glenn schrooyenandClaude Opus 5 8d83ef0dfb
checks / unit (pull_request) Successful in 6m11s
OPT-09: the weights DO move on a wedged unit, and that narrows SAFETY-42
B1, the blocking review finding. §5 of the decision said:

    "A wedged unit reads a healthy SoC, so no envelope closes and no weight
     moves - OPT-09 cannot see it at all."

The first clause is true and is about the ENVELOPE. The second clause is
FALSE, and it was load-bearing for the claim that OPT-09 and SAFETY-42 meet
without overlapping. A weight is a function of a pack's ENERGY HEADROOM, not
of what the pack delivers, so a wedged unit's weight moves whenever its
headroom differs from its sibling's - the ordinary case this card exists to
exploit. And delivery.delinquent() (app/delivery.py:484, threshold at :531)
names a unit only while its short_by() gap exceeds min_w = Tuning.saturation_w
= 500 W in ABSOLUTE WATTS. Shrinking the share shrinks the gap below the
threshold, and the alarm stops firing on a unit still delivering nothing.

So the seam, stated accurately: OPT-09 stops the ask AND narrows SAFETY-42's
detection window for a low-headroom unit. That is a DETECTION REGRESSION at
N=2. It is disclosed here, not fixed: making delinquent() relative to the ask
rather than absolute is SAFETY-42's code and a design change, filed as its own
card.

1. THE CORRECTION, in the three places that carried the claim

   * DECISIONS/OPT-09-soc-aware-weights.md §5 - rewritten. States the seam
     accurately, quotes the sentence it is replacing, carries the measured
     rows and the window arithmetic, and names the residual in the same voice
     as SAFETY-13's "2 of 272" and SAFETY-42's "the discriminator does not
     exist". Also drops "they meet and do not overlap" from the opening.
   * app/packshare.py - a new section in the module docstring, immediately
     after "weights are a comfort choice for stability and not for delivery",
     which is where the over-read starts.
   * CHANGELOG.md - a new paragraph in the SAFETY-42 entry, ending on the
     operator-facing sentence: a wedged inverter with less energy headroom
     than its sibling can now go unreported at ordinary house loads.

   test_packshare.py part 8's closing check and its "what this file cannot
   see" list repeated the same false clause; both now say the ENVELOPE cannot
   reach a wedged unit and point at part 8b for what the WEIGHTS do to it.

2. THE GRADED CHECK - test_packshare.py part 8b, 6 named checks

   The reviewer's probe, reproduced: real compute(), real plan(), real
   packshare.weights(), real delivery.account(), real delivery.delinquent();
   the only model is the plant (A obeys within one cycle inside its rating,
   B accepts its share and delivers 0 W). Unit B is WEDGED at 15 % against
   its own 10 % floor, so envelope() does not close and account() explains
   nothing - a SAFETY-42 true positive by that card's own definition, which
   a PRECONDITION check asserts before anything is concluded from it.

       load 1500 W, B wedged at 15 %, equal weights  named on 199/200 cycles,
         site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
       load 1500 W, B wedged at 15 %, OPT-09 weights named on   0/200 cycles,
         site target +1630 W, shares a+1505, b+125,  grid -5 W, named=(nobody)
       load 6000 W, B wedged at 15 %, equal weights  named on 199/200 cycles
       load 6000 W, B wedged at 15 %, OPT-09 weights named on 195/200 cycles

       suppression window: equal weights, site target < 1000 W; OPT-09
       weights, site target < 6500 W of a 9600 W site

   THE CHECKS ASSERT THE CURRENT, UNFLATTERING BEHAVIOUR ON PURPOSE - that
   the weighted arm names NOBODY where the equal arm names the wedged unit.
   A check asserting the alarm still fires would fail, and papering over it
   would be worse than the original defect. The 6000 W row is there so the
   part is not pinning "the weighted arm never names anybody": past the
   healthy pack's own rating, _fill()'s last-resort pass hands the wedged
   unit 3000 W and both arms name it. The window is real and it has an edge.

   MUTATION - packshare.weights() keeps its shape and forces every weight to
   1.0 (M11 in part 11's table, which now has 11 rows). RUN on a purged tree
   with python3 -B, not reasoned about:

       load 1500 W, B wedged at 15 %, equal weights  named on 199/200 cycles,
         site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
       load 1500 W, B wedged at 15 %, OPT-09 weights named on 199/200 cycles,
         site target +3000 W, shares a+1500, b+1500, grid +0 W, named=[b]
       load 6000 W, B wedged at 15 %, OPT-09 weights named on 199/200 cycles,
         site target +4000 W, shares a+2000, b+2000, grid +4000 W, named=[b]
       suppression window: equal weights < 1000 W; OPT-09 weights < 1000 W

     FAIL  AND WITH OPT-09's WEIGHTS IT IS NAMED ON NONE OF THE 200 [...]
     FAIL  ...and the arithmetic behind it, stated as a window [...]
     FAIL  AND IT IS NOT THAT THE WEIGHTED ARM NEVER NAMES ANYBODY [...]

   test_packshare.py exits 1. Restored: exits 0.

3. THREE PROC-01 PROSE DEFECTS

   * DECISIONS/OPT-09-soc-aware-weights.md:3 said "Base: release/1.0 @
     464d398". The branch was rebased; git merge-base HEAD 3368231 is
     3368231. Corrected, and it says why the old number was there.
   * Same file:13 cited main.py:2272 for "resolution = resolve(...)".
     git show 3368231:goodwe_controller/app/main.py | grep -n says 2422.
     Corrected. The sibling citation arbiter.py:535 is right and is left.
   * DOCS.md:174 said "Since 0.7.x the split is driven by two separate
     things", which tells an operator the fix already shipped. config.yaml
     is 0.8.0 and the live install is 0.7.0, where the split is 50/50 - this
     card's own premise. Now "from 0.8.0 onwards", with an explicit warning
     that 0.7.0 and earlier are a fixed 50/50.

NOT TOUCHED, deliberately: delinquent()'s absolute threshold (SAFETY-42's
code, its own card), and app/main.py:2699's double-logged scope refusal (N4,
filed separately).

INVERTER B DOES NOT EXIST (expected ~2026-09-12). Every two-unit figure above
is TWO COPIES OF A through a plant modelled in test_packshare.py; B's 4600 W /
20.48 kWh / 10 % floor are from the datasheet and the serial. Nothing here was
measured on hardware, and the added disclaimers say so in each place.

Verified with the real harness per .gitea/workflows/checks.yml
(goodwe-addon-checks:1): COLLECTED 24 files, ALLGREEN. Harness positive
control run first - test_validate.py deliberately broken, harness reported
"FAILED: test_validate.py" and exited 1; restored.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-06 22:55:20 +02:00

96 KiB
Raw Blame History

GoodWe RS485 Controller

Drives a GoodWe ES/BP battery inverter over its RS485 meter bus: holds net grid exchange at zero, and runs a monthly battery maintenance cycle so the BMS can balance cells and recalibrate its coulomb counter.

Installers: read FIELD-GUIDE.md in the repository. It is not optional reading — it contains the commissioning gates and the failure modes.

Before you start

You need:

  • A GoodWe ES / BP family inverter (AA55 / RS485 meter-bus generation)
  • The vendor's meter-emulating controller disconnected from the bus
  • A T-CAN485 (ESP32) flashed with firmware/goodwe-master.yaml
  • A grid-power sensor already working in Home Assistant, updating every ~5–10 s

The safety model, in short

The inverter holds its last command forever — it has no meter-timeout. So:

  • The ESP32 commands 0 W if this add-on stops refreshing for ~30 s, and keeps commanding it.
  • This add-on commands 0 W when its inputs go missing, when you stop control, and when it shuts down.
  • This add-on commands 0 W and latches there if what it is commanding and what the meter reads point opposite ways for three minutes — see "The sign-disagreement failsafe" below.
  • The optional RS485 e-stop is the only thing that covers this machine dying. Without it, a failed host leaves the battery latched at its last command until someone intervenes.
  • This add-on raises an alarm — and nothing more — when the meter keeps answering with a reading that never changes while the command sits at the rail. See "The frozen-meter alarm" and, before you rely on it, "Capacity-tariff exposure of the grid-following loop".

If anything looks wrong: stop the add-on. That commands 0 W and the hardware holds it there.

Configuration

⚠️ There are TWO places to configure this add-on (UX-02)

Since UX-02 the ingress panel has a Configuration page of its own, beside Home Assistant's Configuration tab. Both edit the same settings — there is one options blob, and neither surface is a copy of it.

Ingress panel → Configuration Supervisor → Configuration tab
Use it for everyday editing recovery, and when the add-on is down
Sections, units, help real headings, units beside the boxes, the description under each field one flat list of 71 fields, no headings, no units
Tells you a setting is wrong yes — before you save, next to the field no. It knows types and ranges only
Can express a rule spanning two keys yes, because it runs the add-on's own validator no. The schema grammar cannot say "must be at or below max_w"
Available when the add-on is not running no — it is served by the add-on yes
Editing the inverter list cards you add and remove, with the per-entry labels rendered a repeatable section whose per-entry keys render raw on frontend 20250925.1

Which one is authoritative: neither. The stored options blob is, and both are editors of it. DECISIONS/UX-02-two-config-surfaces.md is the record, with the measurements behind it.

The one thing you need to know in practice: the panel refuses to save a configuration the add-on would not start on, and the Configuration tab does not. The tab will happily store maintenance_charge_w: 2500 beside max_w: 2000; the add-on then exits 78 on its next start, the panel goes down with it, and the tab is where you fix it. That asymmetry is the reason both exist.

What the panel does when you press Save

  1. It runs the shipped validator — the same validate_startup_config() and validate_unit_ranges() the add-on runs at startup, not a copy of them — and if anything is refused, nothing is written and your edits stay on screen.
  2. It re-reads the stored blob and refuses if it changed while you were editing — someone in the Configuration tab, or you on another device. It names the keys that moved and shows both values; pressing Save again then writes yours.
  3. It writes the whole blob. It does not restart: POST …/options replaces the stored options, and a key left out would revert to the shipped default, so the panel always sends everything it read.

⚠️ Saving costs nothing. Applying costs a control interruption

Stored settings take effect when the add-on next starts. The panel shows which stored settings are not what the add-on is currently running, and Restart to apply is a separate button with its own confirmation — because the wind-down commands 0 W on every inverter before the process exits, and the battery does nothing until it is back. Nothing else is changed by that restart: a latched sign-disagreement failsafe is restored from the Store on the way back up, not cleared.

Two range checks can be skipped, and the page says so

Two of the refusals compare a configured ceiling against the setpoint device's own reported range, which means asking Home Assistant. If ESPHome has not come up, that range is unknown and those two checks are skipped — on the page and at startup, identically. The page prints a note saying so rather than looking green for a reason you cannot see. If the device answers later and disagrees, the add-on refuses to start then, with the same sentence.

On a phone

One column, big targets, sections collapsed until you open them, and the refusals pinned where you cannot scroll past them. It is the screen for standing in front of the inverter.

What the Configuration tab actually shows you (UX-01)

Since UX-01 the add-on ships translations/en.yaml and translations/nl.yaml, so Home Assistant's Configuration tab renders human labels and a description for every option instead of the raw option keys. What that does and does not buy you is worth stating plainly, because it was measured against the Supervisor image this site runs (ghcr.io/home-assistant/amd64-hassio-supervisor:2026.08.0) rather than assumed — tools/supervisor_shape_probe.py section F prints the whole rendered list, in both languages.

All 71 options are always shown The frontend keeps a field when name in options || required, and every key is in options:. There is no "advanced" fold
Order comes from schema: App.schema_ui is UiOptions(...)(data["schema"]), so the schema half of config.yaml decides the order the tab renders in — not the options: half
There are no section headers Add-on options are a flat list: no header primitive, no per-option advanced flag, no units on the input, no sliders. Grouping is approximated by order plus the Group · prefix in each label, and by nothing else
Groups, in task order Hardware → Meter → Limits → Tariff → Maintenance → Safety → Advanced
The description says whether to touch it A number that was derived names the campaign it came from and says not to change it without re-deriving; a number that is genuinely yours (max_w, peak_cap_w) says "THIS IS YOUR NUMBER"; and cycle_cost_threshold_eur, which is neither, says it is an open product question
Dutch falls back per key translations[your language]?.name || translations["en"]?.name || the raw key. A key missing from nl.yaml degrades to English; a key present but wrong does not degrade at all
⚠️ The per-entry keys inside inverters: still render raw Measured, and negative. A list-of-objects becomes an object selector with multiple: true, and ha-selector-object labels its fields fields[name].label || name — the converter sets no label and no translation_key. The fields: translations are shipped and validated (they are the shape Supervisor's own schema defines) but on frontend 20250925.1 they do not reach the screen. The inverters label and description themselves do

test_translations.py is what stops this rotting: a translation naming an option that does not exist, or an option with no translation, fails CI — in either direction, and the check is mutation-tested both ways.

Sources

option required meaning
meter_entity yes Net grid power. Positive must mean importing
meter_invert Flip the sign if the meter reports the other way
soc_entity yes Battery state of charge — use the ESP32's own read
batt_entity yes Battery power — again the ESP32's read, + = discharging
batt_invert Flip if needed
capacity_kwh This pack's usable capacity. Read only to divide the site target between packs by energy headroom — see below
setpoint_entity yes The ESPHome number.*_goodwe_setpoint_w

Use the ESP32's readings rather than the inverter's cloud or dongle sensors: those serve cached values, and a stale reading here ends the maintenance charge phase having charged nothing.

More than one inverter (inverters)

The six keys above describe one inverter, and if that is your site there is nothing to do here — inverters ships empty and empty means "the flat keys above describe the one inverter". An install that upgrades into 0.6.0 reads identically to before: same entities, same rating, same behaviour, no operator action.

To run two, declare them. Each entry names its own actuator, its own rating and its own sensors:

setpoint_entity: ""          # ⚠️ must be cleared — see below
inverters:
  - name: inverter-a
    setpoint_entity: number.goodwe_a_setpoint_w
    soc_entity: sensor.goodwe_a_soc
    batt_entity: sensor.goodwe_a_battery_power
    max_w: 5000
    capacity_kwh: 15.36
  - name: inverter-b
    setpoint_entity: number.goodwe_b_setpoint_w
    soc_entity: sensor.goodwe_b_soc
    batt_entity: sensor.goodwe_b_battery_power
    max_w: 4600
    capacity_kwh: 20.48

⚠️ The 4600 W is inverter B's datasheet figure, not a measured one. B is a GoodWe GW5048D-ES (serial 55048ESU22AW0992, identified 2026-09-04) whose datasheet gives max charging and discharging power as 4600 W; with nothing connected to its PV inputs the battery path is the ceiling, not the 5000 VA AC nameplate. The datasheet prints that number under Battery Input Data, so it may be a DC figure, while max_w is graded against register 0x0518 — the inverter's own AC power. If it is DC the AC-side ceiling is nearer 4324 W. max_w: 4600 is still the right thing to configure, because the freeze rail is min(max_w, dev_max) and the device range read off the unit is what binds. goodwe/NOTES.md §1.1b records both readings and picks neither.

per-entry key required meaning
name yes Short identifier. It namespaces this unit's SAFETY-02 latch, heartbeat and write bookkeeping in the add-on's state file, so two units may not share one
setpoint_entity yes This inverter's own ESPHome number.*_goodwe_setpoint_w
max_w yes The supervised cap on what may be written to this inverter. The site's ceiling is the sum
soc_entity This pack's state of charge
batt_entity This unit's battery power, + = discharging
batt_invert Flip if needed

⚠️ Nothing is inherited. An entry that leaves out soc_entity has no SoC sensor — it does not fall back to the flat one. That is deliberate: every per-device value became per-instance in 0.5.x precisely so that no inverter is ever graded against a sibling's numbers, and a silent fallback would rebuild that in YAML. name, setpoint_entity and max_w are required of every entry for the same reason: there is no rating to borrow.

⚠️ Clear the flat setpoint_entity when you declare a roster, or the add-on refuses to start and says so. It is the single-inverter form and it is not read once a roster exists, so leaving it set means one of two things: it names an entity an entry also names — two writers on one actuator, which specs §1.5 makes a non-goal and the add-on refuses outright — or it names a different one, which nothing would ever write, leaving a site running quietly smaller than its configuration reads. soc_entity, batt_entity, batt_invert and max_w cannot be blanked (the schema gives them no empty value); they are simply not read, and the add-on writes one line into its action log at every start saying so.

⚠️ Two inverters naming the same setpoint_entity are refused, whichever keys they are declared under and whatever the capitalisation. Two independent setpoints on one inverter is the arbitration problem this add-on exists not to have.

⚠️ Update the add-on first, then add the roster. Home Assistant validates the options you save against the schema of the version that is installed, so inverters cannot be set before 0.6.0 is installed. The order is: update, then configure.

⚠️ Going the other way — downgrading with a roster configured — is recoverable but NOT uneventful, and the add-on will not start until you refill a field. The schema side is fine: the older version's schema has no inverters key, so it drops the key with a warning rather than refusing the whole blob (measured — DECISIONS/CFG-04-inverter-roster.md §E). The add-on side is not. Rule 9(e) requires the flat setpoint_entity be cleared when a roster is declared, so a config that downgrades cleanly is by construction a config whose flat actuator is blank — and the older version has nothing else to write to. It stops at startup validation with a refusal naming setpoint_entity, which is loud and in the log rather than silent, but it is an outage until someone puts the single-inverter entity back in that field. Before downgrading, write down the setpoint_entity of the unit you want to keep running.

How the site target is divided between the packs (OPT-09)

Two packs do not get half each from 0.8.0 onwards. ⚠️ On 0.7.0 and every version before it the split is a fixed 50/50 regardless of what either pack can do — that is the defect this section describes the fix for, so if the add-on you are running reports 0.7.0, none of what follows is happening yet. From 0.8.0 the split is driven by two separate things, and it is worth knowing which is which, because only one of them is a rule:

  • The envelope — a permission. A pack whose own state of charge is at or under its own bms_soc_floor is not asked to discharge; a pack at 100 % is not asked to charge. Its share goes to the sibling, inside that sibling's own rating. This is absolute: the allocator cannot exceed it.
  • The weights — a preference. Between those limits, each pack is asked for the fraction of the site target that matches its energy headroom: the kWh it has above its own cut-out when the site is discharging, the kWh it has below full when the site is charging. That is what capacity_kwh is for.

⚠️ capacity_kwh is optional, and it is all-or-nothing. Leave it out everywhere and the add-on has no opinion about the split — the target is divided evenly, exactly as it was before. Fill it in on every entry or on none: a pack measured in kWh beside one that is not is not a comparison, and the add-on refuses to start rather than ignore half of what you typed.

⚠️ Why energy and not the rating. The two packs here pull in opposite directions — A is 5000 W with 15.36 kWh, B is 4600 W with 20.48 kWh, so B has about a third more energy and about 8 % less power. Dividing by rating hands the work to A; dividing by energy hands it to B. The question a split is answering is "which pack can sustain its share for the hour", so it is the energy one. Each inverter's own rating still binds its own share, separately, through max_w.

⚠️ What the weights will NOT do for you, stated plainly. They are a comfort choice about which pack does the work. They are not a way to make the site deliver. A unit that is at its energy limit — or that has simply stopped responding — does not hand its load to its sibling: the loop sees the shortfall, freezes, and the site runs short by that unit's share. Weighting a failing unit down does not fix that, because when the healthy unit reaches its own rating the allocator hands the remainder to the down-weighted one anyway rather than leave watts unplaced. What you get instead is honesty: the action log reports the watts that could not be placed (ALLOCATOR: +2000 W of the site target could not be placed on any inverter), and a unit that accepts its share and does not produce it is named by the delivery alarm (SAFETY-42, above).

⚠️ At one inverter none of this applies and nothing changed. There is no split to weight, capacity_kwh is not read, and no envelope is closed — self-consumption still discharges down to the battery's own cut-out exactly as it always has.

What appears in Home Assistant at two inverters

Nothing you already have changes. The eight entities this add-on has always published — Setpoint, Grid power, Battery power, Battery SoC, Circulating power, Maintenance phase, Controller status, P1 sample age — keep their device, their unique_ids and therefore their entity ids and their whole recorded history. At a roster of one, nothing new is announced at all: no second device, no renamed entity, not one added topic.

Declare a second inverter and four rows per unit appear beside them:

per-unit row what it is
Setpoint this unit's own share of the site target — the number its heartbeat re-emits
Battery power this unit's own reading, + = discharging
Battery SoC this pack. The site Battery SoC row is the emptiest pack, which may be the other one
Sign latch this unit's SAFETY-02 latch: tripped or clear

⚠️ The devices are deliberately asymmetric, and it is not an oversight. The first inverter's rows are added to the existing GoodWe device; every later inverter gets its own device (GoodWe Inverter B), shown in Home Assistant as connected via the controller. Home Assistant composes an entity id from the device name plus the entity name, so giving the first inverter a device of its own would rename every entity you already have — and because HA keeps the id it composed at first discovery, you would get a new entity beside a dead one: the history stays on the old id and every dashboard, template and automation naming it silently stops updating. The entity ids come out symmetric anyway — sensor.goodwe_inverter_a_battery_power beside sensor.goodwe_inverter_b_battery_power.

Do not rename the device. Not in this add-on, and not in Home Assistant's device page. It is half of every entity id, including sensor.goodwe_p1_sample_age, which the ESP32's stale-input watchdog subscribes to; a rename disarms that guard by leaving it waiting for a state that never arrives, and it fails silently and looks correct.

Grid power and P1 sample age stay site-scoped and are announced once. There is one P1 meter and one grid connection; a per-inverter copy would invent two of a thing there is one of, and P1 sample age is a safety input. Same for Circulating power (it is a property of the set of inverters), the controller status, the maintenance phase and the capacity-tariff peak.

⚠️ Two roster names that differ only in punctuation or case — inverter-b and Inverter B — are two names to the validator and one id once slugged. The add-on gives the second one a _2 suffix so nothing collides, but the ids you get then depend on roster order. Give your inverters plainly different names.

P1 meter ingestion

meter_entity above expects one signed sensor, which usually means a template someone wrote by hand. Setting meter_source moves the whole derivation into the add-on, where it is done once and tested, and replaces meter_entity entirely.

Which mode you want depends on what your P1 reader publishes, and there are two shapes in the wild:

  • Two unsigned registers, consumption and injection, which is what a Belgian P1 read over DSMR gives you → ha_dsmr, or mqtt_p1 for a bridge. The add-on subtracts them.
  • One signed figure, positive = import and negative = export, which is what a HomeWizard P1 gives you (sensor.p1_meter_active_power) → ha_signed. The add-on splits it. ha_dsmr cannot read this: it wants two registers and rejects a negative one outright, which is every exporting telegram.

Either way, do not build the missing shape out of template sensors. The point of meter_source is that the sign convention is derived in one tested place rather than in YAML nobody reviews underneath a safety input.

✅ If your meter is a HomeWizard P1, use homewizard_local, not ha_signed. It reads the same meter and produces the same numbers, but it polls the meter directly instead of watching a Home Assistant entity — and that is the difference between an age sensor a watchdog can threshold and one it cannot. See "sensor.p1_sample_age_s" below; ha_signed remains for installs where the meter is only reachable through Home Assistant.

⚠️ ha_dsmr and mqtt_p1 have never processed a telegram from real hardware. No meter in this installation uses either one. Both were written to the assumption in specs.md §5.2 that a Belgian P1 exposes two unsigned registers, and the meter actually fitted here does not — it is the HomeWizard P1 that ha_signed reads. They are covered by the unit checks in test_p1.py and by an end-to-end test against a fake Home Assistant, and nothing more.

This is recorded because the realistic way it bites is someone debugging a meter problem months from now treating those two paths as proven and looking for the fault elsewhere. If you are the first person to point one at a real meter, expect to find something, and please update this note when you do.

option default meaning
meter_source off off keeps meter_entity. ha_dsmr subscribes to the DSMR integration over the HA WebSocket; mqtt_p1 reads a topic; ha_signed subscribes to one signed entity over the HA WebSocket; homewizard_local polls a HomeWizard P1's own local API, bypassing Home Assistant
meter_phases 1 1 or 3. Must match the telegram, or every telegram is rejected and logged
meter_max_age_s 30 Beyond this the reading is stale and grid power reads as missing. On its own it does not command 0 W — see the timing note below. It is also the longest a reading is held forward into the 15-minute average
meter_poll_s 5 homewizard_local only. Seconds between polls. Must be well under meter_max_age_s — see below
p1_host homewizard_local only. The meter's own address, host or host:port (e.g. 192.168.2.250)
meter_mqtt_topic mqtt_p1 only
p1_import_entity The unsigned consumption sensor. Do not point this at a signed template
p1_export_entity The unsigned injection sensor
p1_phase_import_entities [] L1..L3, in order. Needed for the capacity-tariff peak on a three-phase connection
p1_phase_export_entities [] L1..L3, in order
p1_net_entity ha_signed only. The signed net-power sensor: + import, - export
p1_phase_net_entities [] ha_signed only. L1..L3, in order, each signed the same way. Needed for the capacity-tariff peak on a three-phase connection. The list length must equal meter_phases

Both per-phase lists are checked against meter_phases once at startup: a list of the wrong length disables P1 ingestion with an error in the log, rather than letting every telegram fail its phase-count check one at a time. Leaving the list empty is fine and is not an error — you simply get no per-phase figures, and therefore no capacity-tariff peak. On a three-phase connection that is a much bigger omission than it looks: on a surveyed reading here the phases carried 2769 W of import while the connection netted 187 W, so the billed quantity is understated roughly fifteenfold if the phases are missing.

How long a dead meter takes to reach 0 W

meter_max_age_s and stale_input_s stack. They are two different clocks and neither one is the whole answer:

step option default
telegrams stop, P1 sample goes stale, grid power starts reading missing meter_max_age_s 30 s
inputs have been missing long enough for the loop to command 0 W stale_input_s 15 s
total, meter death → 0 W commanded by this add-on 45 s

So in P1 mode stale_input_s is not "how long inputs may be missing before commanding 0 W" measured from the meter dying — it is measured from the moment the P1 sample already went stale. Size the pair together: the ESP32's own watchdog commands 0 W after ~30 s of silence from this add-on regardless, and that layer is unaffected by either option.

How long a FROZEN inverter power register takes to reach 0 W

A third clock, and it is a different failure from the one above: the entity is still there and still answering — it has simply stopped changing. Before SAFETY-37 that read as a healthy measurement for ever, which is what happened on 2026-09-02 (HW-01): a value held for 6 h 25 m while the pack drained to its floor, and every detector read healthy throughout.

Inverter.batt — the inverter's own AC power, register 0x0518 — is now withheld from the control path when all three of these are true:

the reading has not changed for 35 s
and the command standing on that inverter is over 250 W
and that command has travelled, since the reading last moved, over 250 W

All three, because a converged site legitimately repeats one power figure for minutes — measured at up to 263 s over 30 days of this house's own meter — and a site at rest is not owed movement. It is only when the controller has asked the inverter to move and the register has not answered that the reading is treated as missing.

A withheld reading is a MISSING INPUT, so it joins the stale_input_s clock above: 35 s to withhold, then 15 s of hold, then 0 W. It clears itself the instant the register reports a different value — one watt is enough, and this register dithers ±1 W while holding — so a working inverter clears it on its next 10 s publish. There is no option to configure: the 35 s is derived from the ESPHome publish interval and the two watchdog windows it has to stay inside, and the add-on's own checks refuse a value that does not.

⚠️ What this does NOT catch: a register whose value is WRONG rather than STOPPED, including a dead publisher whose last two samples happen to alternate. Detecting that needs an arrival stamp inside the ESP32 firmware itself, which is TEL-06.

There is no fallback to an inverter-side power figure, deliberately. The inverter's own AC power tracks its battery almost perfectly and the real meter hardly at all, so a controller that failed over to it would be regulating against its own output while looking healthy.

The mqtt_p1 payload is one JSON object per telegram, and the schema is strict — a key it does not recognise is a telegram from something other than what was tested, and guessing a key here means guessing a kilowatt:

{"import_w": 1234.0,
 "export_w": 0.0,
 "phases": [{"import_w": 500, "export_w": 0},
            {"import_w": 400, "export_w": 0},
            {"import_w": 334, "export_w": 0}],
 "timestamp": "2026-08-24T18:00:05+02:00"}

phases and timestamp are optional; timestamp must carry a UTC offset. Where it is present it is used for the age, which is what stops a retained message replayed on reconnect from presenting a ten-minute-old reading as current.

homewizard_local — polling the meter instead of Home Assistant

Set p1_host to the meter's address and the add-on does GET /api/v1/data on it every meter_poll_s seconds, reading active_power_w (signed, same convention as ha_signed) and the three active_power_l{1,2,3}_w fields. Home Assistant is not involved: no entity, no WebSocket, no integration to mis-configure. Per-phase figures are used only when the meter serves all meter_phases of them — a single-phase meter returns null for L2/L3, and the connection-level reading is still accepted on its own.

Why this mode exists: every HTTP response is an arrival. The meter answered, now, with its current reading — whether or not the number moved. That is the signal sensor.p1_sample_age_s needs and the one Home Assistant cannot give it at all (see the note below). It is also simply fewer moving parts: the five-second cadence is the meter's own, rather than an integration's polling of it re-published as a state change.

Cadence. The age is never fresher than the poll interval, so:

meter's own update rate ~5.0 s (measured 4.97 s)
meter_poll_s default 5 s — nothing to gain below the meter's own rate
meter_max_age_s default 30 s, i.e. six polls of headroom
meter_poll_s >= meter_max_age_s refused at startup — every reading would be stale before its successor arrived
meter_poll_s > meter_max_age_s / 2 warned — one missed poll makes the reading stale

A failed poll — timeout, connection refused, non-200, unparseable body — is a missing reading. It submits nothing, so the reading does not become 0 W, the last good value and its timestamp are left alone, and the age goes on climbing. That is exactly what a dead meter should look like.

What it still cannot see: a frozen meter. A meter that answers 200 OK forever with a stale number is arriving, so no arrival detector — this one included — can tell it from a healthy one. The local API does expose the raw material the HA path never had (the total_power_*_kwh registers stop advancing), and the transport tracks it as unchanged_s, but it is deliberately not folded into the age and not thresholded: this controller regulates grid power toward ~0 W, and at a converged −10 W the export register needs six minutes to move by its 1 Wh resolution while the power figure legitimately repeats. Thresholding that at 30 s would rebuild the false-trip limit cycle at the exact operating point the controller aims for. Freeze detection is a separate problem and needs the low-power case solved first.

You read it yourself instead: the add-on's status page shows it on the P1 line, as … 4 rejected, measurement unchanged for 312 s. On a house drawing real power that figure stays in the seconds; minutes of it while the load is clearly not near zero is the meter to go and look at.

sensor.p1_sample_age_s

Published over MQTT discovery whenever a broker is available: seconds since the newest accepted telegram, refreshed every second rather than only when a telegram lands. The ESP32's stale-input watchdog subscribes to this exact entity id, so do not rename it.

The reason it is recomputed against the clock is that Home Assistant only pushes a state when the state changes. A meter sitting at a genuinely constant reading emits nothing, which is indistinguishable — to anything watching the value — from a meter that has died. Watching the age instead separates the two: it climbs when telegrams stop and resets when they arrive, whatever the reading says.

The entity is only created when meter_source is not off. With P1 ingestion disabled there is nothing feeding it, and an age sensor climbing with no ingester behind it would trip the firmware watchdog on a system that is working fine.

Known limit, mqtt_p1. The age measures arrival. On the MQTT path a bridge that is stuck republishing its last telegram keeps arriving, so the age stays near zero and a frozen meter still looks fresh. Detecting that needs a change-detector rather than an arrival-detector, and it is not in this version.

⚠️ Known limit, ha_signed — do not drive a watchdog off this age yet. On the HA WebSocket paths the age is stamped when a state_changed arrives, which means it measures time since the value last changed, not time since the meter last reported. Home Assistant offers nothing better: a repeated reading produces no state_changed, does not advance last_reported on either the REST or the WebSocket serialiser, and state_reported cannot be subscribed to over the WebSocket at all (Event filter is required for event state_reported). All three measured on the ENV-01 rig against the real HomeWizard integration with the meter frozen: 0 state_changed in 70 s and no timestamp movement anywhere.

ha_dsmr mostly escapes this because a DSMR telegram updates several entities and something in the set almost always moves. ha_signed has exactly one entity, so a healthy meter under a flat load is indistinguishable from a dead one. This is not hypothetical: in our own captures (sim/scenarios/ha-p1_meter_active_power-2026-08-20.json) the real house meter went 42.2 s and 97.0 s between changes, and 23 Aug peaks at 29.1 s — all past the default meter_max_age_s of 30.

So sensor.p1_sample_age_s on ha_signed is safe to read, and it is correct whenever the value is moving, but it must not yet be thresholded by the ESP32 stale-input watchdog: a quiet house would trip the battery to 0 W. Raising meter_max_age_s is not the fix — the two conditions produce an identical signal, so a bigger number only chooses which of the two errors you get. The real fix is an arrival stamp the meter itself provides — and that now exists: meter_source: homewizard_local. If you have a HomeWizard P1, switch to it. If your meter is only reachable through Home Assistant, this limit still applies to you and the watchdog threshold still must not be armed.

Where the age is trustworthy:

mode the age measures safe to threshold from firmware
homewizard_local time since the meter answered yes — every HTTP response is an arrival
ha_dsmr time since one of several entities changed no — statistically usually fine, which is a masked bug, not an absent one
ha_signed time since the one entity changed no — see above
mqtt_p1 time since a message arrived arrivals yes, but a stuck bridge republishing keeps arriving

Control

option default meaning
max_w 2000 Hard limit on what may be commanded. Start low, raise after commissioning. Not read when inverters is declared — each entry carries its own, and the site ceiling is their sum
gain 0.6 Correction per cycle. At the limit — do not raise
slew_w 0 Largest change in one cycle. 0 means follow the rail - max_w / 9, i.e. the loop takes the plant's own measured ~18 s settling time to cross its whole output range at the 2 s tick the live install runs. 222 W at max_w: 2000, 556 W at 5000, 1067 W at a ~9600 W two-inverter site. A fixed number is accepted and never silently reduced, but one FASTER than the rail implies is refused at startup (SAFETY-39): slew_w: 1000 against max_w: 5000 crossed the rail in 10 s against an 18 s plant, and on 2026-09-05 drove the meter from 3.4 kW of export to 2.8 kW of import
deadband_w 15 Ignore errors smaller than this
target_grid_w -10 What the meter should rest at. Negative = a slight export
step_w 10 Quantisation
saturation_w 500 Divergence that counts as "the inverter is at a limit"
saturation_cycles 3 How many consecutive cycles before freezing. A cycle is one meter update or cycle_floor_s, whichever comes first - see the note below. Do not set to 1. Every value this file accepts (1-10) is below the freeze's own release bound of 12 cycles, so no accepted setting can stop the block engaging - see SAFETY-13, below
integrator_max_w 0 Bound on the loop's accumulator, and 0 means "same as max_w". Caps how much stale error can be waiting to unwind when the sign flips. Do not raise it above max_w - the output clamp already bounds what is commanded, so the only thing extra headroom buys is more cycles of wrong-direction power after every saturation event. Lowering it below max_w is the useful direction
heartbeat_s 10 Refresh interval; must stay well under the firmware watchdog
cycle_floor_s 15 The longest the loop may go without evaluating. A deadline on the gap between cycles, reset by every cycle — on a healthy meter it never elapses and changes nothing. Raise it only if your meter is slower than ~10 s; it must stay under meter_max_age_s, past which there is no reading to evaluate anyway
stale_input_s 15 How long inputs may be missing before commanding 0 W. In P1 mode this clock starts only after meter_max_age_s has already expired — the two stack, see "How long a dead meter takes to reach 0 W"
auto_start false Start controlling on boot (only after commissioning)
sign_disagree_w 300 Both the command and the meter must exceed this before a sign difference counts. Must stay below max_w or the watchdog can never fire, and the add-on refuses to start
sign_disagree_s 180 How long they must stay opposed, continuously, before the failsafe trips
unit_sign_disagree_w 250 Two or more inverters only. Both a unit's own share and its own measured power must exceed this before their sign difference counts. It is saturation_w / 2, so the smallest divergence it can see is exactly the gap at which the loop already calls the inverter "not following". Must stay below max_w or it can never fire, and the add-on refuses to start
unit_sign_disagree_s 85 Two or more inverters only. How long one unit's command and its own power must stay opposed before that unit is parked
site_sign_disagree_w 300 Two or more inverters only. Threshold for the site-wide check - the sum of the commands against the meter. The same 300 W as sign_disagree_w, for the same reason: near zero the sign is noise
site_sign_disagree_s 325 Two or more inverters only. How long the site's total command and the meter must stay opposed before every inverter is parked. Longer than sign_disagree_s because the command has to cross zero over a rail that is the sum of the roster, at a slew_w that is not - measured at 110 s with one inverter and 215 s with two
delivery_hold_s 185 Two or more inverters only. How long one inverter may stand at a discharge share it is not producing - short by more than saturation_w, with no reason this add-on can read - while at least one sibling is not in that state, before it is named. It reports; it does not act. Nothing is commanded differently and the site goes on running short by that unit's share

The sign-disagreement failsafe

If the setpoint this add-on is emitting and the grid figure it is regulating on point opposite ways — charging the battery while the house imports, or discharging it while the house exports — with both over sign_disagree_w, for sign_disagree_s continuously, the add-on commands 0 W and holds it there. The banner reads FAILSAFE, the commissioning list says which two numbers disagreed and for how long, and the Controller status entity reports failsafe.

⚠️ At two or more inverters this is TWO checks, not one (SAFETY-30)

The paragraph above describes what a one-inverter install does, and it is unchanged: there is one meter, one actuator, and comparing the command against the meter is comparing a thing with a view of itself.

With a second inverter that stops being true. The meter answers for both units, so a command put on one of them can be opposed to it with nothing wrong (inverter A charging while inverter B discharges more), and - the worse direction - a unit genuinely driving the wrong way can be hidden, because its sibling's watts arrive at the meter and the sum looks healthy. So the check splits in two, and they are different faults:

  • Per inverter — that unit's own share against its own measured power (the batt_entity reading, register 0x0518). This catches "this inverter is not doing what it was told". Only that inverter is parked; the site keeps running on the one that works. Thresholds: unit_sign_disagree_w / unit_sign_disagree_s.
  • Site-wide — the sum of what every inverter has standing, against the meter. This catches "the site as a whole is pushing the wrong way", which no per-inverter check can see because every unit may be faithfully executing its share of a number that is itself wrong. Every inverter is parked and the banner names the site rather than an inverter. Thresholds: site_sign_disagree_w / site_sign_disagree_s, latched under flat site_sign_tripped in /data/state.json.

Both latch, both are cleared by the same stop, then start, and both survive a restart. On a one-inverter install neither pair does anything at all - the two questions are the same question there, and only the check described above is armed.

This is not the circulating-power alarm further down: that one compares the inverters against each other and catches them pushing power through each other, which nets to zero at the meter and which no command is evidence about. It is also not the saturation freeze, which is a magnitude test that shapes the loop rather than a direction test that parks an inverter.

It does not clear itself, and restarting the add-on does not clear it either. Pressing Start / stop control twice — stop, then start — is the only thing that does. That is deliberate on both counts:

  • Commanding 0 W removes the command side of the comparison, so the disagreement always vanishes the instant the trip works. A watchdog that took that as proof the fault was over would hand the inverter straight back to the loop that was driving the wrong way, three minutes later, forever.
  • The trip is written to /data/state.json — under unit/<inverter>/sign_tripped, one key per inverter since DEV-02, so a trip caused by one inverter cannot latch another — and restored on startup. The pre-DEV-02 flat sign_tripped is written and cleared alongside it as the rollback view, so downgrading the add-on past DEV-02 still finds the latch, and a trip taken while the install is rolled back is re-armed by the version that comes back up rather than silently lost. Restarting the add-on is the first thing most people try when they see a red banner, and a latch that a restart clears would bring the controller back armed, into the same fault, unattended — and under a Supervisor that restarts a crashed add-on automatically, would do so in a loop. After a restart the banner, the 0 W and the recorded reason are all still there.

What it is for. This is a loop-integrity check: it asks whether the loop's output direction still matches the input state it was regulating. It catches a polarity error anywhere between the meter and the wire, and an integrator so far wound up that unwinding takes minutes. It is the check that would have caught all four episodes of 2026-08-20, when a commercial controller charged the battery out of the grid, four times, for up to 77 minutes at a time.

What it is not for. It does not detect an inverter that acts opposite to what it was told — that moves the meter further the same way, so command and meter agree while everything runs away. That is the saturation freeze's job (saturation_w / saturation_cycles), which compares the command against the battery's actual power. The two checks are complementary and neither replaces the other.

Why it will not false-trip on ordinary operation. A battery that refuses a command (empty, full, standby) leaves the meter where it was, so command and meter agree. A frozen meter drives the loop into agreeing with it. Around the resting point both signals are inside the 300 W gate, so the deadband can never produce one. A load step does flip the meter's sign before the loop catches up — measured on a full captured day, the longest such crossing is 30 s, against a 180 s window. And the watchdog is disarmed whenever the grid-following loop is not what is driving: a maintenance grid charge opposes the meter by design and must not be mistaken for a fault.

Both numbers are measured rather than chosen, and are exposed only because the ticket requires defaults rather than constants. On the captured healthy day sign agreement is 93.4 %; on the four captured fault clusters it is 0.3 %, 0.9 %, 10.5 % and 0.0 %. There is no reason to move either value without a capture that says so.

⚠️ A unit that stops DELIVERING is a third fault again (SAFETY-42)

The two checks above both key on direction. A unit sitting at 0 W against a non-zero share has no direction: it is not pushing the wrong way, it is absent. So the per-unit sign gate never opens (it needs opposition on both sides of unit_sign_disagree_w), the site sum still agrees with the meter in direction, and circulating power is exactly zero — that quantity needs two units pulling against each other, and one of these is pulling nowhere.

The only thing that does fire is the saturation freeze, and this add-on's own code calls that an alarm operators learn to ignore, because a loop can be legally saturated all day: a cold pack, a curtailed inverter, an export limit.

So delivery_hold_s grades a different quantity — how many watts of a discharge share did not arrive — and makes it readable with a reduction that only exists once there is more than one inverter:

a unit is named while it is short of its share by more than saturation_w, with nothing this add-on can read to explain it, and the units in that state are fewer than the units that were asked to discharge.

Both halves matter, and the second is why this cannot fire on a one-inverter install at all:

  • "nothing explains it" is what keeps a legitimately empty pack out. A pack at or below its own bms_soc_floor cannot discharge, and that is the only fact this add-on holds that distinguishes an empty pack from a wedged one — the two are otherwise identical at the unit and at the meter, watt for watt. A unit the add-on has already dropped from the split, or parked by a sign trip, is likewise accounted for.
  • "fewer than were asked" is what keeps a whole-site cause out. A derate this add-on cannot see — thermal, grid-code, DC-side — hits every unit. One box that has stopped listening does not. If every unit that was asked is short and unexplained, nothing is reported: there is no instrument here that tells that from a plant which simply cannot deliver.

It reports. It does not act. Commanding an inverter that has stopped listening achieves nothing — that happened on this hardware once for 6 h 25 m — and the only re-allocation this add-on can express is all-or-nothing, which would throw away the output of a unit delivering part of its share. So the loop is untouched, the sibling keeps regulating, and the site keeps running short by that unit's share until somebody looks. The status page shows it as a caution rather than a failure for exactly that reason: the controller has not stopped.

The report survives a Home Assistant restart (unit/<name>/delivery_tripped in the add-on's own state file) and the notification is re-raised on the next start, because a persistent_notification is in memory and that is precisely how the 2026-09-02 outage went unseen. It is cleared by pressing Start, like the other latches.

The banner reads NOT DELIVERING — <unit> … as a warning, not a failure, and it displaces Running — holding grid at zero. That last sentence is a claim the site cannot make while a unit is absent, and a page that goes on reading healthy while the fault runs is the whole shape this check exists to remove.

Charge shares are not graded, and that is a stated gap rather than an oversight: there is no configured charge ceiling anywhere in this add-on, so a pack in constant-voltage taper — which legitimately takes hundreds of watts less than it is told, for tens of minutes — could not be explained, and arming that direction would fire on the taper of every maintenance charge.

Saturation is counted in cycles, not seconds

The specification states the saturation window as "> 10 s". This add-on counts cycles instead, and that is a deliberate, accepted deviation rather than an oversight - the acceptance criterion is not met as literally written.

A cycle here is one meter update or cycle_floor_s elapsing, whichever comes first. At the reference P1's ~5 s update rate the default of 3 cycles is usually around 15 s, and the worst case is bounded at 3 x cycle_floor_s = 45 s. It is still not the 10 s the specification asks for, so the deviation stands - but it is now a bounded number rather than an open one.

⚠️ This passage used to say something different, and the second half of it was wrong. Until SAFETY-12 the loop ran only when the meter value changed, so a meter that repeated a value stalled the counter for as long as it repeated, with no upper bound at all. That was defended here on the grounds that "a stalled counter is a detection-latency limit and not a runaway risk - the condition that stalls it stops the whole loop, so nothing accumulates while it is stalled". That argument covers integrator windup and nothing else. The hazard it misses is staleness: while the loop was stopped the heartbeat kept re-emitting the last command and the firmware kept putting it on the wire every 2 s, so a command computed from an old reading went on being executed through a real load change, with every indicator reading healthy. Measured on the rig during TEL-05: 70 s at a literally constant 350.0 W, 14 arrivals, zero control cycles.

The half that survives is the first one: the control law is still a pure function with no clock, and the wall-clock window still lives in Controller, which has one - see run_control(). What changed is that the controller now enforces a floor on the gap between cycles, so saturation_cycles finally means a bounded number of seconds.

If a tighter window matters on your site, lower cycle_floor_s (not below your meter's update interval, or the floor starts firing on a healthy meter) or raise saturation_cycles for a fast meter.

This is not a freeze detector, and it deliberately cannot be one. Nothing here decides whether a repeated reading is true — see unchanged_s in the meter section for why no threshold on that is safe at the converged operating point. The floor only stops "the number is the same" from meaning "do not think". The consequence is worth stating plainly: against a meter that is genuinely frozen at a wrong value, the loop will now correct toward that wrong value instead of holding a stale command. It is bounded by max_w, the arbiter and the device rating, and it is the same thing that already happened to a lying meter whose value merely jittered — bit-exact repetition was never a safety property.

When the freeze lets go, and when it deliberately never does (SAFETY-13)

While the loop is frozen the command's magnitude may fall but never rise. That is the anti-windup rule, and at prev_w == 0 it reads as a refusal to start: with nothing commanded there is no magnitude left to fall, so a charge cannot begin. That refusal is deliberate. Commanding 0 W while the inverter reports hundreds of watts means something is driving the actuator that this add-on did not ask, and starting to push power the other way into it is how two controllers end up fighting over one actuator — the configuration §1.5 of the specification rules out.

What was missing was an end to it. Nothing cleared the block: not the error growing, not the integrator moving, not time. The exit is now explicit, and which freezes get one is the decision:

the inverter is… can it clear itself? what happens now
doing less than the command, in the command's own direction — a cold pack, a curtailment, an export cap yes. The command is pinned at something the inverter can reach, so it catches up and the freeze clears unchanged: frozen for as long as it lasts, with no exit
doing something outside what the command can explain — overshooting it, or the opposite sign not necessarily. If another writer is on the actuator, clearing the freeze needs the inverter to track our command and the other writer is what stops it, so nothing ends it the freeze releases once the divergence has outlasted the plant that could otherwise have explained it — see what freeze-released actually tells you, below, because this row is also where our own ramp lands

The second row's threshold is the plant's own measured settling time — the slower of the two directions it was measured in. The 2026-08-22 step test timed the same 1.78 kW step both ways: about 18 s to settle going up, about 23 s coming back down. 23 s is the one that belongs here, because the question this bound answers is how long may the plant still be the explanation, and the safe answer is to keep believing the plant for as long as the plant has ever been seen to take. At the measured 2 s meter tick that is 12 cycles (control.py, SETTLE_CYCLES).

⚠️ The first version of this feature used 18 s, and 9 cycles was wrong in the direction that accuses. Nine cycles is three short of the plant's own down-ramp, so an ordinary load step on a single inverter — the command falling through zero while the pack is still coasting the old way — could produce freeze-released with nothing else on the bus at all. Driven in the container against a model of the measured plant, one inverter and no second writer anywhere: over 272 load-step pairs the 9-cycle bound produced a release in 62 of them and the shipped 12-cycle bound in 2.

Releasing the output freeze does not unfreeze the loop. The integrator freeze is untouched, so the command is free to move only as far as an accumulator that stopped accumulating cycles ago, one slew step per cycle. Measured on the simulator at the live install's shape (max_w 5000, slew_w 400, target_grid_w -10), with another writer holding the pack at +700 W and 2 kW of export standing: the command holds at 0 W while the counter climbs, starts on the twelfth saturated cycle, walks 0 → −400 → −800, and settles at −1190 W against a frozen integrator of −1194 W — not at the 5000 W rail. Before this change the same run held 0.0 W on every cycle, for as long as the other writer stayed.

⚠️ The site still does not reach its target in that state, and it is not supposed to. What the exit buys is that the battery stops being idle while the site exports; what it does not buy is correct regulation against an actuator somebody else is also writing to. A standing grid error with another writer on the bus is the symptom of a configuration this add-on refuses to support, not a tuning problem.

What freeze-released in the action log actually tells you

It says: the inverter's power did not match the command for longer than this plant has ever been measured to take to settle. That is all it says. It is a reason to go looking; it is not a finding, and in particular it is not proof that a second writer exists.

The test behind it compares the reading against one cycle's command, and the pack carries more than one cycle of history. So our own power, arriving late, can look like somebody else's:

  • A big, fast load step is the ordinary innocent cause. The command falls through zero while the pack is still coasting in the old direction, and for a few cycles the reading has the sign the command used to have. Measured, one inverter, nothing else on the bus: eight cycles after a +1990 W command the command was 0 and the pack still read +522.3 W.
  • A plant slower than the one that was measured does it too. The 12-cycle bound is derived from a 23 s down-ramp. A colder or larger pack that takes longer than that will produce releases on its own, and no constant read off the 2026-08-22 measurement can prevent it. In the same container sweep, holding the bound at 12 and lengthening only the plant's down-ramp, single-inverter releases went from 8 of 320 scenarios at the measured 23 s to 59 of 320 at 34 s and 268 of 320 at 50 s.

So, in order: if you see freeze-released once, during or just after a large load or PV swing, that is most likely the loop's own ramp and needs nothing. If you see it standing — cycle after cycle, at a steady load, with a standing grid error the battery is not correcting — then look for the second writer: another controller, a scheduler in the inverter's own app, or an installer tool left connected. That is the configuration §1.5 of the specification rules out, and it is the one this exit exists to stop the loop stalling on forever.

⚠️ No saturation_cycles you can set removes the block. This file accepts 1-10, and all of those are below the 12-cycle release bound, so the freeze always engages before its own exit is due. (The first version of this feature had the bound at 9, where a setting of 9 or 10 did silently delete the block; moving the bound to 12 closed that by construction rather than by warning about it.)

Why target_grid_w is not zero

The deadband is a one-way ratchet: any resting point inside it holds until something disturbs it. Import and export are separate registers on the meter, so a rest point of +14 W is billed for every second it holds and no amount of export cancels it - 14 W all day is 0.34 kWh.

Biasing the target below zero moves that residue into the export register, which is not billed. The resting band becomes target ± deadband, so:

target_grid_w resting band worst billed leak export given away
0 -15 … +15 W ~15 W (0.35 kWh/day) none
-10 -25 … +5 W ~5 W (0.12 kWh/day) ~10 W
-15 -30 … 0 W none ~15 W (0.36 kWh/day)

Set it to -deadband_w if injection is worth nothing to you and you would rather give the energy away than buy it back. Set it to 0 if you are paid properly for export, or if you are debugging and want the loop centred.

⚠️ This is a billing knob, not a speed knob. If import is arriving in bursts rather than as a trickle, the cause is tracking lag, and this will not help - see "Why the tuning is what it is".

Maintenance

option default meaning
maintenance_enabled false Enable the monthly cycle
maintenance_interval_days 28 Minimum gap between cycles
maintenance_start_hour 10 Hour of day a due cycle begins
maintenance_discharge_w 2000 Drain rate (exports the surplus). Above max_w it is clamped to max_w — the drain phase SETs the setpoint and the arbiter bounds it, saying so on the status page (limited by supervised(max_w)). Warned about, not refused: the cycle still completes, just slower
maintenance_charge_w 2000 Charge ceiling, capped again by peak headroom. Must stay at or below max_w or the cheap-window shaping (hi = -maintenance_charge_w) contradicts the supervised limit (lo = -max_w), the arbiter resolves it to 0 W, and maintenance silently never charges in a cheap window — the add-on refuses to start
maintenance_soc_floor 11 Drain target — stay just above the inverter's own floor. ⚠️ This is not peak_soc_floor. It is the depth the monthly recalibration deliberately goes to, once, on purpose; peak_soc_floor is the depth a money-saving discharge may never reach on any day. The right values differ (11 vs 20 as shipped), which is why they are two keys
maintenance_soc_target 99 Charge target
maintenance_hold_min 120 Hold at full so the BMS can balance

Tariff (all optional)

option meaning
peak_forecast_entity Quarter-hour demand forecast, for capacity-tariff markets. Empty = no cap
peak_cap_w The site's capacity-tariff target
peak_soc_floor (20) The percent below which the capacity-peak guard will not discharge the battery. ⚠️ It bounds the peak guard only — it is not a pack-wide reserve, and ordinary self-consumption discharges straight past it (SAFETY-25, see below). Not optional and not the same thing as maintenance_soc_floor
bms_soc_floor (10) The pack's own cut-out percent, the number the BMS enforces whatever you set above. peak_soc_floor must be strictly above it or the add-on refuses to start. ⚠️ At a declared inverters: roster this key moves INTO each entry and is REQUIRED there (SAFETY-32): it describes a battery, and two packs of different models have different cut-outs, so one number for both protects the shallower pack with the deeper pack's BMS. Nothing is inherited — an entry that omits it is refused by name at startup, and the flat key below is then not read at all
price_now_entity, price_avg_entity Dynamic tariff. Empty = never force a paid grid top-up

On a capacity-tariff site the maintenance charge is capped by the headroom left under peak_cap_w, and if the forecast goes over the cap the charge-only clamp is dropped so the battery can shave the peak instead. Money outranks the maintenance schedule.

Capacity-tariff exposure of the grid-following loop

⚠️ This section described the exposure BEFORE SAFETY-07. The loop is now capped — see "The capacity-peak guard" below — and what follows is kept because it is still the clearest statement of WHAT is being guarded and why the number is worth what it is.

⚠️ peak_cap_w caps MAINTENANCE charging. It does not cap the loop. The grid-following loop is bounded by max_w and by the device rating, and by nothing else. That is deliberate — the loop exists to reduce what crosses the meter, so under every healthy condition it lowers the peak rather than raising it — but it means one thing is true and worth writing down:

If the meter lies, the loop will happily buy max_w from the grid for as long as the lie lasts, and no cap in this add-on stops it. A meter frozen at a large export reads as "the house is exporting hard", the loop charges the battery to correct it, and the correction is a grid import. At the schema maximum max_w: 5000 — which is what this house runs, and is also the device rating — that is a 5 kW unattended import.

The bill is not the energy. In the Belgian capaciteitstarief the month is billed on its highest quarter-hour average, so fifteen minutes of this sets the whole month's peak. A measured case: one 4998 W quarter moved a monthly peak from 4832 W to 5013 W, and every day of that month was billed at the higher figure.

What exists today, and what does not:

max_w bounds the magnitude ✅ — but the exposure IS the magnitude
Maintenance charging capped under peak_cap_w ✅
Loop capped under peak_cap_w ✅ — SAFETY-07, on every meter_source but off
Frozen meter detected ✅ on homewizard_local only, alarm only
Frozen meter stopped ✅ — SAFETY-07 forbids importing while the meter is frozen
SoC guard on the loop ❌ — the BMS is the only energy backstop

On the legacy meter_source: off path there are no P1 telegrams, so there is no quarter-hour average to guard, and the status page says NOT COVERED. There the mitigation is still operational: set max_w no higher than the loop actually needs (the tuning was measured at 2000 W and a 1.78 kW load step is tracked fine there), fit the e-stop, and watch for the alarm.

The capacity-peak guard

What it does. Every cycle the add-on projects the open quarter to its end-of-interval average — from P1 telegrams only, never from the command — and compares it to a ceiling. Over the ceiling it files one claim: a lower bound on the setpoint, at P_PEAK. That single shape is both behaviours §10.1 asks for: a hard clamp on charging while the bound sits above the standing charge, and pre-emptive discharge while it sits above zero. It can never cap discharge or export, because a floor cannot.

The number. excess = 900 × (projected − ceiling) ÷ seconds remaining, and the floor is the measured battery power plus that. The 900/remaining factor is the design rather than an accident: it is 1.0 at the top of the quarter and grows, so the guard is gentlest when its projection rests on the least evidence and becomes aggressive only once the quarter is nearly measured.

The ceiling is peak_cap_w, raised to the month's banked peak when that already stands higher — once a month's bill is set at 5013 W, holding later quarters to 3500 W buys nothing and costs real charging. That relaxation is granted only by an OBSERVED reading: a peak store that cannot be read leaves the ceiling at the cap, so a broken instrument makes the guard stricter, never looser.

When it cannot see, it forbids importing. Three states are not evidence and are checked before the projection is graded: no open quarter (a fresh averager projects a confident 0 W, which is under every ceiling there is), a meter gap longer than meter_max_age_s, and SAFETY-18's frozen-meter conjunction. In all three the claim becomes a floor of 0 W. That is the backstop for the frozen meter: the alarm arrives at meter_freeze_s (300 s) of a 900 s billing quarter and commands nothing, and this stops the import.

It trips, where the freeze detector only notifies, and the captures are why. On the healthy reference day (2026-08-23) it engages on zero of 95 quarters. The action is level-triggered and unlatched — re-derived from a fresh projection every cycle, released the instant the projection drops back — so a false engagement costs one cycle of discharge rather than a parked battery. And it is a LIMIT, so every stop in the watchdog table still outranks it.

Replayed on 2026-08-20, the day the vendor controller failed: the billed quarter measured 5029.8 W, above the inverter's own 5000 W rating, and the guard brings it to 3485 W — under the soft limit, without ever asking for more than the inverter can give. Across both committed days the quarters under the limit go from 189/190 to 190/190. Two days is not thirty and does not close AC 3; it is the comparison two days can support.

What it alarms on is saturation, not engagement. An engagement is an ordinary control action and goes to the action log and the status page. A saturated guard — asking for everything the inverter has while the quarter is still projected over — raises one notification (goodwe_peak_saturated), because that is the one state where the money will be spent and shedding load is the only thing left that changes the bill.

No new option for the CEILING. It is peak_cap_w, which already shipped. The coverage threshold is meter_max_age_s, the freeze predicate is meter_freeze_s, and the achievable discharge comes from max_w and the device rating — every one of them a key that already exists.

The energy floor under the forced discharge (peak_soc_floor)

The guard above can command a discharge, and until SAFETY-24 nothing in the add-on bounded how far down it took the pack — the BMS was the only backstop. On the 2026-08-20 replay the guard asks for 878 Wh in a day.

That is not absurd: the BMS floor is real and it works. But it is the pack's protection, not yours. A month of aggressive quarters can leave the battery repeatedly parked at that cut-out with no record on this side of why, and the first symptom — a battery that is never available when you want it — looks exactly like the SoC drift the monthly maintenance cycle exists to correct.

  • peak_soc_floor (20 %) is where the forced discharge stops. Below it the guard files a 0 W floor instead of a sized one: charging stays blocked (that can only ever lower your offtake), and no further discharge is asked for.
  • ⚠️ IT BOUNDS THE PEAK GUARD ONLY. IT IS NOT A PACK-WIDE RESERVE, AND THE NAME READS LIKE ONE. The ordinary self-consumption loop — the grid-following control law that holds your meter at zero — has no SoC floor of any kind. It will discharge straight past this number and keep going until the pack's own BMS cut-out stops it. What you are promised by peak_soc_floor: 20 is "the capacity-peak guard will not spend the pack for money below 20 %", and nothing more. See below for what that costs on a real evening.
  • When it binds you are told, once per episode, with notification goodwe_peak_soc_floor and a status-page row reading PEAK GUARD FLOOR-LIMITED: the quarter will go over the ceiling, so shedding load is the only thing left that changes the bill. Failing to shave is never silent — the euro figure is the whole point of the guard.
  • An unreadable SoC is treated as floor-limited, not as a full battery. A full battery is exactly the value that would disarm this floor.
  • bms_soc_floor (10 %) is the pack's own cut-out — register 0x0560 on the reference GW5000S-BP, consistent with DoD 90. It exists so the add-on can refuse to start when peak_soc_floor is at or below it: such a floor can never be the thing that stops the discharge, and a guard that advertises a backstop it does not have is the one thing this project will not ship. Equal is refused too — equal buys zero margin.

Why 20 %: the reference pack is 13.8 kWh usable, so 10 points of margin over the BMS cut-out is about 1.6× the guard's worst measured day. If your pack is smaller, or your quarters are worse, raise it.

⚠️ What peak_soc_floor does not protect (SAFETY-25)

On a sustained-load evening this add-on will take your battery to the BMS cut-out, whatever peak_soc_floor says. That is measured, not argued. Replayed on the committed 2026-08-20 capture, 19:00–22:00 UTC — three hours of house load after the sun has gone, 830 W average, not one watt of export in the window — with the 13.8 kWh reference pack started at 21 %, one point above the shipped floor:

pack at the start of the evening 21 % (one point above peak_soc_floor)
pack three hours later 10.0 % — the bms_soc_floor cut-out
energy the loop took out 1525 Wh
control cycles below peak_soc_floor 549 of 587, and 343 of those still delivering discharge
cycles on which the peak guard filed any floor 0
same replay at peak_soc_floor = 5, 11, 20, 60 the same 10.0 %, to four decimal places

That last row is the point: this is a property of the control law, not a value you can configure. Raising peak_soc_floor to 60 % changes nothing at all, because the guard it bounds is not the thing doing the discharging.

And the two can happen in the same cycle. On the high-load block of the same day (15:00–17:00 UTC) with the pack below the floor, the guard reports PEAK GUARD FLOOR-LIMITED — "commanding no forced discharge" — on 49 cycles, and on all 49 of them the loop is simultaneously being granted a discharge of up to 2000 W by the arbiter. The status page is telling you the truth about the guard while the battery empties.

Why it is built this way, and why SAFETY-24 could not fix it. The peak guard files a lo limit — a lower bound on the setpoint. That asymmetry is exactly what makes the guard safe: it is provably incapable of lowering a target, capping a discharge or contradicting the arbiter. The same property makes it incapable of stopping a discharge the loop itself wants. A floor on the guard cannot become a floor on the pack by being raised.

Is this a runaway? No. Self-consumption discharge is demand-driven and self-limiting: it stops when the house stops drawing, and every watt of it is serving load you would otherwise have imported. It is not SAFETY-18's frozen-meter rail. What it means is that the depth your pack reaches on a heavy evening is set by your house, not by any number in this file, and the BMS is the only thing underneath it.

This is now a recorded decision, not an open question. On 2026-09-02 the product owner took Option A: the BMS cut-out is deliberately the only backstop for demand-driven discharge, and a loop-side reserve floor is deferred rather than rejected. The options, their costs, the measured replay and the reasoning are in DECISIONS/SAFETY-25-loop-soc-floor.md, together with the revisit trigger (ALLOC-01, the host-side share allocator) under which a reserve becomes safe to build. Nothing about the behaviour above changed — Option A is what has always shipped. What changed is that this section now describes a choice somebody made, and you can read why.

The winding-loop alarm (the output clamp)

Every setpoint this add-on writes is clamped to max_w before it leaves the process, and when that clamp actually engages, it alarms. The clamp on its own is not the feature - this project already clipped, and the clipping is what hid the defect the guard exists for: with the inverter switched off entirely an unclamped integrator climbed ~130 W per 4 s past 10 kW and, pinned at the 5 kW rail, reported 14 768 W. Clipped silently, that is a flat, legal-looking 5000 W hold on every dashboard, and nothing anywhere says the loop asked for three times it.

What "the rating" is. The bound is max_w, and only max_w. It is already validated against the setpoint device's own range at startup - the add-on refuses to start if max_w exceeds what the device accepts (and again once ESPHome is up and the real rating is known), so by the time the loop runs the two numbers agree. The device range is applied a second time inside the write as defence in depth; after a successful validation it cannot bite, and if it ever does, that engagement alarms too and names the bound.

Clamping is not saturation, and the two never share a channel.

what it means what happens
clamp the computed value exceeded the rating a software bug signal - something upstream is winding. Alarm.
saturation the inverter is not following a perfectly legal command a hardware condition - freeze the integrator. No alarm.

A loop can be legally saturated all day: a cold pack, a curtailed inverter, an export limit. Routing the clamp through a saturation-shaped alarm puts the bug signal inside the noise, which is the same silence as clipping quietly. They share no reason code, no notification id, no status row and no counter.

It is an alarm, not a trip. The clamped value is written and the loop keeps running - this is not the sign-disagreement failsafe, which commands 0 W. You get a persistent notification (goodwe_output_clamp, replaced rather than stacked), an ERROR in the log with the reason code OUTPUT_CLAMP, a row in the event list, and a red status banner while it is engaged. Once it clears, a warning row keeps the engagement count so the evidence does not vanish with the condition. Consecutive engagements share one event row carrying the exact count, because the event list keeps only 40 rows and a row per cycle would flush every other guard's entries out of it.

There is nothing to configure, deliberately. The bound is max_w, which you already set; giving the guard a limit of its own would be a second number that can disagree with the first, which is exactly the failure the startup validation exists to prevent. The alarm's cadence - first engagement, then re-asserted every 30 s while it persists, cleared after 3 clean cycles - is fixed for the same reason RAIL_FRAC is: it describes the notification bus, not the plant.

WARNING: on a default install the engagement you will see is the integrator's, not the output's. The control law bounds the integrator to max_w and then derives the command from it, so the command itself can never come out over the rating unless integrator_max_w has been deliberately raised above max_w. Both are watched. A guard that watched only the emitted value would be silent on every standard configuration.

The frozen-meter alarm

A meter that has died is easy — it stops answering, the sample age climbs past meter_max_age_s, the reading becomes missing, and the add-on and the ESP32 both command 0 W. A meter that keeps answering 200 OK with a document that never changes is the hard one: every freshness mechanism in the stack reads it as healthy, because it really is arriving on every poll. The loop then integrates a constant error and winds to the rail, in 75–360 s at max_w: 5000.

The add-on alarms when both of these are true at once:

  • the meter's own document (power figure and both kWh registers) has not changed for meter_freeze_s — 300 s by default; and
  • the command standing on the wire is at the rail, within 5 % of the ceiling the command can actually reach.

That ceiling is min(max_w, the setpoint device's own rating), not max_w. The emitted command is clipped to the device's reported range as well as to max_w, so on a 4700 W inverter configured with max_w: 5000 a rail measured at 4750 W is one the command can never stand at — the guard could not fire, and the status page said armed anyway. It now measures the rail against the smaller number and the page names it, saying "below max_w because …" when the device is what capped it. (On an install that started, the two are equal: a max_w above the device rating is refused at startup. This matters when the rating could not be read at boot — see below.)

Neither half is usable alone. A bare "unchanged for N seconds" rule false-trips at the exact operating point this controller aims for — at a converged −10 W a 1 Wh register legitimately takes about six minutes to move — and a bare "at the rail" rule fires on any genuinely large load. Together they are safe in both directions, because a real railed condition means kilowatts still crossing the meter, and a kilowatt advances a 1 Wh register every 3.6 s.

It is an alarm and nothing else. It does not command 0 W, does not latch, and does not claim the actuator. A false trip here parks the battery; a false notification costs an alert. Turning it into a trip is a separate decision that needs data from a real install — and an answer to "what should the loop do instead", given that 0 W is itself an import of whatever the house is drawing.

When it fires you get a Home Assistant persistent notification (goodwe_meter_frozen, replaced rather than stacked on a repeat), an ERROR in the add-on log, an entry in the UI's event list, and a red banner on the status page. The loop keeps running. If the meter really is stuck, stop control from the add-on UI.

⚠️ Only meter_source: homewizard_local is covered. It is the only transport that reads the meter's own document; on ha_dsmr, mqtt_p1, ha_signed and off there is no signal to threshold and the status page says NOT COVERED rather than pretending the guard is armed.

The same row appears for a second reason: a setpoint device that reports a range from which no command magnitude is available in both directions leaves no rail to measure at all, and a 0 W rail would be satisfied by every command. That is reported as NOT COVERED too, and the detector stays silent rather than degenerating into the bare "unchanged for N seconds" rule this design exists to avoid.

option default meaning
meter_freeze_s 300 Seconds of an unchanged measurement, while the command is at the rail, before the alarm

Why 300 s: over 2399 s of this house at the converged operating point (mean grid −14.2 W, 1194 polls, 735 of them repeating the previous reading) the largest unchanged_s any sample sees is 8.0 s, and the longest interval serving no distinct reading at all is 15.4 s. There is also a structural reason not to lower it much: at 300 s the slowest a healthy register can tick and still look unchanged is 12 W, which is inside the 15 W deadband — so the command there is parked at 0 W and the two halves of the rule cannot both be true. At the schema floor of 60 s that figure is 60 W and only the margin is left.

The circulating-power alarm (SAFETY-31)

Only at two or more inverters. At the shipped roster of one this quantity is identically zero for every reading, no claim is ever filed, and the status page says n/a rather than pretending to watch it.

Two inverters can move a great deal of energy while the meter reads almost nothing. Inverter A charging at 3 kW while inverter B discharges at 3 kW nets ~0 W at P1: the site looks idle, and in reality the packs are being cycled through two round-trip conversion losses continuously, for no benefit.

Nothing else in this add-on can see it, and that is structural rather than an oversight. Every other guard is a consumer of the net figure at the grid connection — the sign-disagreement failsafe gates on abs(grid_w) > 300 W and that gate never opens at a netted zero; the capacity-peak guard and the tariff both bill grid exchange. Circulating power is precisely the component of per-inverter power that the sum destroys.

So the add-on computes a quantity none of them were computing:

circulating_w = Σ|Bᵢ| − |ΣBᵢ|

Zero when the units pull the same way. 2 × min(|B_a|, |B_b|) when they oppose — twice the power going round the loop, which is what both conversion stages are processing between them. It is published as sensor.goodwe_circulating_power, deliberately beside the grid figure: "grid 0 W, circulating 6000 W" is the whole fault in two dashboard rows, and no arithmetic on the grid figure alone can produce the second one.

It is derived from each inverter's own measured power, not from what the controller believed it commanded. That matters because the allocator already refuses to command opposite directions (ALLOC-01's sign-coherence gate), so a figure computed from the allocation record would read zero by construction and detect nothing. What this catches is circulation nobody commanded — a unit ignoring or lagging its share, a stale share still being executed, or an inverter doing something of its own accord.

option default meaning
circulation_w 700 Watts of measured opposition below which nothing is reported
circulation_hold_s 75 Seconds it must stand there continuously before the trip

Why 700 W and 75 s, and why neither is a round number. Both were read off 924 closed-loop runs on the two-master test rig in which nothing was faulty, swept across the whole range the schema accepts for gain and slew_w. A momentary opposition is legitimate: writes to the inverters are serialised, so on a reversing cycle one unit gets its new number up to a control cycle before its sibling, both slew through zero, and between the two crossings they genuinely oppose. The worst continuous legitimate opposition, by threshold, was 505 s at 100 W, 40 s at 250 W, 10 s at 300 W and 5.0 s — one control cycle — at 400 W and above. The knee is 400 W and it is the schema floor; below it, ordinary operation would hold the sensor over the line for minutes and no usable window could tell that from a fault. 700 W carries margin above the knee because the second inverter's ramp and lag are not yet measured. 75 s is 15× the worst legitimate episode, 2.5× the firmware's own 30 s link-veto window, and comfortably inside the 900 s quarter that bills the capacity tariff.

What happens when it trips, and what it honestly cannot do. The site is commanded 0 W on every inverter and latched there until you press start. That is not aimed at making a misbehaving inverter stop — if a unit has stopped listening, no command will reach it. It does two things that do not need its cooperation: it removes this controller as one of the two participants in the loop, and it makes anything still happening visible at the meter instead of cancelled at it, where the ordinary guards can see it. If the grid reading does not move after the trip, one inverter is no longer listening and the remaining actuator is a human at the isolator.

The alarm survives a Home Assistant restart. The latch is written to /data and the notification is re-raised on the first cycle after every start — persistent_notification lives only in memory, and an alarm that vanishes with a restart is how a real outage on this system went unseen for over six hours. Restarting does not clear the trip; starting control from the add-on UI does, and only after you have read why.

Energy price providers

A fetched price moves energy only when you switch arbitrage on. This release ships the five provider plugins, the canonical all-in format they emit, the config that selects one, and — new in OPT-04 — a price-arbitrage strategy that trades on them. With arbitrage_enabled: false, which is the shipped default, turning a provider on still fetches, validates and publishes prices and changes no charging decision.

static_profile below needs no network at all, so its cheap window is computed on every cycle and reaches the maintenance cycle's grid top-up whether or not arbitrage is armed.

option meaning
price_provider off (default) or one of the five plugins below
price_markup_eur_kwh Your supplier's margin, EUR/kWh. Added only when the chosen plugin's feed does not already contain it
price_taxes_eur_kwh Levies and VAT, EUR/kWh. Same rule
export_price_eur_kwh The injection price. A separate scalar, not a series — see below
price_csv_path Where manual_csv reads its file
price_feed_url Override the plugin's default feed. Only a host the plugin itself declares is accepted
price_horizon_h How far ahead to ask for, hours
price_timeout_s Per-request timeout
static_profile A static day/night or fully-fixed tariff. Empty by default — see below

Which plugin sources what. This is the one thing to get right, because adding your markup to a price that already contains it makes every future arbitrage decision wrong by that amount, in a direction nothing reports.

plugin product the published figure contains the add-on adds
generic_dayahead day-ahead energy only (wholesale EPEX BE) markup and taxes
engie_dynamic day-ahead energy + Engie's markup taxes
totalenergies_dynamic day-ahead energy + TotalEnergies' markup taxes
eneco_eddy real-time / imbalance everything, all-in nothing
manual_csv day-ahead everything, all-in nothing

You cannot get this wrong by editing the markup: each plugin declares what its feed contains and the add-on adds only the rest. Set a markup under a plugin that already carries one and it is ignored, with a line in the log saying so — never applied twice.

That holds given a correct declaration, and it is worth knowing where the line is. What the add-on enforces mechanically is that a plugin cannot obtain the markup or apply it: the numbers are not reachable from plugin code, and a plugin whose code mentions them fails to load at all. What it cannot check is whether a plugin described its supplier's feed truthfully — that is a claim about somebody else's tariff, and no code can verify it. If you write a plugin, the sources declaration is the part a reviewer has to read.

eneco_eddy is a real-time/imbalance product rather than a day-ahead one. It is flagged as high-volatility, which widens arbitrage thresholds once the optimiser lands. That comes from the plugin's own declaration, not from its name.

manual_csv — the offline fallback. It needs no internet, no supplier account and no HTTP stack at all, and it is the supported way to run this add-on price-aware on a site with no outbound connectivity. Write a file and point price_csv_path at it:

start,eur_per_kwh,provisional
2026-01-15T00:00:00+01:00,0.1834,false
2026-01-15T01:00:00+01:00,-0.0210,true
2026-01-15T02:00:00+01:00,0.3115,false
  • start must carry its UTC offset (+01:00 in winter, +02:00 in summer). A bare 2026-01-15 00:00 is refused, because for one hour every October a local wall clock names two different moments.
  • eur_per_kwh is all-in — energy plus markup plus taxes. This plugin has no way to know what your numbers already include, so it assumes everything and adds nothing.
  • Negative prices are valid and are kept. They are the best charging hours of the year.
  • provisional is optional; omit the column and every hour is treated as settled.

When there are no prices at all — provider off, feed unreachable, CSV missing — the add-on does not guess. It reports no price data, which is a distinct state from "prices, all of them zero": the plan is marked provisional and arbitrage is disabled, per the degradation matrix. It never falls back to a price of zero, which would read as free electricity.

Injection is priced separately (export_price_eur_kwh). In Belgium it is often near zero, which by itself strongly favours self-consumption over export. It is a single number rather than a curve because no supported supplier publishes a dynamic injection tariff; negative values are accepted.

The old Home Assistant price sensors. price_now_entity and price_avg_entity still work and are unchanged: the add-on compares them and uses the result as a cheap-window hint for the maintenance charge. They are not compatible with price_provider, and not with static_profile either — configure two of them and the add-on refuses to start, naming the conflict, because the add-on reads exactly one and the loser is silent. Use one.

Static day/night and fully-fixed tariffs (static_profile)

Most Belgian households are not on a dynamic contract, and an EMS that only works under hourly pricing is an EMS for a minority. static_profile is how a two-period day/night tariff or a single fixed price becomes a first-class configuration rather than "turn the price feature off and hope".

It is one option, holding a JSON object, on one line:

{"periods": [
  {"name":"day",   "from":"07:00","to":"22:00","days":"mon-fri","eur_per_kwh":0.34},
  {"name":"night", "from":"22:00","to":"07:00","days":"mon-fri","eur_per_kwh":0.26},
  {"name":"night", "from":"00:00","to":"24:00","days":"sat,sun", "eur_per_kwh":0.26}]}

A fully fixed tariff is one period covering the whole week:

{"periods": [
  {"name":"fixed","from":"00:00","to":"24:00","days":"all","eur_per_kwh":0.31}]}
  • eur_per_kwh is all-in — energy plus your supplier's markup plus taxes — exactly like manual_csv. price_markup_eur_kwh and price_taxes_eur_kwh are not added to it.
  • days takes mon…sun, ranges (mon-fri, fri-mon), comma lists (sat,sun) and the words weekday, weekend, all.
  • Times are local Belgian time and windows are half-open: 07:00–22:00 includes 07:00 and excludes 22:00. A window may cross midnight.
  • The clock changes twice a year and the add-on handles it. It generates prices against absolute instants, so a spring-forward day is 23 hours and an autumn-back day is 25.

⚠️ A window belongs to the day the clock reads, not the day it started. 22:00–07:00 on mon-fri covers Friday 23:00 but not Saturday 03:00 — Saturday 03:00 is Saturday's. That is why the example above has a third row for the weekend. Leave it out and the add-on refuses to start, naming the uncovered hours.

Every day type must be covered exactly once. The periods have to tile all seven days with no gap and no overlap, and the add-on checks that at startup. A gap is refused rather than filled in, because a made-up price is one the optimiser would trade on; an overlap is refused because otherwise one of the two prices silently wins on the order you typed them in.

What it changes today. The add-on works out which window you are in and whether that window is cheap — strictly below the tariff's seven-day average. The Web UI shows both on a new Tariff row, and the maintenance cycle's cheap-window grid top-up uses it, which is exactly the "shift load into the cheap window" behaviour a day/night tariff asks for. Nothing else moves energy on a price yet.

Under a fully fixed tariff every hour equals the average, so there is no cheap window by construction and the add-on runs self-consumption only — which is the correct behaviour for that product, not a limitation. Peak shaving, the capacity-tariff tracker, the reserve floor and the maintenance schedule are all unaffected: the capacity tariff is a network cost charged whatever your energy contract is.

Recommended even on a dynamic contract. When a price feed is unreachable the add-on falls back to your static profile, marks the plan provisional and disables arbitrage. With static_profile empty there is nothing to fall back to, and the site simply has no tariff until the feed returns. It is not required — the add-on warns rather than refusing — but filling it in is what makes that fallback work.

Price arbitrage (arbitrage_enabled)

§10.1 priority 3: charge in the cheapest published hour, discharge in the dearest, and only when the spread covers what the round trip costs. Off by default — this is the first strategy in the add-on that commands the battery against the meter on purpose, so it is armed deliberately or not at all.

option meaning
arbitrage_enabled false by default. Arms the strategy
cycle_cost_threshold_eur What one full round trip costs per kWh — pack wear plus conversion losses. A spread below this is not traded
arbitrage_soc_floor The reserve arbitrage may not spend, %
arbitrage_soc_ceiling The headroom it may not overfill, %

What it needs, and what the add-on refuses. Arbitrage requires a price source (price_provider or static_profile) and a P1 meter (meter_source). Without a price source there is nothing to tell cheap from expensive; without P1 the capacity-tariff peak guard never runs, and §9.1 puts peak shaving above arbitrage — a charge that nothing measures is exactly what that guard exists to prevent. Both combinations are refused at startup rather than left looking armed.

Peak shaving always wins. The strategy cannot obtain a spread at all without first answering whether the peak guard is holding, and even if it could, the guard's floor is filed at a higher arbiter priority and clamps an arbitrage charge. Discharging is never capped by it — only offtake is billed.

It never exports into a negative price (§17). A negative hour is the best possible hour to charge in and that is still allowed; selling into one gives energy away and pays for the privilege.

At the shipped threshold a static day/night site does not trade. The realistic Belgian day/night spread is about 0.08 EUR/kWh and the default threshold is 0.10, so the honest answer on such a site is "no opportunity", and the status page says so with the numbers. Whether 0.10 is the right default is a product decision, not a bug: lower it only if you know what a cycle costs your pack.

The prices are fetched in the background, never on the control tick — a supplier's TLS timeout on that path would be a supplier able to push the add-on towards the firmware's 30 s failsafe. The plan refreshes every 30 minutes and retires itself if the refresh stops answering, at which point arbitrage stops with it.

Site

option meaning
estop_fitted Whether the RS485 e-stop is installed. Drives the warning banner
log_level trace/debug/info/warning/error

The Web UI

The ingress panel shows live values, why the controller is commanding what it is, and a Commissioning checklist that names any problem in words. It also carries the three buttons: start/stop control, force a maintenance cycle, and abort one.

Since UX-02 it has a second page, Configuration — see There are TWO places to configure this add-on, above. ⚠️ It adds nothing you can do to the inverter. The configuration page reads and writes the add-on's own settings and can restart the add-on; the set of commands that reach the hardware is exactly the three buttons it always had.

Status entities

If an MQTT broker is available the add-on publishes setpoint, grid power, battery power, circulating power, state of charge, maintenance phase and controller status by MQTT discovery. This is observability only — the controller works fine without a broker, and MQTT problems can never affect control.