glenn schrooyenandClaude Opus 5 aae74d7571 SAFETY-12 review: name the safety claim that could not fire, and fix two figures
Review fixes.

A. test_loop.py takes 73 s, not the ~35 s claimed in three places. That number
is the whole defence against a future developer deleting a slow test, so it was
understated by 2x in exactly the place it matters. Corrected - and it is now
~95 s (measured 93 s), because this commit adds the scenario below rather than
trimming windows to make an inconvenient number smaller. Both call sites carry
an instruction to re-measure if the windows change.

B. "242 checks" was test_p1's own count quoted as the total for all five
suites. The real figure is 395 across the five, plus 14 here.

And the finding this PR should have led with. stale_input_s and the
`inputs missing -> 0 W` claim both live INSIDE cycle(), so pre-fix, on a meter
whose value happened to repeat, that claim could not fire at all. Constant
meter, SoC entity dying at t=4 s, one binary:

  pre-fix   final target 220.0 W, reason 'loop -> 220 W'
  post-fix  final target   0.0 W, reason 'safety -> 0 W'

The old controller held 220 W through the whole input outage with its status
line still reading loop -> 220 W, and layer 1 does not cover that on a
`meter_source: off` install - no P1 age sensor is published, so the firmware has
nothing to veto on, while the heartbeat keeps its watchdog fed. The pre-fix
behaviour was not "holds a stale command safely"; it was a failsafe a repeating
meter switched off. Asserted in test_loop.py, both halves.

Three points of reasoning tightened, none of them wrong before:

- the re-tune is unreachable by construction, not merely by the reset: the
  combined cycle rate is max(arrival rate, 1/floor), never the sum, and 1/15 s
  is strictly slower than the ~1/5 s arrival rate. That holds only while the
  floor exceeds the meter's update interval - and the schema minimum of 5 s is
  exactly the reference meter's interval. Flagged for validate.py, not fixed
  here.
- the ~11 s lower bracket is not only a dropped poll: a 5.0 s poller against a
  4.97 s meter beats, so about every 14 minutes the poller steps over an update
  entirely. Reaching 15 s takes a beat-skip AND a failed poll.
- the "freshness is decided upstream" guarantee is transport-conditional. On
  `meter_source: off` the grid figure comes straight from hass.number() with no
  age gate. Running the full law is still right; the claim is narrower than it
  was stated.

The 15 s default is not independently justified - it rests on the firmware's
30 s ingest veto and moves if that ever does. Said beside the constant.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-28 21:14:58 +02:00

214 lines
8.8 KiB
Python

"""Runnable check for the control loop's cadence. `python3 test_loop.py`
SAFETY-12: the loop must evaluate on a clock as well as on a change. Before the
fix, `run_control()` ran `cycle()` only when the meter value differed from the
previous poll, so a meter that repeats a value ran NO control cycles while the
heartbeat kept re-emitting the last command - measured on the rig during TEL-05
as 70 s at a literally constant 350.0 W with 14 arrivals and zero cycles.
⚠️ THIS TEST TAKES ~95 SECONDS OF WALL CLOCK (measured 93 s), on purpose, and
that figure is the only thing standing between it and a future developer who
decides a slow test is a broken one. The thing under test is a wall-clock floor
inside a loop that sleeps 1 s; mocking the clock would leave the assertion
testing the mock. It drives the real `run_control()` and counts what actually
happened. Eight runs of the real loop is what the eight scenarios cost.
⚠️ If you shorten the windows, re-measure and update this number and the one in
HANDOVER.md. An understated runtime reads as a hang.
`cycle_floor_s` is read from options with no lower bound in code, so a huge
value reproduces the pre-fix behaviour exactly. Every claim below is therefore
an A/B on one binary, not a comparison against a remembered old one.
"""
import asyncio
import sys
import time
from app.main import Controller
fails = []
NEVER = 1e9 # cycle_floor_s so large the floor can never elapse: pre-fix
def check(name, cond):
print(f" {'ok ' if cond else 'FAIL'} {name}")
if not cond:
fails.append(name)
class FakeHass:
"""A scripted meter and a plant that tracks the command instantly."""
def __init__(self, meter, soc_dies_at=None):
self.meter = meter
self.soc_dies_at = soc_dies_at
self.batt = 0.0
self.writes = []
self.t0 = time.monotonic()
async def limits(self, entity):
return (-5000.0, 5000.0, 1.0)
async def number(self, entity, invert=False):
now = time.monotonic() - self.t0
if entity == "sensor.grid":
return self.meter(now)
if entity == "sensor.batt":
return self.batt
if entity == "sensor.soc":
if self.soc_dies_at is not None and now >= self.soc_dies_at:
return None
return 50.0
return None
async def set_number(self, entity, value):
self.writes.append(float(value))
self.batt = float(value)
return True
class _Store:
data = {}
def set(self, *a):
pass
class _Pub:
enabled = False
def publish(self, *a, **k):
pass
def close(self):
pass
BASE = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 2000, "gain": 0.6, "slew_w": 1000,
"deadband_w": 15, "target_grid_w": -10, "step_w": 10,
"heartbeat_s": 10, "stale_input_s": 15}
def drive(meter, floor, seconds, soc_dies_at=None, **over):
"""Run the real control loop for `seconds`; return (cycle times, writes)."""
async def go():
hass = FakeHass(meter, soc_dies_at)
c = Controller(dict(BASE, cycle_floor_s=floor, **over), hass, _Store(),
_Pub(), stop=asyncio.Event())
c.auto = True
stamps = []
real = c.cycle
async def counted():
stamps.append(time.monotonic() - hass.t0)
await real()
c.cycle = counted
task = asyncio.create_task(c.run_control())
await asyncio.sleep(seconds)
c.stopping = True
await asyncio.wait_for(task, timeout=10)
return stamps, hass.writes, c.target, c.reason
return asyncio.run(go())
def worst_gap(stamps, seconds):
"""Longest stretch with no cycle, including the tail after the last one."""
edges = [0.0] + list(stamps) + [seconds]
return max(b - a for a, b in zip(edges, edges[1:]))
# --------------------------------------------------------------------------- #
print("a meter that repeats the same value")
FLAT = lambda t: 350.0 # noqa: E731
FLOOR, SECONDS = 3.0, 12.0
pre_stamps, pre_writes, _, _ = drive(FLAT, NEVER, SECONDS)
# The defect itself, demonstrated rather than described: one cycle at startup
# and then nothing for the rest of the window, while writes keep happening.
check("pre-fix: a constant meter runs exactly one cycle, at startup",
len(pre_stamps) == 1)
check("...while the heartbeat keeps writing anyway, so nothing looks wrong",
len(pre_writes) >= 2)
post_stamps, post_writes, _, _ = drive(FLAT, FLOOR, SECONDS)
check("post-fix: the same constant meter runs cycles throughout",
len(post_stamps) >= int(SECONDS / FLOOR) - 1)
# The actual acceptance criterion: a BOUND on the gap, not a count.
gap = worst_gap(post_stamps, SECONDS)
check(f"...with no gap longer than the floor ({gap:.1f}s <= {FLOOR + 1.5:.1f}s)",
gap <= FLOOR + 1.5)
check("...and the loop actually corrected, instead of holding a stale command",
len(post_writes) > len(pre_writes))
# --------------------------------------------------------------------------- #
print("a meter that changes normally - nothing may move")
# ⚠️ THE REGRESSION GUARD, and the more important half. The floor is a deadline
# on the gap between cycles, reset by every cycle whichever trigger fired - not
# a second scheduler. On a healthy meter it must never elapse, so the cycle
# count, the write count and the commanded values must be IDENTICAL either side
# of the fix. Anything else is a new write cadence, which SAFETY-12 forbids:
# the deadband, step_w and the 10 s force-write decide what reaches the wire,
# and this change is only allowed to alter when the loop thinks.
STEPS = [0.0, 300.0, 850.0, -400.0, 120.0, -900.0, 60.0]
LIVE = lambda t: STEPS[int(t // 2) % len(STEPS)] # noqa: E731
a_stamps, a_writes, _, _ = drive(LIVE, NEVER, 12.0)
b_stamps, b_writes, _, _ = drive(LIVE, FLOOR, 12.0)
check("a changing meter runs the same number of cycles as before the fix",
len(a_stamps) == len(b_stamps))
check("...commanding exactly the same sequence of values", a_writes == b_writes)
# --------------------------------------------------------------------------- #
print("a meter parked at the target - the converged operating point")
# The case TEL-05 warned about: at the converged target the power figure
# legitimately repeats for minutes. The loop must still run, and must still
# write nothing but the heartbeat, because the deadband - not the arrival
# trigger - is what holds the command still.
AT_TARGET = lambda t: -10.0 # noqa: E731
c_stamps, c_writes, _, _ = drive(AT_TARGET, NEVER, 12.0)
d_stamps, d_writes, _, _ = drive(AT_TARGET, FLOOR, 12.0)
check("the loop evaluates at the converged point too", len(d_stamps) > len(c_stamps))
check("...and the deadband still holds the command, so writes are unchanged",
d_writes == c_writes)
# --------------------------------------------------------------------------- #
print("an input dies while the meter repeats - the safety claim must still fire")
# ⚠️ THE STRONGEST PROPERTY IN SAFETY-12, and the one that makes it a safety fix
# rather than a latency fix. The `inputs missing -> 0 W` claim lives INSIDE
# cycle() (main.py, the stale_input_s branch and the P_SAFETY claim below it).
# Pre-fix, on a meter whose value happened to repeat, cycle() was never called
# again - so that claim could not fire AT ALL. The controller held its last
# command through an input outage of unbounded length with the status line still
# reading "loop -> N W".
#
# Layer 1 does not cover this either on a `meter_source: off` install: no P1 age
# sensor is published (see Controller.publish), so the firmware has nothing to
# veto on, and the heartbeat keeps its watchdog fed the whole time.
#
# stale_input_s is shortened to 3 s here so the outage resolves inside a test
# rather than inside a quarter of a minute. The mechanism is the default one.
c2_stamps, c2_writes, pre_target, pre_reason = drive(
FLAT, NEVER, 10.0, soc_dies_at=4.0, stale_input_s=3)
check("pre-fix: a dead input during a constant meter never reaches the safety claim",
pre_target != 0.0 and "safety" not in pre_reason)
check(f"...so it holds its last command instead ({pre_target:g} W, {pre_reason!r})",
pre_target == 220.0)
d2_stamps, d2_writes, post_target, post_reason = drive(
FLAT, FLOOR, 10.0, soc_dies_at=4.0, stale_input_s=3)
check("post-fix: the same outage commands 0 W", post_target == 0.0)
check(f"...through the safety claim, not by accident ({post_reason!r})",
"safety" in post_reason)
check("...and the 0 W actually reached the device", 0.0 in d2_writes)
# --------------------------------------------------------------------------- #
print()
if fails:
print(f"{len(fails)} FAILED: " + "; ".join(fails))
sys.exit(1)
print("all checks passed")