glenn schrooyenandClaude Opus 5 c040aac4b8 SAFETY-03: alarm when a computed setpoint exceeds the rating, do not just clip it
The clamp was never the missing half. specs.md 10.3 records an unclamped
integrator climbing ~130 W per 4 s past 10 kW and reporting 14 768 W pinned at
the 5 kW rail; clipped silently that is a flat, legal-looking 5000 W hold and
nothing says the loop asked for three times it.

write_setpoint() - the one path every write takes - now clamps to the VALIDATED
max_w and reports whether the raw value differed; check_output_clamp() raises
OUTPUT_CLAMP as a notification, an ERROR, an event row and a red status banner.
Not a trip: the clamped value is written and the loop keeps running.

The rating is max_w and nothing is min()ed at runtime - CFG-01 already refuses a
max_w outside the device range at startup. The device range is applied second as
defence in depth; it cannot bite after a successful validation, so if it ever
does it alarms too and names the bound. No new config key.

Decision grew i_clamped / clamped booleans, and that is the load-bearing part:
`reason` is one string that slew-limiting and the saturation freeze overwrite,
so an alarm keyed on it is silent on exactly the cycles a winding loop produces.
Mutating main.py back onto the string drops the 10.3 replay from 2 engagements
to 0.

Distinct from saturation by construction - no shared reason code, notification
id, status row or counter - and checked in the negative, after first asserting
the saturation freeze really did engage.

Two things found by running it rather than by reading it: a row per engagement
flushed the 40-row event log and evicted SAFETY-18's own METER FROZEN? row (now
coalesced per episode with an exact count), and a naive clamp turns a nan into a
command at the full rating because every comparison against nan is False.

test_clamp.py is new: assert-based, no framework. Six author mutations
reproduced red, including "clamp kept, alarm deleted". Two of the check's own
hypotheses about the freeze/clamp interaction were refused by its sweep and
rewritten to what it measured.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
2026-08-30 15:22:22 +02:00

GoodWe RS485 Controller — Home Assistant add-on repository

Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.

repository.yaml            add-on repository metadata
goodwe_controller/         the add-on
  config.yaml              manifest + options schema (the per-site config form)
  app/                     the controller
    control.py             the control law — pure functions, no I/O
    maintenance.py         the monthly cycle state machine
    hass.py                Supervisor/Core API access
    store.py               persistent state in /data
    mqtt.py                optional status entities
    web.py                 ingress UI
    main.py                orchestration, heartbeat, failsafe behaviour
  test_control.py          runnable checks — no framework needed
  test_maintenance.py      runnable checks — walks a full cycle in fake time
  DOCS.md                  the add-on's documentation tab
firmware/goodwe-master.yaml  ESPHome config for the T-CAN485
estop/rs485_log.py           optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf  the guide techs carry (10pp, A4)
docs/build_guide.py          its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md             how to edit and rebuild the guide

Picking this up after a break? Read HANDOVER.md first — current state, what is known broken, and what to do next.

Install

Settings → Add-ons → Add-on store → ⋮ → Repositories → add

https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon

then install GoodWe RS485 Controller.

⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it anonymously; against a private repo the store shows nothing and gives no useful error. If it must stay private, install locally instead: copy goodwe_controller/ into the machine's /addons/ folder, then ha store reload — it appears as a Local add-on.

⚠️ Bump version: in goodwe_controller/config.yaml for every change. Supervisor keys the built image by that version, so without a bump it silently reuses the old image and your fix appears not to work — on your bench and on every client's machine.

Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.

Read this first

The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.

Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:

  1. ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
  2. Wind-down before firmware updates — 0 W written before the update starts.
  3. RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.

Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md §10 signed.

Development

The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:

cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py

Both must pass before shipping any change. They are not unit-test theatre — each assertion corresponds to a rule whose absence produced an observed failure on real hardware, and the comments in control.py say which.

Compatibility

Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:

tag platform verdict
ESU EMU ESA BPS BPU EMJ IJL 105 — ES/EM/BP, AA55-era meter bus supported
SPB SPN 745 — SBP G2 (GW…-SBP-20) no
ESN ESC 745 — ES G2 (GW…-ES-20) no
ETU EHU BTU … 205/745/753 — ET/EH/BT hybrids no
SDT DST MSU NSU … PV-only inverters — no battery to control no

A "-20" or "G2" suffix means a different platform with a different meter protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which is also what Home Assistant's own integration uses to pick a protocol.

  • GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
  • The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.
S
Description
No description provided
Readme
18 MiB
Languages
Python 98.1%
JavaScript 1.2%
CSS 0.3%
Shell 0.2%
HTML 0.2%