Files
goodwe-addon/goodwe_controller/DECISIONS/OPT-11-battery-modes.md
T
Claude review c38dd1e969
checks / unit (pull_request) Failing after 3s
infra-pin / fresh (pull_request) Successful in 1s
OPT-15 review: bound unmeasured charge stops, test the hold's rules and M15
- A second unmeasured-headroom stop in a quarter latches the charge: a
  headroom missing every other cycle flipped it 1799 times in 30 min.
- Unit test of the run-edge hold's end conditions and of a small step.
- Outside its probe a refuser does not make the others rest (M15 red).
- DECISIONS: one review line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-29 22:31:52 +02:00

114 lines
7.7 KiB
Markdown

# OPT-11 - battery modes, per battery
A battery's mode (on/off, Solar first, Leftover solar) is a soft unit limit at
`P_MODE` = 35 that always holds 0 W. A SET above 35 (a safety stop) overrides
it; a limit above 35 (the peak guard) makes it give way only as far as that
limit needs, and a battery its mode holds back then carries only what the
others cannot (`arbiter._unit_modes()`, `_site_mode()`). Design and owner answers: `goodwe-session/OPT-11-design.md` (2026-09-27);
P1 is its section 6 P1, and the pull request lists what was measured.
- Off by default (`battery_modes_enabled`); off, commands are byte-identical to
a5dddad (`test_modes.py` part 1).
- Off is a mode range, so the peak guard can still use an Off battery when the
others cannot cover the floor (design sections 2-3). Whether Off should be
absolute is an open owner question.
- Review (PR #149): releasing only when the peak floor bound S let a trade won
above the floor keep the modes and place less than the floor, and let a
capped grid charge release an Off battery. Both are graded in
`test_arbiter.py` part 11. The loop bound leaves a side that reaches the
rail to the rail, so SAFETY-03 still flags a loop winding into it.
- P2 (HA entities): a select and a switch per battery, only while modes are
on; commands go through `handle_action()`, the page's path. A retained
command is dropped, not applied: the store already holds the last choice,
and a replay after a restart could otherwise undo a newer one. The config
topics announced are kept in the store (`mqtt_mode_configs`), so turning
modes off removes exactly those, and an install that never turned them on
publishes what ed739d4 did (`test_mqtt.py` part 10). A removed topic stays
in that list and its empty config is re-sent on each start, so a start with
no broker cannot lose it; re-sending is harmless. The HA options are the
page's English names, pinned by a test, and are not renamed with the page:
automations send them.
- In P1 only Off closes a direction; Leftover solar differs by charging last.
- P3 (price runs, `priceruns.py`, `modetrade.py`): each battery's range is
narrowed by its role this tick (hold, give, charge, rest, sell); main.py
files the intersection with the switch, so it still holds 0 W. With modes on
the site trade is filed by the modes, sized from the loop bound (so no
battery a mode or a refusal holds is asked for watts, P1's unmet share) and
the guard's headroom; `arbitrage.decide()` runs only with modes off, which
stays byte-identical to 7a00f12 (`test_modes_p3.py` part 1).
- SAFETY-46 item 2 is decided as the owner answered (2026-09-25): a trade is
a run of consecutive firm slots. It applies with battery modes on; the
modes-off trade keeps its one-period shape, because that path must not move.
- Choices that were measured, not assumed (tools/opt11p3_replay.py):
- a sale needs the guard to have measured the quarter, not to be clear: a
5 kW discharge alone reads "engaged" on export and flipped the sale every
5 s;
- a grid charge makes the others rest, so it starts only at 500 W and, once
the guard or the headroom stops it, stays off for that 15-minute period
(without: 13 flips in 4 minutes under a 3.5 kW house);
- stored energy is valued at the last cheap run for 12 h, and a charge
needs its own run to clear the spread (without: a night charge was spent
on flat morning prices, then charging went on at them);
- a run edge reseeds the loop at the house's level (a 3 kW import spike
removed) and, since OPT-15, holds it there until the meter shows the step.
- Replay (tools/opt11p3_replay.py, 16 recorded days, EPEX hourly prices a
year earlier, modelled batteries), net EUR, lower is better: P2 19.33, P3
Solar first + Leftover solar 19.57, with a sale 19.60, the old one-period
trade 18.14. Review of #153 (same model, with a per-action split):
- the cheapest hours were at midday on 15 of 16 days, so Leftover solar (acting
as Cheap hours until P4) bought 12.2 kWh there that the sun would have
given: 7 kWh more exported, 12 kWh less solar stored. Holding for the
expensive hours saved 4 kWh of import, not enough. With no grid charge on
Leftover solar: 19.44;
- the old trade charged one hour, so the afternoon sun still fit;
- a sale earned the wholesale price (2.27 EUR for 11.4 kWh) and the house
then bought the same energy back (2.29 EUR): a wash before wear. It pays
only when the sale hour's wholesale price beats the later import price,
levies included (about 0.13 EUR/kWh above that hour's wholesale here);
- valuing the charge left at the end, wear and real Flemish levies make
selling worse and do not change the order.
- Owner decision 2026-09-29 (option A): selling is off until it can be judged
on the price the grid pays (`packmode.SELLING_ENABLED`, code kept), and
Leftover solar takes solar only until P4's forecast
(`packmode.GRID_CHARGE_MODES`); Cheap hours only still charges from the grid. Replayed
(16 days, as above): Solar first + Leftover solar 19.44 EUR net against
P2's 19.33; Solar first + Cheap hours only 19.57.
- Not done in P3: the forecast (P4), and a headroom too short for the run
moving the rest to the next cheap periods.
- OPT-15 (TEST-23 findings on 5a4cdc2, `test_price_run_fixes.py`):
- F1, a charge stopped at a quarter edge and latched for the quarter. The
P1 averager opens a quarter only when a sample arrives, and the HA source
builds one 0.35 s after the reading, so the cycle on the boundary still
saw the old block: "no seconds left", headroom None, "no trade
(headroom)", latched for the new quarter. With modes on the guard now
projects the quarter `now` is in (`PeakTracker.project(roll=True)`,
crediting the held sample as the averager will), and only a measured
stop latches. Modes off still reads the old block (identity).
- F2, -1120 W export at a charge end against -257 W modelled. The replay
acted every 5 s on readings of that instant, and by then the lagged
battery had nearly arrived, so it never acted on a reading that still
showed the trade. The add-on cycles on each meter update (1 s on the rig)
on readings 1-2 s old: the two cycles after the reseed saw the trade's
+3300 W and slewed E up 555 W each. The loop now holds E until the meter
reaches the target (or `EDGE_HOLD_S`, 18 s; to 36 s while the battery
still moves). The replay gained `Lag` (dead time, reading age, the P1
debounce, 1 s cycles). Charge end, 800 W house: -10 to -51 W over eight
lag variants; without the hold -1370 W (meter 2 s).
- F3, a charge refusal in a cheap run was never probed: the SAFETY-73 pin
stands only while the site asks that way, and nothing asked to charge.
Probing was chosen over changing the card: the probe is 200 W for 34 s
each 15 min under the same peak gates, and it wins back the run. In its
probe window the refusing battery is a charger, pinned at 200 W by its
own claim, and the others rest. At one inverter SAFETY-52 already ends a
charge refusal as soon as the house asks for power.
- Not fixed, same on 5a4cdc2: with lagged readings a headroom-sized quarter
banks up to 1.4 W over the aim (48.6 W under the cap), and a battery
reading older than the meter can make a charge start look like a house
over the aim, a real guard stop.
- Review: an unmeasured stop that never latched let a headroom missing
every other cycle flip the charge 1799 times in 30 min, so the second one
in a quarter latches (at most 4 changes a quarter). House steps of +3 and
+5 kW during the hold, N=1 and 2: the peak guard's floor ends the hold at
once, and no banked quarter differs from the loop without the hold by
more than +33 W (1342 W, far under the aim).