0 s
between changes — both past the default `meter_max_age_s` of 30, i.e. a false
trip to 0 W on a meter that is fine. If you have a HomeWizard P1, move to this
mode.
Everything TEL-01 established is reused, not re-implemented: ingest
timestamping, `meter_max_age_s`, the clock-recomputed age, the plausibility
bounds and the §20 unsigned-decode rejection, and the same `split_signed` sign
convention `ha_signed` uses. A failed or timed-out poll submits nothing, so it
is a *missing* reading — never 0 W — and it does not reset the age.
Verified on the ENV-01 rig against `sim/hwsim.py`, steady and with `--fault
freeze` injected. Still defaults to `off`.
⚠️ **An arrival stamp still cannot see a *frozen* meter**, and no arrival
detector can: a meter answering `200 OK` forever with a stale number is
arriving. The local API does expose what the HA path never had — the
`total_power_*_kwh` registers stop advancing — and the transport tracks it as
`unchanged_s`, but that is deliberately **not** folded into the age and not
thresholded: this controller regulates grid power toward ~0 W, and at a
converged −10 W the export register needs six minutes to move by its 1 Wh
resolution while the power figure legitimately repeats. Thresholding it at 30 s
would rebuild the false-trip limit cycle at the exact operating point we aim
for. Freeze detection needs the low-power case solved first, separately. It is
shown on the status page's P1 line instead — leaving it unthresholded only
holds up if a human can read it, so now they can.
**TEL-04.** A third `meter_source`, `ha_signed`, reading **one signed** Home
Assistant entity: positive = import, negative = export. That is the shape a
HomeWizard P1 publishes (`sensor.p1_meter_active_power`), and it is the meter
actually fitted here - which neither TEL-01 transport can read, because
`ha_dsmr` needs two unsigned registers and refuses a negative one, i.e. every
exporting telegram. Set `p1_net_entity`, and `p1_phase_net_entities` for the
per-phase capacity-tariff figures on a three-phase connection.
Everything TEL-01 established is inherited rather than re-implemented - the
new transport is a subclass of the `ha_dsmr` one overriding only which
entities it wants and how they become a sample. So ingest timestamping,
`meter_max_age_s`, `sensor.p1_sample_age_s` recomputed against the clock and
republished once a second, the plausibility bounds, and `unavailable` /
`unknown` treated as a *missing reading and never 0 W* all behave identically
across the three sources.
Still defaults to `off`; an existing install is unaffected until it opts in.
⚠️ **`sensor.p1_sample_age_s` is published on `ha_signed`, but must not yet be
thresholded by the ESP32 stale-input watchdog.** On the HA WebSocket paths the
age is stamped from `state_changed`, so it measures time since the value
*changed*, not since the meter *reported* - and Home Assistant exposes no
arrival signal for a repeated reading (no `state_changed`, no `last_reported`
movement on either serialiser, and `state_reported` is not subscribable over
the WebSocket). Measured on the ENV-01 rig against the real HomeWizard
integration. `ha_dsmr` mostly escapes it because a telegram moves several
entities at once; `ha_signed` has one, so a healthy meter under a flat load is
indistinguishable from a dead one. Our own capture has the house meter going
42.2 s and 97.0 s between changes. Raising `meter_max_age_s` does not fix that,
it only chooses which error you get; the fix is an arrival stamp from the meter
itself and is a separate ticket. Full detail in DOCS.md.
## 0.3.0
**SAFETY-04.** The control law's integrator is now an explicit accumulator,
bounded independently of the output clamp instead of inheriting whatever
headroom the clamp happened to leave. It also freezes while the inverter is
not tracking, rather than continuing to wind up against a command nothing is
acting on. `integrator_max_w` (default `0`) governs the bound; `0` means
"follow `max_w`", which is the existing behaviour.
Behaviour is unchanged at the defaults - a 4,928-case equivalence sweep
against the previous control law confirms it decides identically at
`integrator_max_w: 0`.
**TEL-01.** P1 meter ingestion, so a Belgian P1's two unsigned registers
(consumption, injection) no longer need a hand-written signed template
sensor: the subtraction moves into the add-on, done once and tested. Two
transports, chosen with the new `meter_source` option: `ha_dsmr` subscribes
to the DSMR integration over the HA WebSocket, `mqtt_p1` reads a topic.
Defaults to `off`, which keeps the existing `meter_entity` path untouched -
nothing changes for an install that does not opt in.
Enabling it publishes `sensor.p1_sample_age_s`: seconds since the newest
accepted telegram, recomputed against the clock and republished roughly once
a second rather than only when a telegram lands. That is deliberate - Home
Assistant only pushes a state on change, so a meter sitting at a genuinely
constant reading would otherwise look identical to a dead one. Watching the
age instead means a frozen meter shows a climbing age, not a flat line. The
firmware watchdog subscribes to this exact entity id.
Known limits, both already in DOCS.md: on `mqtt_p1`, a bridge stuck
republishing its last telegram still "arrives", so the age cannot detect
that particular failure - prefer `ha_dsmr` where both are available. And a
dead P1 meter takes 45 s to reach 0 W commanded (30 s for `meter_max_age_s`
to call the reading stale, then 15 s of `stale_input_s` on top), which is
`meter_max_age_s` and `stale_input_s` stacking, not either one alone.
## 0.2.1
`target_grid_w` (default -10 W): what the meter should rest at. The deadband
holds any resting point inside it indefinitely, and the meter bills import and
export on separate registers, so resting at +14 W import costs 0.34 kWh/day
with the loop behaving perfectly. Biasing the target slightly negative moves
that residue onto the export register. Configurable in the Configuration tab;
see DOCS.md for the trade-off table.
Behaviour is unchanged at `target_grid_w: 0`.
## 0.2.0
Precedence between strategies is now a first-class object instead of an if/else
ladder, ahead of there being more than three of them.
Every strategy returns a CLAIM each cycle - `set` ("I want X") or `limit` ("the
result must stay within these bounds") - and `arbiter.py` resolves them by one
rule:
1. Highest-priority `set` wins; no claim at all means 0 W.
2. Then every `limit` whose priority is >= that set's priority applies, most
restrictive first.
3. Contradictory limits are a BUG: command 0 W and say so.
Clause 2 is why "money outranks maintenance" is now a consequence of the
priorities rather than a special case in a Jinja template: the maintenance
charge-only limit binds the loop, but will not bind a higher-priority peak
shaving claim when one exists.
- Maintenance shaping (charge-only, cheap-window floor) moved out of the control
law. `control.py` is once again only a controller that tracks the meter.
- The loop computes from the ARBITER's last output, not its own last wish. If
something outranked it, that is what the hardware actually did, and tracking
anything else makes it jump when it regains control.
- Every decision is explainable: "loop -> 0 W, limited by maintenance
(charge-only)" now appears in the UI and the log, instead of a bare number.
- Safety limits (device rating, supervised max_w) bind every strategy including
the highest, and are still enforced a second time at the point of writing.
## 0.1.6
Findings from installing this on a live system, replacing a working YAML
implementation. Every one of these was silent - the add-on looked healthy while
being completely unable to do its job.
- **`run.sh` must use `#!/usr/bin/with-contenv sh`.** The HA base images run
s6-overlay, which starts services with a SANITISED environment. With a plain
shebang, SUPERVISOR_TOKEN is simply absent and every Home Assistant call
returns 401 - while `homeassistant_api: true` makes the permissions look
correctly granted. Startup now logs the token length and probes the Core API,
so the next person sees it in one line.
- **Bump `version:` for every change.** Supervisor keys the built image by
version, so editing source and rebuilding silently reuses the old image. Two
fixes appeared not to work because of this.
- **Dependencies come from apk, not pip.** Alpine is musl and there are no musl
wheels for aiohttp; pip would compile it on the client's Pi.
- **paho-mqtt 1.x and 2.x are both supported.** Alpine ships 1.x, which has no
`CallbackAPIVersion`; that raised and took the whole add-on down with it.
- **MQTT can no longer take down control.** Publisher construction is wrapped -
observability must never stop the controller.
- **MQTT discovery is published from `on_connect`.** paho drops QoS-0 publishes
issued before the CONNACK, so announcing straight after `connect()` published
nothing at all while logging "MQTT connected".
- **Repeated failures log at most once a minute.** The control loop retries every
second; unthrottled warnings rolled the log buffer and destroyed the startup
diagnostics needed to debug the 401 above.
- **`auto_start` works.** The store's defaults supplied `auto: False`, so the
fallback to the option could never fire.
Known issue: after deleting the MQTT entities from the registry during
development, Home Assistant would not re-adopt them from retained discovery -
not even after clearing the retained topics and reconnecting. The add-on
publishes correct discovery and live state (verified on the broker); this is an
HA-side adoption problem and affects status entities only, never control.
## 0.1.0
First packaged release. Ports the control loop and the monthly maintenance
cycle from the reference Home Assistant implementation into an add-on.
- Grid-following control: gain/slew/clamp/deadband with anti-windup, all tuned
against measured hardware behaviour (see FIELD-GUIDE.md §14).
- Saturation freeze **with the duration term** — three consecutive diverging
cycles, not one. The instantaneous test fires on every large correction,
because the plant itself needs 3-6 s to settle.
- Monthly maintenance cycle as an ownership state machine: drain / charge /
hold, with exactly one writer of the setpoint at any moment.
- Capacity-tariff awareness: the maintenance charge is capped by quarter-hour
peak headroom, and peak shaving outranks the maintenance schedule.
- Failsafe behaviour: commands 0 W on missing inputs, on stop, and on shutdown.
Never replays a stale setpoint - the reference implementation did, and the
hardware watchdog cannot catch that.
- Ingress UI with a commissioning checklist that names problems in words.
- Optional MQTT discovery for status entities.
Known limits:
- Home Assistant OS / Supervised only (add-ons cannot run on Container/Core).
- The inverter protocol is reverse-engineered; no vendor contract.
- Without the optional RS485 e-stop, nothing covers the host machine dying.